European Safety Systems Ltd.

  Impress House, Mansell Road, Acton, London W3 7QH 

 

 

 

 

 

 

 

www.e2s.com  Tel: +44 (0)208 743 8880 

Document D154-00-155-IS   Issue 8  12-09-2022 

 

 

Sheet 1 of 3 

 

 

 

 

 

INSTRUCTION MANUAL  

GNExCP6C-PB Button Manual Call Point 

For use in Flammable Gas and Dust Atmospheres 

 

 

 

GNExCP6C-PB

 

Manual Call Point – Push Button 
With Resistor Modules 

For use in Flammable Gas and 
Combustible Dust Atmospheres. 
 
 
 

 

 
 

 

1) 

Introduction 

The  GNExCP6C-PB  is  a  push  button  manual  call 
point  which  is  certified  to  the  European  and 
International  Gas  and  Dust  standards.  The  unit 
meets  the  requirements  of  the  ATEX  directive 
2014/34/EU, IECEx and UKEX schemes. 
 
The  call  point  can  be  used  in  hazardous  areas 
where  potentially  flammable  gas  and  dust 
atmospheres may be present. 
 
All units have up to two of the following: 

 

Monitoring resistors up to 1.5W per module 

 

Monitoring diode 

 

Monitoring Zener diode 

Units  may  also  incorporate  an  LED  indicator  in 
addition  to  the  two  series  and/  or  EOL  devices 
allowed. 
 
The units are  Group II, EPL (equipment protection 
level) Gb. The equipment is certified ‘Ex db eb mb 
IIC  T4  Gb’  and  as  such  may  be  used  in  Zones  1 
and 2 with flammable gases and vapours with gas 
groups  IIA,  IIB  &  IIC  and  temperature  classes  T1, 
T2, T3 and T4. 

 
These  units  are  also  Group  III,  EPL  Db.  The 
equipment is certified ‘Ex tb IIIC T75ºC Db’ and as 
such  may  be  used  in  Zones  21  and  22  for 
combustible dusts groups IIIA, IIIB & IIIC. 
 

2) 

Ratings & Markings 

All  units  have  a  rating  label,  which  carries  the 
following important information: - 

 

Unit Type No.: 
GNExCP6C-PB Manual Call Point 
 
Input Voltages: 

Important: 

See section 7.1 for current ratings 

 

125VDC Max    0.5A Max. Resistive Load;  

       0.03A Max Inductive Load 

75VDC Max      0.75A Max 
48VDC Max      1.0A Max 
24VDC Max      5.0A Max Resistive Load; 

       3.0A Max Inductive Load 

12VDC Max      5.0A Max 
6VDC Max        5.0A Max 
 
Code: 
GNExCP6C-PB 

      

Ex db eb mb IIC T4 Gb      
Ex tb IIIC T75ºC Db 

      

IP66 

 

      

–40ºC <= Ta <= +65ºC      
 
Certificate No.: 
SIRA 09ATEX3286X 
IECEx SIR 09.0121X 
CSAE 21UKEX3556X 
 
Epsilon x:                         II 2GD 
 
 
CE Marking 
Notified  

  

2813 

Body No.               
 
UKCA Marking 
Notified Body No.

 

0518 

 
 
Year/Serial No. i.e. 20/1CP6CPB000001    
 
WARNING - DO NOT OPEN WHEN AN 
EXPLOSIVE ATMOSPHERE MAY BE PRESENT, 
ELECTROSTATIC HAZARD – CLEAN ONLY 
WITH A DAMP CLOTH 
 

 

3) 

Type Approval Standards 

The  call  point  has  an  EC  Type  examination 
certificate issued by SIRA and have been approved 
to the following standards: - 
 
EN60079-0:2018 / IEC60079-0:2017 
EN60079-1:2014 / IEC60079-1:2014 
EN60079-7:2015 / IEC60079-7:2017 
EN60079-18:2015 / IEC60079-18:2014 
EN60079-31:2014 / IEC60079-31:2013 
 
The equipment is certified for use in ambient 
temperatures in the range: 
GNExCP6C-PB -40

o

C to +65

o

C  

and shall not be used outside this range. 
 

4) 

Installation Requirements 

 
Installation  of  this  equipment  shall  only  be  carried 
out  by  suitably  trained  personnel  in  accordance 
with the applicable code of practice e.g.  
IEC 60079-14/EN 60079-14  
 
Repair of this equipment shall only be carried out 
by the manufacturer or in accordance with the 
applicable code of practice e.g. IEC 60079-19/EN 
60079-19. 
 
Refer  to  certificates  SIRA  09ATEX3286X,  IECEx 
SIR  09.0121X  and  CSAE  21UKEX3556X  for 
special conditions of safe use. 
 
The  certification  of  this  equipment  relies  on  the 
following materials used in its construction: 
 
Enclosure:

 

GRP - Glass Reinforced Polyester 

 
Through enclosure mechanism: Plastic Nylon Zytel 
Injection Moulded 
 
Sealing  of  enclosure  and  mechanism:  O-ring 
Acrylonitrile-Butadiene Rubber  
 
Potting Compound of resistors where  used: Epoxy 
Resin 
 
If the  equipment is likely to come into  contact with 
aggressive substances,  then it is the responsibility 
of the user to take suitable precautions that prevent 
it from being adversely affected, thus ensuring that 
the type of protection is not compromised. 
 
 
 

 
“Aggressive substances” - e.g. acidic liquids, gases 
or solvents that may affect polymeric materials. 
 
“Suitable precautions” - e.g. regular checks as part 
of  routine  inspections  or  establishing  from  the 
material’s  data  sheet  that  it  is  resistant  to  specific 
chemicals. 
 
Under extreme conditions the unit may generate an 
ignition-capable  level  of  electrostatic  charges.  The 
unit must not be installed in a location where it may 
be  subjected  to  external  conditions  (such  as  high-
pressure  steam)  which  may  cause  a  build-up  of 
electrostatic charges on non-conducting surfaces.  
 
Cleaning of the unit must only be carried out with a 
damp cloth. 
 

5) 

Call Point Location and Mounting 

The location of the call point should enable ease of 
access  for  operation  and  testing.  The  unit  should 
be  mounted  using  the  4  off  fixing  holes  which  will 
accept up to M5 sized fixings. 
 

 

 

 

 

 
 

 

View of base unit showing fixing centres (in mm). 
 
To  gain  access  to  the  mounting  holes  in  the  base 
the front cover must be removed.  
 
This  is  achieved  by  removing  the  4  off  M4  cap 
head 

bolts 

holding 

on 

the 

cover.

 

Содержание GNExCP6C-PB

Страница 1: ...by SIRA and have been approved to the following standards EN60079 0 2018 IEC60079 0 2017 EN60079 1 2014 IEC60079 1 2014 EN60079 7 2015 IEC60079 7 2017 EN60079 18 2015 IEC60079 18 2014 EN60079 31 2014...

Страница 2: ...ent Limitations The maximum allowable current is determined as the smallest value from the following scenarios 1 When both module resistor values are the same as or above the minimum range of values s...

Страница 3: ...EC EN61508 which has been assessed and is considered suitable for use in low demand safety function Random Hardware Failures and Systematic Failures route 2H As an unvoted item i e hardware fault tole...

Страница 4: ...DED CONFIG 8 AND 12 ADDED LED ONLY CONFIG 13 REMOVED CONFIGS RE NUMBERED 1 TO 24 4 warning signals Circuit shown in Unoperated condition Unoperated condition Glass Intact Standby Condition Terminals 2...

Страница 5: ...cuit shown in Unoperated condition Unoperated condition Glass Intact Standby Condition Terminals 1 2 M S 1 and 4 5 M S 2 open Terminals 1 3 M S 1 and 4 6 M S 2 closed Operated condition Glass Broken B...

Страница 6: ...ng signals Circuit shown in Unoperated condition Unoperated condition Glass Intact Standby Condition Terminals 2 3 4 5 open Terminals 2 3 6 closed Operated condition Glass Broken Button pushed in Term...

Страница 7: ...he LED current limiting resistor RL1 using LED option C In all other cases RL1 is included Circuit shown in Unoperated condition Unoperated condition Glass Intact Standby Condition Terminals 2 3 M S 1...

Страница 8: ...S 1 M S 2 open Terminals 2 3 6 M S 1 M S 2 closed Operated condition Glass Broken Button pushed in Terminals 2 3 4 5 M S 1 M S 2 closed Terminals 2 3 6 M S 1 M S 2 open Circuit shown in Unoperated co...

Страница 9: ...rated condition Glass Broken Button pushed in Terminals 3 4 5 6 M S 1 M S 2 closed Terminals 3 4 7 M S 1 M S 2 open Circuit shown in Unoperated condition Unoperated condition Glass Intact Standby Cond...

Страница 10: ...surance Notification Conformity to EU type based on quality assurance of the production process Module D Sira Certification Service Notified Body No 2813 CSA Group Netherlands B V Utrechtseweg 310 681...

Страница 11: ...and electronic equipment including amendment by Directive 2015 863 EU Regulation EC 1907 2006 Registration Evaluation Authorisation and Restriction of Chemicals REACH The product and all the componen...

Страница 12: ...t GNExCP6A GNExCP6B GNExCP6C GNExCP6D GNExCP6E II 2G Ex db eb IIC T6 Gb 40 C Ta 70 C II 2D Ex tb IIIC T75 C Db 40 C Ta 70 C or II 2G Ex db eb mb IIC T4 Gb 40 C Ta 50 C II 2D Ex tb IIIC T80 C Db 40 C T...

Страница 13: ...ity Other Standards and Regulations EN 60529 1992 A2 2013 Degrees of protection provided by enclosures IP code enclosure rated IP66 On behalf of European Safety Systems Ltd I declare that on the date...

Отзывы: