E2S GNExB2X05-S Series Скачать руководство пользователя страница 11

 

European Safety Systems Ltd.

   Impress House, Mansell Road, Acton, London W3 7QH

 

www.e2s.com

 

Tel: +44 (0)208 743 8880

 

Document No. D156-00-621-IS

 

Issue 1

 

27-10-22

 

 

Sheet 11 of 15

 

 

15-1) SIL 2 System Wiring for Fault Detection in Standby and Active Mode 

 4 Wire Installation 

(Recommended) 

 
The customer is required to wire into both the beacon power supply terminals and also the SIL 2 Relay terminals TB1. 
 
The power supply terminals only need to have the supply power connected. This will be reverse polarity for  monitoring mode and 
normal  polarity  for  active mode.  There  is  no  need  to  fit an EOL  resistor on  the  power  supply  terminal  as  the  TB1 is  configured to 
raise a fault alarm in any situation. 
 
Terminal block TB1 is the output from the SIL 2 monitoring relay. Relay RLY 1-2 provides a closed circuit between TB1 terminals 1 & 
2 whilst powered. On detection of a fault event this will become open circuit. 
 
The fault will be seen via the SIL 2 TB1 terminals as soon as the fault occurs in either Active or Standby modes. 
 
When no fault is detected the circuit to the SIL 2 TB1  terminals 1 & 2 will include a factory fitted 3.3K Ohm current sense resistor 
(CSR) in series. When the circuit is driven with 24Vdc the detection current seen is ~7.3mA @ 24V. 
 
The only other fault mode is if the cable goes short circuit where a short will be seen by the panel.  
 

Option:

 Should the fault event output of RLY1-2 be required to operate as a switch, header J1 can be set to link pins 1 & 2 (see 

Figure 13) thereby removing the 3.3k Ohm current sense resistor (CSR) from the circuit. 
 

Note

: a cable short circuit will not be detectable in this configuration. 

 

 

 

For one unit only: 

Beacon power 

supply terminal 

block

 

Current  drawn 

(mA)

 

Active Mode 

190mA 

Standby Mode 

25mA 

 

 

SIL2 

TB1 Current 

Sense Resistor 

value

 

Current drawn 

(mA)

 

3.3kΩ

 

7.2mA 

On fault mode, current drops to 0 as 
circuit goes open. 

 

Figure 13: Schematic of SIL 2 system wiring for fault detection in standby and active mode 

 4 wire installation. 

 
If multiple SIL 2 alarm horn sounders are to be cabled in series, the monitoring connections differ from that of a single beacon. For 
more information see manual D197-00-621-IS available from the E2S website. 

 
 

15-2) SIL 2 System Wiring for Fault Detection in Standby Mode Only 

 2 Wire Installation 

 
Cabling is required to the positive '+' and negative '-' power input terminals only.  Monitoring will occur in standby mode only whilst 
power supply polarity is reversed. An  EOL resistor may be added during installation or can be factory fitted. See Table 5 for EOL 
resistor value guidance. 
 
The SIL2 monitoring module contains a factory fitted Power Supply Fault Resistor 2.2k Ohm (FR). When a fault is detected the Fault 
Resistor  will  activated.  The  total  measurable  resistance  of  the  EOL  resistor  and  Fault  Resistor  across  the  power  terminals  which 
already has customer EOL resist

or (2.2kΩ) in place. This will result in a total f

ault detection current of 41.8mA @ 24V but can only 

be detected when unit is in Standby Mode. 
 

Important

: - The 2 wire configuration will not warn of a fault whilst in  Active mode. A fault will only be detectable in standby mode 

when power supply polarity is reversed. 
 

Important

: - The 2-wire configuration requires the J2 header pin to be set to position B (see figure 16). Factory default position is A. 

 

Содержание GNExB2X05-S Series

Страница 1: ...AND CABLE GLANDS IF TEMPERATURE EXCEEDS AS PER STANDARDS INDICATIONS BELOW FOR ATEX IECEx UKEX STANDARDS 70 C AT ENTRY OR 80 C AT BRANCHING POINT FOR NEC CEC STANDARDS 60 C AT ENTRY OR 60 C AT BRANCHI...

Страница 2: ...in compliance with the National Electric Code CEC Class Zone Ratings Canada Standards CAN CSA C22 2 No 60079 0 Ed 4 02 2019 Explosive Atmospheres Part 0 Equipment General Requirements CAN CSA C22 2 N...

Страница 3: ...mented joints is not permitted Figure 1 Flame Path The enclosure is non conducting and may generate an ignition capable level of electrostatic charges under certain extreme conditions The user should...

Страница 4: ...Explosive dust atmospheres The installation of the units must also be in accordance with any local codes that may apply and should only be carried out by a competent electrical engineer who has the ne...

Страница 5: ...C or the cable branching point temperature may exceed 60 C and therefore suitable heat resisting cables and cable glands must be used with a rated service temperature at least as stated below Table 3...

Страница 6: ...P Switch Location Switch Setting S1 Mode SIL Approved 00 1Hz 60FPM Yes 01 1 33Hz 80FPM No 10 1 5Hz 90FPM No 11 Double Flash No Table 4 Switch Positions for Flash Patterns 9 End of Line Monitoring DC U...

Страница 7: ...l and Repair Maintenance repair and overhaul of the equipment should only be carried out by suitably qualified personnel in accordance with the current relevant standards EN60079 19 IEC60079 19 Explos...

Страница 8: ...and Function The SIL 2 Beacon Unit Monitors Standby mode and Active mode Health status of power supply Beacons correct function and flash pattern The SIL 2 beacon operates as part of a SIL 2 system Th...

Страница 9: ...correct the latched fault the alarm horn sounder may require further investigation please contact your local E2S representative Commissioning System Functional start up of System Normally in reverse...

Страница 10: ...hough it is highly recommended that the unit is wired as stated in section 15 1 as a 4 Wire System J1 Header Current Sense Resistor CSR Shown in factory default position A see section 15 3 places TB1...

Страница 11: ...om the circuit Note a cable short circuit will not be detectable in this configuration For one unit only Beacon power supply terminal block Current drawn mA Active Mode 190mA Standby Mode 25mA SIL2 TB...

Страница 12: ...hen no faults and faults occur If multiple SIL 2 alarm horn sounders are to be cabled in series the monitoring connections differ from that of a single beacon For more information see manual D197 00 6...

Страница 13: ...Position B pins 2 3 linked Places power supply terminal Fault Resistor RLY 1 2 in circuit As used in 2 Wire Configuration Figure 16 J2 Header pin positions Fault Resistor FR 15 4 SIL 2 Hard Reset Func...

Страница 14: ...Random Hardware Failures and Architectural constraints route 1H 2 As an unvoted item i e hardware fault tolerance of 0 at SIL 2 The product was assessed against failure modes Failure respond to an in...

Страница 15: ...be specified when ordering The values of resistors available are shown in table 6 below Code Resistor Value Default resistor coding is as follows GNExB2X05DC024AS1S1R A AFZ Example of a custom require...

Страница 16: ...ATERIAL SHEET SCALE TITLE A3 IF IN DOUBT ASK DO NOT SCALE ALL DIMENSIONS IN MM DRAWING NUMBER A B C D E F G 10 9 G F E 7 8 6 5 D C 1 3 4 2 A B D191 06 621 M ABALOS B ISARD R N POTTS OF NTS 1 1 23 09 2...

Страница 17: ...B V Utrechtseweg 310 6812 AR Arnhem Netherlands Quality Assurance Notification Module D SIRA 05 ATEX M342 Provisions fulfilled by the equipment II 2G Ex db IIC T4 T6 Gb II 2D Ex tb IIIC T80 C T138 C D...

Страница 18: ...Date and Place of Issue London 03 12 2021 EU Declaration of Conformity On behalf of European Safety Systems Ltd I declare that on the date the equipment accompanied by this declaration is placed on t...

Страница 19: ...e Lane Eccleston Chester CH4 9JN UK Quality Assurance Notification Module D CSAE 22UKQAN0046 Provisions fulfilled by the equipment II 2G Ex db IIC T4 T6 Gb II 2D Ex tb IIIC T80 C T138 C Db IP6X Dust P...

Страница 20: ...r Date and Place of Issue London 24 02 2022 UKCA Declaration of Conformity On behalf of European Safety Systems Ltd I declare that on the date the equipment accompanied by this declaration is placed o...

Отзывы: