E2S D2xB1LD2 Скачать руководство пользователя страница 2

 

European Safety Systems Ltd.

   Impress House, Mansell Road, Acton, London W3 7QH

 

www.e2s.com

 

Tel: +44 (0)208 743 8880

 

Document No. D211-00-401-IS

 

Issue 1

 

20-08-22

 

 

Sheet 2 of 7

 

 

3.3. NEC & CEC Ratings 

 
NEC & CEC Class / Division Ratings for US / Canada 

 

Standards 

UL 121201-2021 (Ed. 9) 
CAN/CSA C22.2 No. 213-17 (Ed. 3) 

Ratings 

D2xB1LD2: 
 

Class I Div 2 ABCD T4 Ta -40°C to +50°C 
Class I Div 2 ABCD T4A Ta -40°C to +40°C 
Class II Div 2 FG T6 Ta -40°C to +50°C 
Class III Div 1&2 Ta -40°C to +50°C 
 

Installation must be carried out in compliance with the National 
Electric Code / Canadian Electric Code 

 

NEC Class / Zone ratings US 

 

Standards 

UL 60079-0 (Ed. 7): 

Explosive Atmospheres - part 0: Equipment - General 
Requirements  

UL 60079-7 (Ed. 5): 

Explosive Atmospheres - Equipment Protection by Increased 

Safety "e" 

UL 60079-31 (Ed. 2) 

Explosive Atmospheres - Equipment Dust Ignition Protection by 

Enclosure "t"

 

Ratings 

D2xB1LD2: 
 

Class I Zone 2 AEx ec IIC Gc T4 Ta -40°C to 
+50°C 
AEx tc IIIC T75°C Dc Ta -40°C to +50°C 

Installation must be carried out in compliance with the National 
Electric Code. 

 

CEC Class / Zone ratings Canada 

 

Standards 

CAN/CSA C22.2 No. 60079-0 (Ed. 4) 02/2019 

Explosive Atmospheres - Part 0: Equipment - General 
Requirements  

CAN/CSA C22.2 No. 60079-7 (Ed. 2) 

Explosive Atmospheres - Equipment Protection by Increased 

Safety "e" 

CAN/CSA C22.2 No. 60079-31 (Ed. 2) 

Explosive Atmospheres - Equipment Dust Ignition Protection by 

Enclosure "t"

 

Rating 

D2xB2LD2: 

 

Ex ec IIC Gc X T4 Ta -40°C to +50°C 
Ex tc IIIC T75°C Dc X Ta -20°C to +50°C 
 

Installation must be carried out in compliance with the Canadian 
Electric Code 

 

 
 
 
 
 
 

4)  Zones, Gas Group, Category and 

Temperature Classification 

 

When connected to an approved system the D2XB1LD2 LED 
beacon may be installed in: 
 

Area Classification 

Zone 2 

Explosive gas air mixture not likely to occur in 
normal operation, and if it does, it will only 
exist for a short time. 

Zone 22 

Explosive dust air mixture not likely to occur in 
normal operation, and if it does, it will only 
exist for a short time. 

Gas Groupings 

Group IIA 

Propane 

Group IIB 

Ethylene 

Group IIC 

Hydrogen and Acetylene 

Temperature Classification for Gas Applications 

T1 

450ºC  

T2 

300ºC 

T3 

200ºC 

T4 

135°C 

Dust Groupings 

(ATEX / IECEx / UKEX only) 

Group IIIA 

Combustible Flyings 

Group IIIB 

Non-conductive Dust 

Group IIIC 

Conductive Dust 

Maximum Surface Temperature for Dust Applications 

(ATEX / IECEx / UKEX only) 

D2xB1LD2: 

75°C 

Equipment Category 

3G / 3D  

Equipment Level Protection 

Gc, Dc 

Ambient Temperature Range 

-40°C to +50°C 

IP Rating 

IP6X to EN/IEC60079-0 

IP66 to EN60529 
To maintain the ingress protection rating, the two off cable entries 
must be fitted with suitably rated, certified cable entry and/or 
blanking devices during installation. 

Type Rating 

Per UL50E / NEMA250: 4 / 4X / 3R / 13

 

 

Installation must be carried out in compliance with the 
latest issue of the following standards: 

 
EN60079-14 / IEC60079-14: Explosive atmospheres - 
Electrical installations design, selection and erection 
EN60079-10-1 / IEC60079-10-1: Explosive atmospheres - 
Classification of areas. Explosive gas atmospheres 
EN60079-10-2 / IEC60079-10-2: Explosive atmospheres –  
Classification of areas. Explosive dust atmospheres 

Содержание D2xB1LD2

Страница 1: ...n For use in public mode the beacon must be without the wire guard or plastic lens cover See fire instruction manual D211 00 401 IS SC UL 3 2 ATEX IECEx UKEx Ratings Standards EN IEC 60079 0 2018 IEC6...

Страница 2: ...20 C to 50 C Installation must be carried out in compliance with the Canadian Electric Code 4 Zones Gas Group Category and Temperature Classification When connected to an approved system the D2XB1LD2...

Страница 3: ...st first be fitted to the base using the 2 off M4 X 12mm countersunk screws provided Additional feet are available as spare parts if required The unit can also be pole mounted using the NPT Entry in t...

Страница 4: ...used If fitting 2 off wires to one terminal way the sum of the 2 off wires must be a maximum cross sectional area of 2 5mm Strip wires to 8mm Wires may also be fitted using ferrules Terminal screws ne...

Страница 5: ...g crimp terminal to secure the earth conductor to the earth stud The external earth conductor should be at least 4mm2 in size The external earth crimp ring should be located between the two M5 plain w...

Страница 6: ...new lens cover aligning the fixing holes of the guard lens cover and housing Refit the fixings to hold into place the fixings MUST be fitted in the order shown above 14 Maintenance Overhaul Repair Mai...

Страница 7: ...3Hz 104mA 143mA Flashing 2Hz 103mA 146mA Flashing Double Strike 122 4mA 180mA Flashing Triple Strike 144 8mA 211 2mA D2xB1LD2AC115 115Vac 60Hz 115 120Vac 50 60Hz Steady High Power 83mA 102 4mA Steady...

Страница 8: ...on 10 For light output ratings see section 2 Up to 6 off units can be connected to the same wire run without a separate synchronization module and meet the synchronization requirements of UL1971 UL163...

Страница 9: ...h rate 0 100 38 38 35 87 25 97 5 25 90 34 54 32 28 23 37 30 45 75 28 79 26 90 19 48 50 55 21 11 14 28 14 28 55 45 17 27 11 69 11 69 60 40 15 35 10 39 10 39 65 35 13 43 9 09 9 09 70 35 13 43 9 09 9 09...

Страница 10: ...L 1971 UL1638 CAN ULC S526 at worst case min input voltage 2 4 On axis light output rating private mode Table 3 Vertical Light Output Dispersion for Ceiling Mounting Viewing Angle Of Rating Intensity...

Страница 11: ...7QH www e2s com Tel 44 0 208 743 8880 Document No D211 00 401 IS SC UL Issue A 22 07 2022 Sheet 4 of 4 3 Electrical Ratings 3 1 Surge current for Fire Alarm system use Table 6 Surge Currents Model No...

Страница 12: ...attern Apply power to ve ve Stage 2 Flash Pattern Apply power to ve ve Connect Stage 2 to ve Stage 3 Flash Pattern Apply power to ve ve Connect Stage 3 to ve AC LED D2XB1LD2 UNITS Power Live Neutral R...

Страница 13: ...herlands B V Utrechtseweg 310 6812 AR Arnhem Netherlands Quality Assurance Notification Module D SIRA 05 ATEX M342 Provisions fulfilled by the equipment II 3G Ex ec IIC T6 T4 T3 T2 T1 Gc II 3D Ex tc I...

Страница 14: ...e and Place of Issue London 22 08 2022 EU Declaration of Conformity On behalf of European Safety Systems Ltd I declare that on the date the equipment accompanied by this declaration is placed on the m...

Страница 15: ...Lane Eccleston Chester CH4 9JN UK Quality Assurance Notification Module D CSAE 22UKQAN0046 Provisions fulfilled by the equipment II 3G Ex ec IIC T6 T4 T3 T2 T1 Gc II 3D Ex tc IIIC Ex tc IIIC T55 75 80...

Страница 16: ...Place of Issue London 22 08 2022 UKCA Declaration of Conformity On behalf of European Safety Systems Ltd I declare that on the date the equipment accompanied by this declaration is placed on the marke...

Отзывы: