background image

 

 

European Safety Systems Ltd.

   Impress House, Mansell Road, Acton, London W3 7QH

 

www.e2s.com

 

Tel: +44 (0)208 743 8880

 

Document No. D252-00-001-IS

 

Issue 1

 

21-12-2023

 

 

Sheet 6 of 7

 

 

9)  End of Line Monitoring (DC Units) 

 

9.1 

Standard DC End Of Line Monitoring 

  

On  D2xS2  DC  units,  DC  reverse  line  monitoring  can  be  used  if 
required. All DC sounders have a blocking diode fitted in their supply 
input lines. An end of line monitoring resistor can be connected across 
the +ve and 

–ve terminals. If an end of line resistor is used it must have 

the following values: 
 
24V DC Max Sounder 
Minimum resistance 3K9 Ohms  

Minimum Power 0.5W 

Minimum resistance 1K Ohms  

Minimum Power 2.0W 

 
48V DC Max Sounders 
Minimum resistance 15K Ohms 

Minimum Power 0.5W 

Minimum resistance 3K9 Ohms 

Minimum Power 2.0W 

 
The  resistor  must  be  connected  directly  across  the  +ve  and  -ve 
terminals as shown in the following drawing. Whilst keeping its leads 
as short  as  possible,  a spacing  of  at least  1/16”  (1.58mm) must  be 
provided through air and over surfaces between uninsulated live parts. 
See D252-06-001 for details. 
 

Figure 9: End of Line Resistor placement. 

 

Note that the maximum forward polarity monitoring voltage is 6V. A 
monitoring voltage greater than 6V may activate the alarm horn 
sounder and the 2nd, 3rd or 4th stages. 
 

9.2      Custom DC Multi-Stage End Of Line Monitoring 

  

An optional 12-way terminal module is available to enable up to four 
alarm stages to be activated from three DC voltage output channels. 
The three alarm stage activation inputs can be independently 
monitored. 
  
Refer to Schematic D252-06-001, Config. 6. 
Specify Product option ‘V’ when ordering. 
Spare part code for field installation: SP78-0001 

 
 

 

Figure 10: End of Line Resistor placement 

– 

Optional 12-Way Terminal Module. 
 
 
 
 
 

 

10) Maintenance, Overhaul and Repair 

 

Maintenance,  repair  and  overhaul  of  the  equipment  should  only  be 
carried  out  by  suitably  qualified  personnel  in  accordance  with  the 
current relevant standards: 
 

For ATEx/IECEx or UKEx: 

 

EN60079-19/IEC60079-19  

 

Explosive  atmospheres 

–  Equipment  repair,  overhaul  and 

reclamation 

 

EN 60079-17/IEC60079-17    
Explosive  atmospheres 

– Electrical installations inspection 

and maintenance 

 
Units must not be opened while an explosive atmosphere is present. 
 
If opening the unit during maintenance operations, a clean 
environment must be maintained and any dust layer removed prior to 
opening the unit. 
 
To avoid a possible ELECTROSTACTIC CHARGE the unit must only 
be cleaned with a damp cloth. 
 
 

11) SIL 2 Reliability Data 

 
Reliability and Functional safety IEC/EN61508 which has been 
assessed and is considered suitable for use in low demand safety 
function: 
 
1. 

Random Hardware Failures and Architectural constraints (route 
2

H

). 

2. 

As an unvoted item (i.e. hardware fault tolerance of 0) at SIL 2. 

The product was assessed against failure modes: 

 

Failure respond to an input by sounding sounder. 

 

Spurious sound output despite no input. 

3. 

When employing the device in a SIL2 compliant system the user 
should ensure frequent or continuous automatic monitoring of 
continuity. 
 

 

Integrity in respect of failure to function 

SIL2 & SIL1 

Total Failure rate 

0.55 pmh 

“Hazardous” failure rate (revealed) 

0 pmh 

“Hazardous” failure rate (unrevealed) 

0.55 pmh 

“Safe” failure rate (revealed) 

0 pmh 

“Safe” failure rate (unrevealed) 

System type 

Hardware Fault Tolerance 

Diagnostic Coverage 

>80% 

PFD (hazardous failure) 

2.4 x 10

-3

 

Proof Test Interval 

Up to 1 year 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

Содержание D2xS2F Series

Страница 1: ...above are for the 440Hz Continuous tone nominal input voltage Nominal current at nominal voltage Table 1 Electrical Ratings 2 Warnings DO NOT OPEN WHEN AN EXPLOSIVE ATMOSPHERE IS PRESENT DO NOT OPEN W...

Страница 2: ...ition 7 EN IEC 60079 7 2015 A1 2018 IEC 60079 7 2018 Edition 5 1 EN 60079 31 2014 IEC 60079 31 2022 Edition 3 Model No Rating D2xS2FDC024 D2xS2HDC024 Ex ec IIC T3 Gc Ta 55 C to 75 C Ex ec IIC T4 Gc Ta...

Страница 3: ...ys be fitted d Replace the cover of the unit taking care not to damage the threads Tighten fully 6 3 Access to the Enclosure Fig 2 Accessing the enclosure To access the chamber loosen the M4 grub scre...

Страница 4: ...lands or blanking plugs A minimum ingress protection rating of IP54 must be maintained for installations in explosive gas atmospheres and IP6X must be maintained for installations in explosive dust at...

Страница 5: ...e 1 DIP switch setting Following table Table 3 is a summary of DC D252 06 001 AC D252 06 005 wiring options Config Voltage Configuration Description Features Product Option Identifier 1a DC Single Sta...

Страница 6: ...duct option V when ordering Spare part code for field installation SP78 0001 Figure 10 End of Line Resistor placement Optional 12 Way Terminal Module 10 Maintenance Overhaul and Repair Maintenance rep...

Страница 7: ...with suitably rated cable glands or stopping plugs EOL Monitoring DC Only End of Line Devices may be fitted between the ve ve terminals of the PCBA Please ensure that the device legs meet the wire si...

Страница 8: ...4V D2xS2HDC024 A is approved for use as an audible signal appliance for fire alarm use Public Mode UL464 CAN ULC S525 and produces a minimum sound pressure level of P2 US 95 51dB A CA 103 8dB A P3 US...

Страница 9: ...1 0 1 0 0 0 0 1 1 0 0 0 1 1 1 0 0 0 0 0 0 1 0 0 1 0 0 1 0 0 0 1 0 1 0 0 1 1 0 1 0 0 0 0 1 1 0 0 1 0 1 1 0 0 0 1 1 1 0 0 1 1 1 1 0 0 0 0 0 0 1 0 1 0 0 0 1 0 0 1 0 0 1 0 1 1 0 0 1 0 0 0 1 0 1 0 1 0 1 0...

Страница 10: ...MONITORING RESISTOR CUSTOMER SUPPLIED 24V MAX SYSTEM 3K9 MIN 0 5W MIN OR 1K MIN 2 0W MIN 48V MAX SYSTEM 15K MIN 0 5W MIN OR 3K9 MIN 2 0W MIN RECOMMENDED MINIMUM VALUES R1 Stage 1 ve IN Stage 1 ve OUT...

Страница 11: ...e OUT Stage 1 ve OUT Stage 3 ve Stage 1 ve IN H2 H1 Stage 1 ve Stage 1 ve Stage 2 ve Stage 2 ve OF 2 3 R1 S2 S3 R1 S2 R2 OPTIONAL LINE MONITORING RESISTOR CUSTOMER SUPPLIED RECOMMENDED MINIMUM VALUES...

Страница 12: ...to Stage 2 ve Stage 2 ve Two Three Stage Voltage Free Activation Configuration Config 5 Customer Set H1 H2 to Negative Switching See Below Power ve ve Stage 1 Connect Stage 1 ve to Common ve Stage 2 C...

Страница 13: ...2 A B D252 06 005 R S RAIT B ISARD R N POTTS OF NTS 1 SWITCHES FOR STAGE OPERATION CUSTOMER SUPPLIED 1 Earth Earth Stage 2 Stage 3 Common Live IN Live OUT Neutral IN Neutral OUT Earth Stage 1 Stage 2...

Страница 14: ...urance Notification Conformity to EU type based on quality assurance of the production process Module D Sira Certification Service Notified Body No 2813 CSA Group Netherlands B V Utrechtseweg 310 6812...

Страница 15: ...the components contained within it are free from substances of very high concern Other Standards and Regulations EN 60529 1992 A2 2013 Degrees of protection provided by enclosures IP code enclosure r...

Страница 16: ...Assurance Notification Conformity to EU type based on quality assurance of the production process Module D Sira Certification Service Notified Body No 0518 Rake Lane Eccleston Chester CH4 9JN UK Quali...

Страница 17: ...e components contained within it are free from substances of very high concern Other Standards and Regulations EN 60529 1992 A2 2013 Degrees of protection provided by enclosures IP code enclosure rate...

Страница 18: ...Page left Intentionally blank...

Страница 19: ...Page left Intentionally blank...

Страница 20: ...Page left Intentionally blank...

Отзывы: