DC Sounder Terminals 

1

-1

5m

m

4 - 7mm

1

-1

5m

m

5 - 10mm

S2

S3

+

-

E

 
 

24VDC Strobe Terminals   

48VDC Strobe Terminals 

 

Fig. 5 DC Terminals 

 

11)  Earthing 

 

The  unit  has  both  internal  and  external  earth  terminals, 
(please see fig 3). 
Internal  earthing  connections  should  be  made  to  the  internal 
earth terminal on the PCBA, (please see fig 4 for AC, fig 5 for 
DC). The earth conductor should be at least equal in size and 
rating  to  the  incoming  power  conductors.  The  internal  earth 
bonding wire connects the PCBA earth terminal to the internal 
earth terminal in the enclosure back box. 
 
External  earth  connections  should  be  made  to  the  M5  earth 
stud, using a ring crimp terminal to secure the earth conductor 
to  the  earth  stud.  The  external  earth  conductor  should  be  at 
least  4mm

2

  in  size.  The  external  earth  crimp  ring  should  be 

located  between  the  two  M5  plain  washers  provided  and 
securely locked down with the M5 spring washer and M5 nut. 
 

12)  End Of Line Monitoring (DC Units Only) 

 

On D2xC2 DC units, dc reverse line monitoring can be used if 
required.  All  DC  units  have  a  blocking  diode  fitted  in  their 
supply  input  lines.  An  end  of  line  monitoring  resistor  can  be 
connected across the +ve and –ve terminals. If an end of line 
resistor is used it must have the following values:- 
 

 

Min. Resistance 

Min. Power 

24V DC 

3.9KΩ 

0.5W 

1KΩ 

2W 

48V DC 

15KΩ 

0.5W 

3.9KΩ 

2W 

 
The resistor must be connected directly across the +ve and  
-ve terminals as shown in the following drawing. Form the 
resistor legs as shown in Fig. 7, remove the +ve and –ve 
terminal plugs and fit the resistor across the two terminal 
plugs before refitting them to the PCBA as shown in Fig. 8a or 
8b. A spacing of at least 1/16” (1.58mm) must be provided 
through air and over surfaces between uninsulated live parts. 
 
 
 

 

 
 
 
 
 
 

 

       Sounder EOL Resistor 

          Beacon EOL Resistor 

 

Fig. 7 End of Line Resistor Forming 

 
 
 
 
 
 
 
 
 
 
 

 

 

 

 

 

Fig. 8a 48VDC Beacon End of Line Resistor Placement 

 

 
 
 
 
 
 

 

 

 

 

 

 

 

 

 

Fig. 8b 24VDC Beacon End of Line Resistor Placement 

 

 

 

Fig. 9 Sounder End Of Line Resistor Placement 

 

13)  Settings 

 
13.1 Volume Control 

 

The  alarm  horn  output  level  of  the  DxC2  unit  can  be  set  by 
adjusting  the  volume  control  potentiometer  (see  Fig  10).  For 
maximum output, set the potentiometer fully clockwise. 
 

End of Line Resistor 

- -     + +    E E 

- -     + +    E E 

EOL 
Resistor 

Содержание D2xC2 Series

Страница 1: ...WER BEFORE OPENING THE ENCLOSURE Avertissement NE PAS OUVRIR UN PRESENCE D ATMOSPHERE EXPLOSIVE NE PAS OUVRIR ENERGIE DANGER POTENTIEL CHARGE ÉLECTROSTATIQUE NETTOYER UNIQUEMENT AVEC UN CHIFFON HUMIDE HAUT TENSION RISK DE CHOC ATTENDEZ 5 MINUTES APRES AVOIR DEBRANCHE L ALIMENTATION AVANT D OUVRIR LA BOITIER Model Nominal Voltage Beacon Current Sounder Current D2xC2X05DC024 20 28Vdc 296mA 313mA D2x...

Страница 2: ...a 40 C to 50 C Class III Div 1 2 Ta 40 C to 50 C D2xC2 X05DC048 X05AC115 X05AC230 Class I Div 2 ABCD T3 Ta 40 C to 50 C Class II Div 2 FG T5 Ta 40 C to 50 C Class II Div 2 FG T6 Ta 40 C to 40 C Class III Div 1 2 Ta 40 C to 50 C D2xC2 X10DC048 X10AC115 X10AC230 Class I Div 2 ABCD T2B Ta 40 C to 50 C Class II Div 2 FG T5 Ta 40 C to 50 C Class II Div 2 FG T6 Ta 40 C to 40 C Class III Div 1 2 Ta 40 C ...

Страница 3: ...test issue of the following standards EN60079 14 IEC60079 14 Explosive atmospheres Electrical installations design selection and erection EN60079 10 1 IEC60079 10 1 Explosive atmospheres Classification of areas Explosive gas atmospheres EN60079 10 2 IEC60079 10 2 Explosive atmospheres Classification of areas Explosive dust atmospheres 5 Special Conditions for Safe Use Special Condition for safe Us...

Страница 4: ...For use in explosive dust atmospheres a minimum ingress protection rating of IP6X must be maintained For use in explosive gas atmospheres a minimum ingress protection rating of IP54 must be maintained NPT stopping plugs should be greased before insertion 8 Cable Connections Electrical connections are to be made into the terminal blocks on the PCBA located in the enclosure See section 6 of this man...

Страница 5: ...End Of Line Monitoring DC Units Only On D2xC2 DC units dc reverse line monitoring can be used if required All DC units have a blocking diode fitted in their supply input lines An end of line monitoring resistor can be connected across the ve and ve terminals If an end of line resistor is used it must have the following values Min Resistance Min Power 24V DC 3 9KΩ 0 5W 1KΩ 2W 48V DC 15KΩ 0 5W 3 9KΩ...

Страница 6: ...fixing holes of the guard lens cover and housing Refit the fixings to hold into place the fixings MUST be fitted in the order shown above 15 DIP Switch Please note that the D2xC2X05DC024 D2xC2X10DC024 beacon PCBAs have a DIP Switch that is NOT customer configurable This should only ever be set to 00 Fig 12 DIP Switch setting 00 16 Maintenance Overhaul Repair Maintenance repair and overhaul of the ...

Страница 7: ... 0 5s off x3 1s gap ISO 8201 Temporal Pattern 0 1 0 1 0 0 44 1 8 12 1000Hz 0 5s on 0 5s off x3 1s gap ISO 8201 Temporal Pattern 1 1 0 1 0 0 44 1 8 13 422 775Hz 0 85 on 0 5 off x3 1s gap NFPA Temporal Coded 0 0 1 1 0 0 44 1 8 14 1000 2000Hz 1Hz Singapore 1 0 1 1 0 0 23 3 35 15 300Hz Continuous 0 1 1 1 0 0 44 24 35 16 440Hz Continuous 1 1 1 1 0 0 44 24 35 17 470Hz Continuous 0 0 0 0 1 0 44 24 35 18 ...

Страница 8: ...3Hz Sweeping 1 0 0 0 1 1 44 24 12 51 600 1250Hz 0 125Hz Sweeping 0 1 0 0 1 1 44 24 12 52 660 1200Hz 1Hz Sweeping 1 1 0 0 1 1 64 24 12 53 800 1000Hz 1Hz Sweeping 0 0 1 0 1 1 56 24 12 54 800 1000Hz 7Hz Sweeping 1 0 1 0 1 1 57 24 12 55 800 1000Hz 50Hz Sweeping 0 1 1 0 1 1 54 24 12 56 2400 2900Hz 7Hz Sweeping 1 1 1 0 1 1 57 24 12 57 2400 2900Hz 1Hz Sweeping 0 0 0 1 1 1 47 24 12 58 2400 2900Hz 50Hz Swe...

Страница 9: ...st setting see volume control section The sounder section produces a sound pressure level above 75dB A at 10 feet For fire alarm use the temporal pattern tone No 12 as per the tone table provided in these instructions must be selected This tone produces a minimum sound pressure level of CAN ULC S525 100 4dB A at 10 feet anechoic room UL464 92 2dB A at 10 feet reverberation room 3 Surge Current Rat...

Страница 10: ...2 and Stage 3 to ve AC D2XC2X05 D2XC2X10 UNITS Power Live Neutral Stage 1 Apply power to Sounder L N Stage 2 Apply power to Sounder L N Connect Stage 2 to Common Stage 3 Apply power to Sounder L N Connect Stage 3 to Common Stage 4 Apply power to Sounder L N Connect Stage 2 and Stage 3 to Common OPTIONAL LINE MONITORING RESISTOR CUSTOMER SUPPLIED REQUIRED MINIMUM VALUES R1 24VDC 1KΩ MIN 2W MIN OR 3...

Страница 11: ...therlands B V Utrechtseweg 310 6812 AR Arnhem Netherlands Quality Assurance Notification Module D SIRA 05 ATEX M342 Provisions fulfilled by the equipment II 3G Ex ec IIC T6 T4 T3 T2 T1 Gc II 3D Ex tc IIIC Ex tc IIIC T55 75 80 85 90 95 105 110 C Dc IP66 Ingress Dust Protection to EN60079 0 EN60079 31 Standards applied EN IEC 60079 0 2018 EN IEC 60079 7 2015 A1 2018 EN 60079 31 2014 Directive 2014 3...

Страница 12: ...te and Place of Issue London 22 08 2022 EU Declaration of Conformity On behalf of European Safety Systems Ltd I declare that on the date the equipment accompanied by this declaration is placed on the market the equipment conforms with all technical and regulatory requirements of the above listed directives regulations and standards This Declaration is issued under the sole responsibility of the ma...

Страница 13: ... Lane Eccleston Chester CH4 9JN UK Quality Assurance Notification Module D CSAE 22UKQAN0046 Provisions fulfilled by the equipment II 3G Ex ec IIC T6 T4 T3 T2 T1 Gc II 3D Ex tc IIIC Ex tc IIIC T55 75 80 85 90 95 105 110 C Dc IP66 Ingress Dust Protection to EN60079 0 EN60079 31 Standards applied EN IEC 60079 0 2018 EN IEC 60079 7 2015 A1 2018 EN 60079 31 2014 Directive 2014 30 EU Electromagnetic Com...

Страница 14: ... Place of Issue London 22 08 2022 UKCA Declaration of Conformity On behalf of European Safety Systems Ltd I declare that on the date the equipment accompanied by this declaration is placed on the market the equipment conforms with all technical and regulatory requirements of the above listed directives regulations and standards This Declaration is issued under the sole responsibility of the manufa...

Отзывы:

Похожие инструкции для D2xC2 Series