European Safety Systems Ltd.

   Impress House, Mansell Road, Acton, London W3 7QH

 

www.e2s.com

 

Tel: +44 (0)208 743 8880

 

Document No. D211-00-601-IS

 

Issue 1

 

20-08-22

 

 

Sheet 3 of 8

 

 

D2xB1: 
X05DC048 
X05AC115 
X05AC230

 

Ex ec IIC T3 Gc X Ta -40°C to +50°C 
Ex tc IIIC T95°C Dc X Ta -40°C to +50°C 
 

D2xB1: 
X10DC048 
X10AC115 
X10AC230 

Ex ec IIC T2 Gc X Ta -40°C to +50°C 
Ex tc IIIC T95°C Dc X Ta -40°C to +50°C 
 

Installation must be carried out in compliance with the Canadian 
Electric Code 

 

4)  Zones, Gas / Dust Groups and 

Temperature Classification 

 

Area Classification 

Zone 2 

Explosive gas air mixture not likely to occur in 
normal operation, and if it does, it will only 
exist for a short time. 

Zone 22 

Explosive dust air mixture not likely to occur 
in normal operation, and if it does, it will only 
exist for a short time. 

Gas Groupings 

Group IIA 

Propane 

Group IIB 

Ethylene 

Group IIC 

Hydrogen and Acetylene 

Temperature Classification for Gas Applications 

T1 

450ºC  

T2 

300ºC 

T3 

200ºC 
(D2xC2X05 only) 

Dust Groupings 

(ATEX / IECEx / UKEX only) 

Group IIIA 

Combustible Flyings 

Group IIIB 

Non-conductive Dust 

Group IIIC 

Conductive Dust 

Maximum Surface Temperature for Dust Applications 

(ATEX / IECEx / UKEX only) 

D2xC2X05DC024  75°C 

D2xC2X10DC024  85ºC 

D2xC2: 
48Vdc, 115Vac 
and 230Vac units 

95ºC 

Equipment Category 

3G / 3D  

Equipment Level Protection 

Gc, Dc 

Ambient Temperature Range 

-40°C to +50°C 

IP Rating 

IP6X to EN/IEC60079-0 

IP66 to EN60529 
To maintain the ingress protection rating, the two off cable entries 
must be fitted with suitably rated, certified cable entry and/or 
blanking devices during installation. 
 

Type Rating 

Per UL50E / NEMA250: 4 / 4X / 3R / 13

 

 

 
Installation must be carried out in compliance with the latest 
issue of the following standards: 
 
EN60079-14 / IEC60079-14: Explosive atmospheres - Electrical 
installations design, selection and erection 
EN60079-10-1 / IEC60079-10-1: Explosive atmospheres - 
Classification of areas. Explosive gas atmospheres 
EN60079-10-2 / IEC60079-10-2: Explosive atmospheres –  
Classification of areas. Explosive dust atmospheres 
 

5)  Special Conditions for Safe Use 

 
Special Condition for safe Use as stated on the Type 
Examination Certificate DEMKO 14 ATEX 4786493904X / CoC 
IECEx ULD 14.0004X /

 

UL21UKEX2131X: 

 
When  used  for  a  Group  III  application,  the  surface  of  the 
enclosure may store electrostatic charge and become a source 
of  ignition  in  applications  with  a  low  relative  humidity  <~30% 
relative  humidity  where  the  surface  is  relatively  free  of  surface 
contamination such as dirt, dust, or oil. 
 
Guidance  on  protection  against  the  risk  of  ignition  due  to 
electrostatic  discharge  can  be  found  in  EN  TR50404  and  IEC 
TR60079-32. 

 

End  user  shall  adhere  to  the  manufacturer’s  installation  and 
instruction when performing housekeeping to avoid the potential 
for hazardous electrostatic charges during cleaning, by using a 
damp cloth. 
 
To  maintain  the  ingress  protection  rating  and  mode  of 
protection,  the  cable  entries  must  be  fitted  with  suitably  rated, 
certified cable entry and/or blanking devices during installation.  
 

6)  Product Mounting and Access 
 

6.1. Location and Mounting 

 

The location of the combined alarm horn and beacon should be 
made with due regard to the area over which the warning signal 
must be visible and  audible.  It  should only be fixed  to  services 
that can carry the weight of the unit. 

 

DxC2 Alarm Horn and Strobe to a flat surface via the two 9.7 x 
6.7mm,  147mm  pitch  fixing  holes  in  the  mounting  feet  of  the 
sounder section and the two 7mm fixing holes in the feet of the 
base. 
 
The  equipment  is  not  to  be  mounted  with  the  horn  facing 
upwards. 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

Содержание D2xC2 Series

Страница 1: ...WER BEFORE OPENING THE ENCLOSURE Avertissement NE PAS OUVRIR UN PRESENCE D ATMOSPHERE EXPLOSIVE NE PAS OUVRIR ENERGIE DANGER POTENTIEL CHARGE ÉLECTROSTATIQUE NETTOYER UNIQUEMENT AVEC UN CHIFFON HUMIDE HAUT TENSION RISK DE CHOC ATTENDEZ 5 MINUTES APRES AVOIR DEBRANCHE L ALIMENTATION AVANT D OUVRIR LA BOITIER Model Nominal Voltage Beacon Current Sounder Current D2xC2X05DC024 20 28Vdc 296mA 313mA D2x...

Страница 2: ...a 40 C to 50 C Class III Div 1 2 Ta 40 C to 50 C D2xC2 X05DC048 X05AC115 X05AC230 Class I Div 2 ABCD T3 Ta 40 C to 50 C Class II Div 2 FG T5 Ta 40 C to 50 C Class II Div 2 FG T6 Ta 40 C to 40 C Class III Div 1 2 Ta 40 C to 50 C D2xC2 X10DC048 X10AC115 X10AC230 Class I Div 2 ABCD T2B Ta 40 C to 50 C Class II Div 2 FG T5 Ta 40 C to 50 C Class II Div 2 FG T6 Ta 40 C to 40 C Class III Div 1 2 Ta 40 C ...

Страница 3: ...test issue of the following standards EN60079 14 IEC60079 14 Explosive atmospheres Electrical installations design selection and erection EN60079 10 1 IEC60079 10 1 Explosive atmospheres Classification of areas Explosive gas atmospheres EN60079 10 2 IEC60079 10 2 Explosive atmospheres Classification of areas Explosive dust atmospheres 5 Special Conditions for Safe Use Special Condition for safe Us...

Страница 4: ...For use in explosive dust atmospheres a minimum ingress protection rating of IP6X must be maintained For use in explosive gas atmospheres a minimum ingress protection rating of IP54 must be maintained NPT stopping plugs should be greased before insertion 8 Cable Connections Electrical connections are to be made into the terminal blocks on the PCBA located in the enclosure See section 6 of this man...

Страница 5: ...End Of Line Monitoring DC Units Only On D2xC2 DC units dc reverse line monitoring can be used if required All DC units have a blocking diode fitted in their supply input lines An end of line monitoring resistor can be connected across the ve and ve terminals If an end of line resistor is used it must have the following values Min Resistance Min Power 24V DC 3 9KΩ 0 5W 1KΩ 2W 48V DC 15KΩ 0 5W 3 9KΩ...

Страница 6: ...fixing holes of the guard lens cover and housing Refit the fixings to hold into place the fixings MUST be fitted in the order shown above 15 DIP Switch Please note that the D2xC2X05DC024 D2xC2X10DC024 beacon PCBAs have a DIP Switch that is NOT customer configurable This should only ever be set to 00 Fig 12 DIP Switch setting 00 16 Maintenance Overhaul Repair Maintenance repair and overhaul of the ...

Страница 7: ... 0 5s off x3 1s gap ISO 8201 Temporal Pattern 0 1 0 1 0 0 44 1 8 12 1000Hz 0 5s on 0 5s off x3 1s gap ISO 8201 Temporal Pattern 1 1 0 1 0 0 44 1 8 13 422 775Hz 0 85 on 0 5 off x3 1s gap NFPA Temporal Coded 0 0 1 1 0 0 44 1 8 14 1000 2000Hz 1Hz Singapore 1 0 1 1 0 0 23 3 35 15 300Hz Continuous 0 1 1 1 0 0 44 24 35 16 440Hz Continuous 1 1 1 1 0 0 44 24 35 17 470Hz Continuous 0 0 0 0 1 0 44 24 35 18 ...

Страница 8: ...3Hz Sweeping 1 0 0 0 1 1 44 24 12 51 600 1250Hz 0 125Hz Sweeping 0 1 0 0 1 1 44 24 12 52 660 1200Hz 1Hz Sweeping 1 1 0 0 1 1 64 24 12 53 800 1000Hz 1Hz Sweeping 0 0 1 0 1 1 56 24 12 54 800 1000Hz 7Hz Sweeping 1 0 1 0 1 1 57 24 12 55 800 1000Hz 50Hz Sweeping 0 1 1 0 1 1 54 24 12 56 2400 2900Hz 7Hz Sweeping 1 1 1 0 1 1 57 24 12 57 2400 2900Hz 1Hz Sweeping 0 0 0 1 1 1 47 24 12 58 2400 2900Hz 50Hz Swe...

Страница 9: ...st setting see volume control section The sounder section produces a sound pressure level above 75dB A at 10 feet For fire alarm use the temporal pattern tone No 12 as per the tone table provided in these instructions must be selected This tone produces a minimum sound pressure level of CAN ULC S525 100 4dB A at 10 feet anechoic room UL464 92 2dB A at 10 feet reverberation room 3 Surge Current Rat...

Страница 10: ...2 and Stage 3 to ve AC D2XC2X05 D2XC2X10 UNITS Power Live Neutral Stage 1 Apply power to Sounder L N Stage 2 Apply power to Sounder L N Connect Stage 2 to Common Stage 3 Apply power to Sounder L N Connect Stage 3 to Common Stage 4 Apply power to Sounder L N Connect Stage 2 and Stage 3 to Common OPTIONAL LINE MONITORING RESISTOR CUSTOMER SUPPLIED REQUIRED MINIMUM VALUES R1 24VDC 1KΩ MIN 2W MIN OR 3...

Страница 11: ...therlands B V Utrechtseweg 310 6812 AR Arnhem Netherlands Quality Assurance Notification Module D SIRA 05 ATEX M342 Provisions fulfilled by the equipment II 3G Ex ec IIC T6 T4 T3 T2 T1 Gc II 3D Ex tc IIIC Ex tc IIIC T55 75 80 85 90 95 105 110 C Dc IP66 Ingress Dust Protection to EN60079 0 EN60079 31 Standards applied EN IEC 60079 0 2018 EN IEC 60079 7 2015 A1 2018 EN 60079 31 2014 Directive 2014 3...

Страница 12: ...te and Place of Issue London 22 08 2022 EU Declaration of Conformity On behalf of European Safety Systems Ltd I declare that on the date the equipment accompanied by this declaration is placed on the market the equipment conforms with all technical and regulatory requirements of the above listed directives regulations and standards This Declaration is issued under the sole responsibility of the ma...

Страница 13: ... Lane Eccleston Chester CH4 9JN UK Quality Assurance Notification Module D CSAE 22UKQAN0046 Provisions fulfilled by the equipment II 3G Ex ec IIC T6 T4 T3 T2 T1 Gc II 3D Ex tc IIIC Ex tc IIIC T55 75 80 85 90 95 105 110 C Dc IP66 Ingress Dust Protection to EN60079 0 EN60079 31 Standards applied EN IEC 60079 0 2018 EN IEC 60079 7 2015 A1 2018 EN 60079 31 2014 Directive 2014 30 EU Electromagnetic Com...

Страница 14: ... Place of Issue London 22 08 2022 UKCA Declaration of Conformity On behalf of European Safety Systems Ltd I declare that on the date the equipment accompanied by this declaration is placed on the market the equipment conforms with all technical and regulatory requirements of the above listed directives regulations and standards This Declaration is issued under the sole responsibility of the manufa...

Отзывы: