European Safety Systems Ltd.

   Impress House, Mansell Road, Acton, London W3 7QH

 

www.e2s.com

 

Tel: +44 (0)208 743 8880

 

Document No. D211-00-651-IS

 

Issue 1

 

20-08-22

 

 

Sheet 2 of 8

 

 

3.3.  NEC & CEC Ratings 

 
NEC & CEC Class / Division Ratings for US / Canada 

 

Standards 

UL 121201-2021 (Ed. 9) 
CAN/CSA C22.2 No. 213-17 (Ed. 3) 

Ratings 

D2xC2XH1 

Class I Div 2 ABCD T3 Ta -40°C to +50°C 
Class II Div 2 FG T6 Ta -40°C to +50°C 
Class III Div 1&2 Ta -40°C to +50°C 

D2xC2XH2 

Class I Div 2 ABCD T2A Ta -40°C to +50°C 
Class II Div 2 FG T6 Ta -40°C to +50°C 
Class III Div 1&2 Ta -40°C to +50°C 

Installation must be carried out in compliance with the National 
Electric Code / Canadian Electric Code 

 

NEC Class / Zone ratings US 
 

Standards 

UL 60079-0 (Ed. 7): 

Explosive Atmospheres - part 0: Equipment - General 
Requirements  

UL 60079-7 (Ed. 5): 

Explosive Atmospheres - Equipment Protection by Increased 

Safety "e" 

UL 60079-31 (Ed. 2) 

Explosive Atmospheres - Equipment Dust Ignition Protection by 

Enclosure "t" 

 
 

Ratings 

D2xC2XH1 

Class I Zone 2 AEx ec IIC T3 Gc Ta -40°C to 
+50°C 
Zone 22 AEx tc IIIC T75°C Dc Ta -40°C to 
+50°C 

D2xC2XH2 

Class I Zone 2 AEx ec IIC T2 Gc Ta -40°C to 
+50°C 
Zone 22 AEx tc IIIC T85°C Dc Ta -40°C to 
+50°C 

Installation must be carried out in compliance with the National 
Electric Code. 

 
CEC Class / Zone ratings Canada 

 

Standards 

CAN/CSA C22.2 No. 60079-0 (Ed. 4) 02/2019 

Explosive Atmospheres - Part 0: Equipment - General 
Requirements  

CAN/CSA C22.2 No. 60079-7 (Ed. 2) 

Explosive Atmospheres - Equipment Protection by Increased 

Safety "e" 

CAN/CSA C22.2 No. 60079-31 (Ed. 2) 

Explosive Atmospheres - Equipment Dust Ignition Protection by 

Enclosure "t"

 

Rating 

D2xC2XH1

 

Ex ec IIC T3 Gc X Ta -40°C to +50°C 
Ex tc IIIC T75°C Dc Ta -40°C to +50°C 

D2xC2XH2

 

Ex ec IIC T2 Gc X Ta -40°C to +50°C 
Ex tc IIIC T85°C Dc Ta -40°C to +50°C 

Installation must be carried out in compliance with the Canadian 
Electric Code 

 

4) 

Zones, Gas Group, Category and 
Temperature Classification 

 

Area Classification 

Zone 2 

Explosive gas air mixture not likely to occur in 
normal operation, and if it does, it will only 
exist for a short time. 

Zone 22 

Explosive dust air mixture not likely to occur 
in normal operation, and if it does, it will only 
exist for a short time. 

Gas Groupings 

Group IIA 

Propane 

Group IIB 

Ethylene 

Group IIC 

Hydrogen and Acetylene 

Temperature Classification for Gas Applications 

T1 

450ºC  

T2 

300ºC 

T3 

200ºC 
(D2xC2XH1 only) 

Dust Groupings 

(ATEX / IECEx / UKEX only) 

Group IIIA 

Combustible Flyings 

Group IIIB 

Non-conductive Dust 

Group IIIC 

Conductive Dust 

Maximum Surface Temperature for Dust Applications 

(ATEX / IECEx / UKEX only) 

D2xC2XH1 

75°C 

D2xC2XH2 

85ºC 

Equipment Category 

3G / 3D  

Equipment Level Protection 

Gc, Dc 

Ambient Temperature Range 

-40°C to +50°C 

IP Rating 

IP6X to EN/IEC60079-0 

IP66 to EN60529 
To maintain the ingress protection rating, the two off cable entries 
must be fitted with suitably rated, certified cable entry and/or 
blanking devices during installation. 

Type Rating 

Per UL50E / NEMA250: 4 / 4X / 3R / 13

 

 

Installation must be carried out in compliance with the latest 
issue of the following standards: 
EN60079-14 / IEC60079-14: Explosive atmospheres - Electrical 
installations design, selection and erection 
EN60079-10-1 / IEC60079-10-1: Explosive atmospheres - 
Classification of areas. Explosive gas atmospheres 
EN60079-10-2 / IEC60079-10-2: Explosive atmospheres –  
Classification of areas. Explosive dust atmospheres 
 

Содержание D2XC2XH1

Страница 1: ...and D2xC2XH2 are certified for use as public mode audible and visual alarm devices in accordance with UL1971 UL1638 UL464 See fire instructions D211 00 651 IS SC UL 3 2 ATEX IECEx UKEx certification S...

Страница 2: ...y Enclosure t Rating D2xC2XH1 Ex ec IIC T3 Gc X Ta 40 C to 50 C Ex tc IIIC T75 C Dc Ta 40 C to 50 C D2xC2XH2 Ex ec IIC T2 Gc X Ta 40 C to 50 C Ex tc IIIC T85 C Dc Ta 40 C to 50 C Installation must be...

Страница 3: ...ent is not to be mounted with the horn facing upwards Fig 1 Fixing locations 6 2 Access to the Enclosure Warning High voltage may be present risk of electric shock DO NOT open when energised disconnec...

Страница 4: ...user wishes to power the strobe separately For further wiring schematics refer to document D211 06 651 10 Earthing The unit has both internal and external earth points please see fig 2 fig 4 Internal...

Страница 5: ...the PCB The alarm horns can also be switched to sound the second third and fourth stage alarm tones The tone table shows the switch positions for the 64 tone and which tones are available for the seco...

Страница 6: ...22 Sheet 6 of 8 14 Electrical Ratings 14 1 Operating current Consumption Table 6 Electrical Ratings Model Nom Voltage Voltage Range Flash Rate Setting Max operating current D2xC2XH1DC024 24Vdc 20 28Vd...

Страница 7: ...s on 0 5s off x3 1s gap ISO 8201 Temporal Pattern 1 1 0 1 0 0 44 1 8 13 422 775Hz 0 85 on 0 5 off x3 1s gap NFPA Temporal Coded 0 0 1 1 0 0 44 1 8 14 1000 2000Hz 1Hz Singapore 1 0 1 1 0 0 23 3 35 15 3...

Страница 8: ...Hz Sweeping 1 0 0 0 1 1 44 24 12 51 600 1250Hz 0 125Hz Sweeping 0 1 0 0 1 1 44 24 12 52 660 1200Hz 1Hz Sweeping 1 1 0 0 1 1 64 24 12 53 800 1000Hz 1Hz Sweeping 0 0 1 0 1 1 56 24 12 54 800 1000Hz 7Hz S...

Страница 9: ...alarm use the temporal pattern tone No 12 as per the tone table provided in these instructions must be selected This tone produces a minimum sound pressure level of CAN ULC S525 100 4dB A at 10 feet...

Страница 10: ...Dispersion for wall mounting public mode 75 60 45 30 15 0 90 Fig 1 Vertical dispersion angles for wall mounting 55 45 8 18 60 40 7 27 65 35 6 36 70 35 6 36 75 30 5 45 80 30 5 45 85 25 4 55 90 25 4 55...

Страница 11: ...ght Output Dispersion for Wall Mounting Viewing Angle Of Rating Intensity cd at 1Hz flash rate 0 100 18 18 5 30 90 16 36 35 65 11 82 40 46 8 36 45 34 6 18 50 27 4 91 55 22 4 00 60 18 3 27 65 16 2 91 7...

Страница 12: ...fpm 2 28A 1 19A D2xC2XH2DC024 24Vdc 20 28Vdc 1Hz 60fpm 2 76A 1 35A 4 Sound Directional Characteristics for Canadian Fire CAN ULC S525 Horizontal Axis Angle OSPL Angle OSPL Reference 90 101 2 dB A Refe...

Страница 13: ...o Sounder ve ve Stage 2 Apply power to Sounder ve ve Connect Stage 2 to ve Stage 3 Apply power to Sounder ve ve Connect Stage 3 to ve Stage 4 Apply power to Sounder ve ve Connect Stage 2 and Stage 3 t...

Страница 14: ...herlands B V Utrechtseweg 310 6812 AR Arnhem Netherlands Quality Assurance Notification Module D SIRA 05 ATEX M342 Provisions fulfilled by the equipment II 3G Ex ec IIC T6 T4 T3 T2 T1 Gc II 3D Ex tc I...

Страница 15: ...e and Place of Issue London 22 08 2022 EU Declaration of Conformity On behalf of European Safety Systems Ltd I declare that on the date the equipment accompanied by this declaration is placed on the m...

Страница 16: ...Lane Eccleston Chester CH4 9JN UK Quality Assurance Notification Module D CSAE 22UKQAN0046 Provisions fulfilled by the equipment II 3G Ex ec IIC T6 T4 T3 T2 T1 Gc II 3D Ex tc IIIC Ex tc IIIC T55 75 80...

Страница 17: ...Place of Issue London 22 08 2022 UKCA Declaration of Conformity On behalf of European Safety Systems Ltd I declare that on the date the equipment accompanied by this declaration is placed on the marke...

Отзывы: