E2S GNExB2X05-S Series Скачать руководство пользователя страница 6

 

European Safety Systems Ltd.

   Impress House, Mansell Road, Acton, London W3 7QH

 

www.e2s.com

 

Tel: +44 (0)208 743 8880

 

Document No. D156-00-621-IS

 

Issue 1

 

27-10-22

 

 

Sheet 6 of 15

 

 

Ingress Protection 

 
Follow instructions according to the approvals applied. 
 

ATEX / IECEx & UKEx Requirements Only 
 
If a high IP (Ingress Protection) rating is required then a 
suitable  sealing  washer  must  be  fitted  under  the  cable 
glands or blanking plugs. A minimum ingress protection 
rating  of  IP6X  must  be  maintained  for  installations  in 
explosive dust atmospheres. 
 
NEC / CEC Requirements Only 
 
If a high IP (Ingress Protection) rating is required then a 
suitable  sealing  washer  must  be  fitted  under  the  cable 
glands or blanking plugs. A minimum ingress protection 
rating  of  IP6X  must  be  maintained  for  installations  in 
explosive dust atmospheres. 

 

Adapters 

 
The GNEx Beacon Range can be supplied with the following 
types of adapters: 
 

M20 to 1/2

 NPT 

M20 to 3/4

” NPT

 

M20 to M25 

 
It  is  important  to  note  that  stopping  plugs  cannot  be  fitted 
onto adapters, only directly onto the M20 entries. 
 
Any other adapters used must be suitably rated as per the 
applicable standards. 
 

8)  Flash Pattern Settings 

 

 

 

The GNExB2 beacon can produce different flash patterns as 
shown  in  Table  4.  The  flash  patterns  are  selected  by 
operation of the flash setting DIP switch on the PCB, Fig 6. 
 
For SIL 2 operation, only the 1Hz Flash rate is approved. 
 

 

Figure 6: DIP Switch Location. 

 
 
 
 
 

 

Switch 

Setting

 

S1 Mode

 

SIL Approved 

00 

1Hz (60FPM) 

Yes 

01 

1.33Hz (80FPM) 

No 

10 

1.5Hz (90FPM) 

No 

11 

Double Flash 

No 

Table 4: Switch Positions for Flash Patterns 

 

9)  End of Line Monitoring (DC Units) 

 
All DC units have a blocking diode fitted in their supply input 
lines.  An  end  of  line  monitoring  diode  or  an  end  of  line 
monitoring resistor can be connected across the +ve and 

ve 

terminals in the flameproof chamber. If an end of line resistor 
is used it must have a minimum resistance value of 3k3 ohms 
and  a  minimum  wattage  of  0.5W  or  a  minimum  resistance 
value of 500 ohms and a minimum wattage of 2W. 
 
The resistor must be connected directly across the +ve and - 
ve terminals as shown in the following drawing. The resistor 
leads should be kept as short as possible. 
 

 

Figure 7: End of Line Resistor Placement. 

 
SIL2  line  monitoring module  product  version:  see  section  19 
for  standard  default  values  and  product  coding.  See 
document D191-06-621 for associated wiring diagram. 
 

10) Interchangeable & Spare Parts 

 

 

 

The  beacon  lens  is  interchangeable,  contact  European 
Safety  Systems  Ltd  for  a  replacement  lens  available  in 
various colours. 
 
The  guard  is  an  integral  part  of  the  protection  and  must  be 
reassembled exactly the same way as it was disassembled.  

 

To change the lens, unscrew the M5 socket head screws and 
remove the M5 screws, M5 spring & flat washers.  

 

Warning 

 

Hot surfaces. External surfaces 

and internal components may be hot after 
operation, take care when handling the 
equipment. 
 

Warning 

 high-intensity light source. Avoid 

looking directly at the light source for 
extended periods of time. 

Содержание GNExB2X05-S Series

Страница 1: ...AND CABLE GLANDS IF TEMPERATURE EXCEEDS AS PER STANDARDS INDICATIONS BELOW FOR ATEX IECEx UKEX STANDARDS 70 C AT ENTRY OR 80 C AT BRANCHING POINT FOR NEC CEC STANDARDS 60 C AT ENTRY OR 60 C AT BRANCHI...

Страница 2: ...in compliance with the National Electric Code CEC Class Zone Ratings Canada Standards CAN CSA C22 2 No 60079 0 Ed 4 02 2019 Explosive Atmospheres Part 0 Equipment General Requirements CAN CSA C22 2 N...

Страница 3: ...mented joints is not permitted Figure 1 Flame Path The enclosure is non conducting and may generate an ignition capable level of electrostatic charges under certain extreme conditions The user should...

Страница 4: ...Explosive dust atmospheres The installation of the units must also be in accordance with any local codes that may apply and should only be carried out by a competent electrical engineer who has the ne...

Страница 5: ...C or the cable branching point temperature may exceed 60 C and therefore suitable heat resisting cables and cable glands must be used with a rated service temperature at least as stated below Table 3...

Страница 6: ...P Switch Location Switch Setting S1 Mode SIL Approved 00 1Hz 60FPM Yes 01 1 33Hz 80FPM No 10 1 5Hz 90FPM No 11 Double Flash No Table 4 Switch Positions for Flash Patterns 9 End of Line Monitoring DC U...

Страница 7: ...l and Repair Maintenance repair and overhaul of the equipment should only be carried out by suitably qualified personnel in accordance with the current relevant standards EN60079 19 IEC60079 19 Explos...

Страница 8: ...and Function The SIL 2 Beacon Unit Monitors Standby mode and Active mode Health status of power supply Beacons correct function and flash pattern The SIL 2 beacon operates as part of a SIL 2 system Th...

Страница 9: ...correct the latched fault the alarm horn sounder may require further investigation please contact your local E2S representative Commissioning System Functional start up of System Normally in reverse...

Страница 10: ...hough it is highly recommended that the unit is wired as stated in section 15 1 as a 4 Wire System J1 Header Current Sense Resistor CSR Shown in factory default position A see section 15 3 places TB1...

Страница 11: ...om the circuit Note a cable short circuit will not be detectable in this configuration For one unit only Beacon power supply terminal block Current drawn mA Active Mode 190mA Standby Mode 25mA SIL2 TB...

Страница 12: ...hen no faults and faults occur If multiple SIL 2 alarm horn sounders are to be cabled in series the monitoring connections differ from that of a single beacon For more information see manual D197 00 6...

Страница 13: ...Position B pins 2 3 linked Places power supply terminal Fault Resistor RLY 1 2 in circuit As used in 2 Wire Configuration Figure 16 J2 Header pin positions Fault Resistor FR 15 4 SIL 2 Hard Reset Func...

Страница 14: ...Random Hardware Failures and Architectural constraints route 1H 2 As an unvoted item i e hardware fault tolerance of 0 at SIL 2 The product was assessed against failure modes Failure respond to an in...

Страница 15: ...be specified when ordering The values of resistors available are shown in table 6 below Code Resistor Value Default resistor coding is as follows GNExB2X05DC024AS1S1R A AFZ Example of a custom require...

Страница 16: ...ATERIAL SHEET SCALE TITLE A3 IF IN DOUBT ASK DO NOT SCALE ALL DIMENSIONS IN MM DRAWING NUMBER A B C D E F G 10 9 G F E 7 8 6 5 D C 1 3 4 2 A B D191 06 621 M ABALOS B ISARD R N POTTS OF NTS 1 1 23 09 2...

Страница 17: ...B V Utrechtseweg 310 6812 AR Arnhem Netherlands Quality Assurance Notification Module D SIRA 05 ATEX M342 Provisions fulfilled by the equipment II 2G Ex db IIC T4 T6 Gb II 2D Ex tb IIIC T80 C T138 C D...

Страница 18: ...Date and Place of Issue London 03 12 2021 EU Declaration of Conformity On behalf of European Safety Systems Ltd I declare that on the date the equipment accompanied by this declaration is placed on t...

Страница 19: ...e Lane Eccleston Chester CH4 9JN UK Quality Assurance Notification Module D CSAE 22UKQAN0046 Provisions fulfilled by the equipment II 2G Ex db IIC T4 T6 Gb II 2D Ex tb IIIC T80 C T138 C Db IP6X Dust P...

Страница 20: ...r Date and Place of Issue London 24 02 2022 UKCA Declaration of Conformity On behalf of European Safety Systems Ltd I declare that on the date the equipment accompanied by this declaration is placed o...

Отзывы: