Страница 1: ...rtificate No DEMKO 06ATEX 0421554X IECEx ULD 14 0012X The E2xC1LD2 combined alarm horn and LED beacon is rated as follows CE Marking Zones Gas Dust Groups and Temperature Classification When connected...

Страница 2: ...24 18 30Vdc 346mA 284mA E2xC1LD2FDC048 E2xC1LD2RDC048 42 54Vdc 115mA 146mA E2xC1LD2FAC115 E2xC1LD2RAC115 115 120Vac 50 60Hz 102 4mA 104mA E2xC1LD2FAC230 E2xC1LD2RAC230 220 230Vac 50 60Hz 49 4mA 54mA I...

Страница 3: ...s and cable glands must be used as per table below Ambient Temp 40 C 45 C 50 C 55 C Min Rating of cables and cable glands 90 C 95 C 100 C 105 C If a high IP Ingress Protection rating is required then...

Страница 4: ...d be removed from both sets of terminal blocks refer to fig 3b 5b 9 AC Wiring A 6 way terminal block is provided on the AC Sounder for power There are 2 off Live 2 off Neutral and 2 off Earth terminal...

Страница 5: ...here are 2 off ve 2 off ve 1 off stage2 and 1 off stage 3 terminals in total 10 1 Wiring Diagrams Fig 5a E2xC1LD2 DC Simplified Block Diagram for Simultaneous Beacon Sounder Operation Pre wired Connec...

Страница 6: ...e resistor legs as shown in Fig 9a remove the ve and ve terminal plugs and fit the resistor across the two terminal plugs before refitting them to the PCBA as shown in Fig 9b A spacing of at least 1 1...

Страница 7: ...and overhaul of the equipment should only be carried out by suitably qualified personnel in accordance with the current relevant standards EN60079 19 IEC60079 19 Explosive atmospheres Equipment repai...

Страница 8: ...1 1 0 554Hz Continuous 27 Tone 15 Tone 2 1 0 0 1 1 0 Bell 26 Tone 5 Tone 29 0 0 0 1 1 0 2400 2900Hz 50Hz Sweeping 25 Tone 5 Tone 29 1 1 1 0 1 0 800 1000Hz 50Hz Sweeping 24 Tone 5 Tone 6 0 1 1 0 1 0 8...