3)  Marking & Rating Information 

 

The GNExCP7-BG Call Points comply with the following standards 
for hazardous locations:  

 

3.1 

Class/Division Ratings for US & Canada 

 

Standards 

UL 60079-0:2020 (Ed 7): Explosive Atmospheres - Part 0: Equipment - 
General requirements  
UL 60079-11:2023 (Ed6): Explosive Atmospheres - Part 1: Equipment 
protection by Intrinsic Safety 
 
CSA C22.2 NO. 60079-0: 2019 (Ed 4) Explosive Atmospheres – Part 0: 
Equipment – General requirements  
CSA C22.2 NO. 60079-11:2014 (Ed 3): Explosive Atmospheres – Part 11: 
Equipment protection by Intrinsic Safety 

Class Division Ratings for US (NEC) & Canada (CEC) 

Model No: 

Rating 

GNExCP7-BG-I 
 

 

Class I Div 1 Group ABCD T6 Ta -55°C to 
+70°C 

GNExCP7-BG-IR 

Class I Div 1 Group ABCD T4 Ta -55°C to 
+70°C 

Class Zone Ratings for US (NEC)

 

Model No:

 

Rating

 

GNExCP7-BG-I 

Class I Zone 0 AEx ia IIC T6 Ga Ta -55°C 
to +70°C 
 

GNExCP7-BG-IR 

Class I Zone 0 AEx ia IIC T4 Ga Ta -55°C 
to +70°C 
 

Class Zone Ratings for Canada (CEC)

 

Model No:

 

Rating

 

GNExCP7-BG-I 

Ex ia IIC T6 Ga Ta –55°C to +70°C 
 

GNExCP7-BG-IR 

Ex ia IIC T4 Ga Ta –55°C to +70°C 
 

Installation must be carried out in compliance with the National Electric 
Code / Canadian Electric Code 

 
 

3.2 

ATEX / IECEx & UKEx Ratings 

 

Standards 

EN60079-0:2018/IEC60079-0:2017 (ed.7): Explosive Atmospheres - 
Equipment General Requirements. 
EN60079-11:2012/IEC60079-11:2019 (ed.6): Explosive Atmospheres - 
Equipment Protection by Intrinsically Safe Enclosures “ia”.

 

Model No: 

Rating 

GNExCP7-BG-I 

 

Ex ia IIC T6 Ga Ta –55°C to +70°C 
 

GNExCP7-BG-IR 

Ex ia IIC T4 Ga Ta –55°C to +70°C 
 

See Product table for electrical ratings of each unit model 

 
Certificate No.    

DEMKO 19 ATEX 2101X 
IECEx ULD 19.0007X  
UKEx UL UL21UKEX2134X          

Epsilon x 
Equipment Group 
and Category: 

 

II 2G 
II 2D

 

CE Marking and 
Notified Body No. 

 

2813 

UKCA Marking and 
Notified Body No. 

 

 

0518 

 

3.3 

DNV Type Approval 

 

The units have been tested and approved for the installation 
on ships in the following locations: 
 

Temperature

:   Class A,B,C & D (all locations including 

open decks and masts) 

Humidity:

 

Class A & B (all locations) 

Vibration:

 

Class A (all locations except installation on 
machinery such as combustion engines, 
compressors, pumps, including piping on 
such machinery) 

EMC:

 

Class A & B (all locations including open 
decks and bridge) 

Enclosure:

 

Class A, B & C – IP56 (all locations except 
submerged applications and bilges) 

 
 
 

3.4 

UL 60947 Approval 

 

 

 
All models are approved for use as Alarm System use: 
 
UL 60947-4-1 LOW-VOLTAGE SWITCHGEAR AND 
CONTROLGEAR - PART 4-1: CONTACTORS AND 
MOTORSTARTERS - ELECTROMECHANICAL 
CONTACTORS AND MOTOR-STARTERS- Edition 3 - 
Revision Date 2017/10/17 
 
CSA C22.2 NO. 60947-4-1-14 LOW-VOLTAGE 
SWITCHGEAR AND CONTROLGEAR — PART 4-1: 
CONTACTORS AND MOTOR-STARTERS — 
ELECTROMECHANICAL CONTACTORS AND MOTOR-
STARTERS- Edition 2 - Issue Date 2014/01/04 
 
UL 60947 Ambient Temperature Range: -55°C to +60°C  

 

For Indoor and Outdoor Use 
Pour usage Interier INTÉRIEUR 

 
 
 
 
 
 
 
 
 
 
 
 
 
 

Содержание GNExCP7-BG-I

Страница 1: ...8 743 8880 Document No D202 00 501 IS Issue 1 28 01 2024 Sheet 1 of 9 GNExCP7 BG I GNExCP7 BG IR 1 Product Table Unit Type Code Input Parameters GNExCP7 BG I GNExCP7 BG IR Ui 30V Ii 500mA Pi 1100mW Ci...

Страница 2: ...atings Standards EN60079 0 2018 IEC60079 0 2017 ed 7 Explosive Atmospheres Equipment General Requirements EN60079 11 2012 IEC60079 11 2019 ed 6 Explosive Atmospheres Equipment Protection by Intrinsica...

Страница 3: ...uit and parts which may be earthed This shall be considered in the end use application to ensure the possibility of an earth connection will not compromise intrinsic safety Use galvanically isolating...

Страница 4: ...x certified Zener barrier or galvanic isolator which have output parameters equal to or less than 30V 500mA and 1100mW where Io is resistively limited The cable parameters stated on the selected Zener...

Страница 5: ...n and allows for the wiring of switches only Model GNExCP7 BG I For full wiring details see wiring diagrams D202 06 501 The PCB Terminal Version has a 6 way connector but is designed to allow for full...

Страница 6: ...iclockwise 90 to its original vertical position The glass element should now raise up so it is level again horizontal in the viewable window Replace the cover plate and tighten the 4 off M4 cap head s...

Страница 7: ...tions inspections and maintenance For US CEC Class Div Zone UL 60079 19 Explosive atmospheres Equipment repair overhaul and reclamation UL 60079 17 Explosive atmospheres Electrical installations inspe...

Страница 8: ...ween open circuit voltage and short circuit current 2 Installed should be in accordance with its manufacturer s control drawing and Article 504 of the National Electrical Code ANSI NFPA 70 for Canadia...

Страница 9: ...le stage call point alarm using single galvanic isolator 1 Associated apparatus output current must be limited by a resistor such that the output voltage current plot is a straight line drawn between...

Страница 10: ...IS THE COPYRIGHT PROPERTY OF EUROPEAN SAFETY SYSTEMS LTD NEITHER THE WHOLE OR ANY EXTRACT MAY BE DISCLOSED LOANED COPIED OR USED FOR DRAWING TO BS8888 2000 GEOMETRIC TOLERANCES TO ISO1101 1983 Introd...

Страница 11: ...R N Exxxx Sxxxx Single PCB Version With EOL Series NO LED EOL Series S P W N Exxxx Sxxxx Single PCB Version Alt EOL Pos n NO LED EOL Series SHEET 1 PRODUCTS GNExCP7 STExCP8 WP7 S P R N SWITCH TYPE s...

Страница 12: ...rance Notification Module D SIRA 05 ATEX M342 Provisions fulfilled by the equipment II 1G Ex ia IIC T6 T4 Ga Standards applied EN 60079 0 2018 EN 60079 11 2012 Directive 2014 30 EU Electromagnetic Com...

Страница 13: ...ion Module D CSAE 22UKQAN0046 Provisions fulfilled by the equipment II 1G Ex ia IIC T6 T4 Ga Standards applied EN 60079 0 2018 EN 60079 11 2012 Directive 2014 30 EU Electromagnetic Compatibility Direc...

Отзывы: