E2S GNExCP7-BG-I Скачать руководство пользователя страница 13

 

 
 

 
 
 
 
 
 
 
 
E2S Telephone: +44 (0)20 8743 8880 Fax: +44 (0)20 8740 4200 Email: sales@e2s.com 

www.e2s.com 

DC-117_Issue_A - Page 1 of 1 - QAF_252_Issue_5

 

 
 
 

Martin Streetz 

Document No.: 

DC-117_Issue_A 

Quality Assurance Manager 

Date and Place of Issue: 

London, 29/02/2024 

UKCA Declaration of Conformity 

Manufacturer:   

 

European Safety Systems Ltd. 

 

 

 

Impress House, Mansell Road, Acton 

 

 

 

London, W3 7QH 

  

 

United 

Kingdom 

 
Equipment Type:  

 

GNExCP7-BG-I, GNExCP7-BG-IR 

 

 

 

GNExCP7-PB-I, GNExCP7-PM-I, GNExCP7-PT-I, 

 

 

 

GNExCP7-PB-IR, GNExCP7-PM-IT, GNExCP7-PT-IR, 

 

Directive  UKSI 2016:1107 (as amended by UKSI 2019:696) – Schedule 3A, Part 1 : Product or Protective System Intended for use in Potentially Explosive Atmospheres  
(UKCA) 

Notified Body for UK type Examination (Module B): 

UL International (UK) Ltd 
Notified Body No.: 0843 
Unit 1-3 Horizon Kingsland Business Park, Wade Road, 
Basingstoke, Hampshire RG24 8AH UK 

UK-type Examination Certificate (Module B): 

UL21UKEX2134X 

Notified Body for Quality Assurance Notification / Conformity to EU-type 
based on quality assurance of the production process (Module D): 

Sira Certification Service 
Notified Body No.: 0518 
Rake Lane, Eccleston, Chester CH4 9JN, UK 

Quality Assurance Notification (Module D): 

CSAE 22UKQAN0046 

Provisions fulfilled by the equipment: 

II 1G Ex ia IIC T6…T4 Ga 

Standards applied: 

EN 60079-0:2018 
EN 60079-11:2012 

Directive 2014/30/EU: Electromagnetic Compatibility Directive (EMC)  

Standards applied: 

EN 61000-6-1:2007 
EN 61000-6-2:2005 
EN 61000-6-3:2007 / A1:2011 / AC: 2012 
EN 61000-6-4:2007 / A1: 2011 

Directive 2011/65/EU: Restriction of the use of certain hazardous substances in electrical and electronic equipment (RoHS) 

The product and all the components contained within it are in accordance with the restriction of the use of hazardous substances in electrical and electronic 
equipment, including amendment by Directive 2015/863/EU.

 

Regulation (EC) 1907/2006: Registration, Evaluation, Authorisation and Restriction of Chemicals (REACH) 

The product and all the components contained within it are free from substances of very high concern. 

Other Standards and Regulations 

EN 60529:1991 + A1:2000 + A2:2013. - Degrees of protection provided by enclosures (IP code) – enclosure rated IP66/67/68 

 

On behalf of European Safety Systems Ltd., I declare that, on the date the equipment accompanied by this declaration is placed on the market, the equipment 
conforms with all technical and regulatory requirements of the above listed directives, regulations and standards. 
 
This Declaration is issued under the sole responsibility of the manufacturer.

 

Содержание GNExCP7-BG-I

Страница 1: ...8 743 8880 Document No D202 00 501 IS Issue 1 28 01 2024 Sheet 1 of 9 GNExCP7 BG I GNExCP7 BG IR 1 Product Table Unit Type Code Input Parameters GNExCP7 BG I GNExCP7 BG IR Ui 30V Ii 500mA Pi 1100mW Ci...

Страница 2: ...atings Standards EN60079 0 2018 IEC60079 0 2017 ed 7 Explosive Atmospheres Equipment General Requirements EN60079 11 2012 IEC60079 11 2019 ed 6 Explosive Atmospheres Equipment Protection by Intrinsica...

Страница 3: ...uit and parts which may be earthed This shall be considered in the end use application to ensure the possibility of an earth connection will not compromise intrinsic safety Use galvanically isolating...

Страница 4: ...x certified Zener barrier or galvanic isolator which have output parameters equal to or less than 30V 500mA and 1100mW where Io is resistively limited The cable parameters stated on the selected Zener...

Страница 5: ...n and allows for the wiring of switches only Model GNExCP7 BG I For full wiring details see wiring diagrams D202 06 501 The PCB Terminal Version has a 6 way connector but is designed to allow for full...

Страница 6: ...iclockwise 90 to its original vertical position The glass element should now raise up so it is level again horizontal in the viewable window Replace the cover plate and tighten the 4 off M4 cap head s...

Страница 7: ...tions inspections and maintenance For US CEC Class Div Zone UL 60079 19 Explosive atmospheres Equipment repair overhaul and reclamation UL 60079 17 Explosive atmospheres Electrical installations inspe...

Страница 8: ...ween open circuit voltage and short circuit current 2 Installed should be in accordance with its manufacturer s control drawing and Article 504 of the National Electrical Code ANSI NFPA 70 for Canadia...

Страница 9: ...le stage call point alarm using single galvanic isolator 1 Associated apparatus output current must be limited by a resistor such that the output voltage current plot is a straight line drawn between...

Страница 10: ...IS THE COPYRIGHT PROPERTY OF EUROPEAN SAFETY SYSTEMS LTD NEITHER THE WHOLE OR ANY EXTRACT MAY BE DISCLOSED LOANED COPIED OR USED FOR DRAWING TO BS8888 2000 GEOMETRIC TOLERANCES TO ISO1101 1983 Introd...

Страница 11: ...R N Exxxx Sxxxx Single PCB Version With EOL Series NO LED EOL Series S P W N Exxxx Sxxxx Single PCB Version Alt EOL Pos n NO LED EOL Series SHEET 1 PRODUCTS GNExCP7 STExCP8 WP7 S P R N SWITCH TYPE s...

Страница 12: ...rance Notification Module D SIRA 05 ATEX M342 Provisions fulfilled by the equipment II 1G Ex ia IIC T6 T4 Ga Standards applied EN 60079 0 2018 EN 60079 11 2012 Directive 2014 30 EU Electromagnetic Com...

Страница 13: ...ion Module D CSAE 22UKQAN0046 Provisions fulfilled by the equipment II 1G Ex ia IIC T6 T4 Ga Standards applied EN 60079 0 2018 EN 60079 11 2012 Directive 2014 30 EU Electromagnetic Compatibility Direc...

Отзывы: