background image

 

 

European Safety Systems Ltd.

   Impress House, Mansell Road, Acton, London W3 7QH

 

www.e2s.com

 

Tel: +44 (0)208 743 8880

 

Document No. D190-00-671-IS

 

Issue 1

 

27-10-2022

 

 

Sheet 2 of 15

 

 

3) 

Marking & Rating Information 

 

The  D1xS2  Alarm  Horns  comply  with  the  following  standards  for 
hazardous locations:  

 

3.1.  Class/Division Ratings for US & Canada 

 

Standards 

Class I UL 1203 & CSA C22.2 No 30-M1986

 

Class Division Ratings for US (NEC) 

Model No: 

Rating 

D1xS2F- 
DC024-S  

Class I Div 1 ABCD T4A Ta -55°C to +85°C

 

Class I Div 1 ABCD T5 Ta -55°C to +80°C

 

Class I Div 1 ABCD T6 Ta -55°C to +65°C

 

Class Division Ratings for Canada (CEC)

 

Model No:

 

Rating

 

D1xS2F- 
DC024-A  

Class I Div 1 ABCD T4A Ta -55°C to +85°C

 

Class I Div 1 ABCD T5 Ta -55°C to +80°C

 

Class I Div 1 ABCD T6 Ta -55°C to +65°C

 

Class Zone Ratings for US (NEC)

 

Model No:

 

Rating

 

D1xS2F- 
DC024-S 

Class I Zone 1 IIC T4A Ta -55°C to +85°C

 

Class I Zone 1 IIC T5 Ta -55°C to +80°C

 

Class I Zone 1 IIC T6 Ta -55°C to +65°C

 

Class Zone Ratings for Canada (CEC)

 

Model No:

 

Rating

 

D1xS2F- 
DC024-A  

Class I Zone 1 IIC T4A Ta -55°C to +85°C

 

Class I Zone 1 IIC T5 Ta -55°C to +80°C

 

Class I Zone 1 IIC T6 Ta -55°C to +65°C

 

Installation must be carried out in compliance with the National 
Electric Code / Canadian Electric Code 

 

3.2.  ATEX / IECEx & UKEx Ratings 

 

Standards 

EN60079-0:2018/IEC60079-0:2017 (ed.7): Explosive Atmospheres - 

Equipment General Requirements.

 

EN60079-1:2014/IEC60079-1:2014 (ed.7): Explosive Atmospheres - 

Equipment Protection by Flameproof Enclosures “d”.

 

EN60079-31:2014/IEC60079-31:2013 

(ed.2): 

Explosive 

Atmospheres - Equipment Dust Ignition Protection by enclosure “t”.

 

Model No: 

Rating 

D1xS2F- 
DC024-S 

Ex db IIC T5 Gb Ta 

55°C to +75°C 

Ex db IIC T6 Gb Ta 

55°C to +60°C 

Ex tb IIIC T95°C Db Ta 

55°C to +75°C 

See Product table for electrical ratings of each unit model

 

 

Certificate No.    

DEMKO  19ATEX2141X  
IECEx ULD 19.0008X 

 

UKEx UL UL21UKEX2132X          

Epsilon x 
Equipment Group 
and Category: 

 

II 2G 
II 2D

 

CE Marking and 
Notified Body No.

 

 

2813

 

UKCA Marking and 
Notified Body No. 

 

 

0518 

 
 
 
 

4) 

Zones, Gas Group, Category and 
Temperature Classification 

 

The units can be installed in locations with the following conditions: 

 

Area Classification Gas 

Zone 1 

Explosive gas air mixture likely to occur in normal 
operation. 

Zone 2 

Explosive gas air mixture not likely to occur in 
normal operation, and if it does, it will only exist for 
a short time. 

Gas Groupings 

Group IIA 

Propane 

Group IIB 

Ethylene 

Group IIC 

Hydrogen and Acetylene 

Temperature Classification for Gas Applications 

T1 

450

o

 C  

T2 

300

o

 C 

T3 

200

o

 C 

T4 

135

o

 C 

T5 

100ºC 

T6 

85ºC (D1xS2FDC024-S up to 60°C ambient) 

Area Classification Dust 

Zone 21 

Explosive dust air mixture likely to occur in normal 
operation. 

Zone 22 

Explosive dust air mixture not likely to occur in 
normal operation, and if it does, it will only exist for 
a short time. 

Dust Groupings 

Group IIIA 

Combustible Dusts 

Group IIIB 

Non-Conductive Dusts 

Group IIIC 

Conductive Dusts 

Equipment Category 

2G, 2D

 

Equipment Protection Level 

Gb, Gc, Db, Dc

 

Maximum Surface Temperature for Dust Applications 

95°C (D1xS2FDC024-S) 

Ambient Temperature Range 

-55°C to +75°C (-67°F to +167°F) 

IP Rating 

IP66 to EN60529 
4 / 4X / 3R / 13 to UL50E / NEMA250 

Installation must be carried out in compliance with the latest issue 

of the following standards:

 

  

EN60079-14  /  IEC60079-14:  Explosive  atmospheres  -  Electrical 

installations design, selection and erection

 

EN60079-10-1  /  IEC60079-10-1:  Explosive  atmospheres  - 

Classification of areas. Explosive gas atmospheres

 

EN60079-10-2  /  IEC60079-10-2:  Explosive  atmospheres  - 

Classification of areas. Explosive dust atmospheres

 

 
 

 

Содержание D1xS2FDC024-S

Страница 1: ...UNS WITHIN 18 INCHES FROM ENCLOSURE EQUIPMENT MUST NOT BE INSTALLED WITH THE HORN FACING UPWARDS OF HORIZONTAL DO NOT OPEN WHEN AN EXPLOSIVE ATMOSPHERE IS PRESENT DO NOT OPEN WHEN ENERGISED POTENTIAL...

Страница 2: ...C Ex tb IIIC T95 C Db Ta 55 C to 75 C See Product table for electrical ratings of each unit model Certificate No DEMKO 19ATEX2141X IECEx ULD 19 0008X UKEx UL UL21UKEX2132X Epsilon x Equipment Group an...

Страница 3: ...use a build up of electrostatic charges on non conducting surfaces Only the explosionproof cover is to be used for access to the enclosure for installation service and maintenance 6 Specific Condition...

Страница 4: ...on the line and the length of the cable runs The cable size selected must have the necessary capacity to provide the input current to all the sounders connected to the line DC 0 2 2 5mm2 AWG24 AWG12 F...

Страница 5: ...witching Fig 6 Stage Switching Polarity 9 3 Tone Selection The D1x Alarm Horn Sounders have 64 different tones that can be selected independently for the first and second stage alarms The tones are se...

Страница 6: ...0 5W or a minimum resistance value of 500 ohms and a minimum wattage of 2W The resistor must be connected directly across the ve and ve terminals as shown in the following drawing The resistor leads s...

Страница 7: ...End of Line Devices may be fitted between the ve ve terminals of the PCBA Please ensure that the device legs meet the wire size range stated for the connection terminals and are fitted correctly in or...

Страница 8: ...perates as part of a SIL 2 system The sounder will after commissioning remain powered in Standby mode reverse polarity until the sounder is required to operate When the signaling device is required to...

Страница 9: ...rity mode When Commissioning system the power must not be disrupted to the SIL 2 Unit within the unit s initialization cycle which is 5 seconds Once past this period the SIL 2 system is fully operatio...

Страница 10: ...heck on pattern generation and signal output checks Important Only tones use tones that are stated as SIL 2 approved for the SIL 2 application Ensure that the unit is set to one of these tones see in...

Страница 11: ...rom the circuit Note a cable short circuit will not be detectable in this configuration For one unit only Sounder power supply terminal block Current drawn mA Active Mode 190mA Standby Mode 25mA SIL2...

Страница 12: ...multiple SIL 2 alarm horn sounders are to be cabled in series the monitoring connections differ from that of a single alarm horn sounder For more information see manual D197 00 651 IS available from t...

Страница 13: ...ion B pins 2 3 linked Places power supply terminal Fault resistor RLY 1 2 in circuit As used in 2 Wire Configuration Figure 14 J2 Header pin positions Fault Resistor FR 16 4 SIL 2 Hard Reset Function...

Страница 14: ...ound output despite no input D1xS2FDC024 S Failure to Sound Integrity in respect of failure to release SIL 2 Total Failure rate 0 447 pmh hazardous failure rate revealed 0 443 pmh hazardous failure ra...

Страница 15: ...g The values of resistors available are shown in table 7 below Code Resistor Value Default resistor coding as follows D1xS2FDC024AB1S1R AFZ Example of a custom requirement resistor coding D1xS2FDC024A...

Страница 16: ...0 1 0 0 1 0 1 1 0 0 1 0 0 0 1 0 1 0 1 0 1 0 1 0 0 1 1 0 1 0 1 1 1 0 1 0 1 1 0 1 1 0 0 0 1 1 1 0 0 1 1 1 1 0 0 0 0 0 0 1 0 1 0 0 0 1 1 1 0 0 0 1 0 0 1 0 0 1 1 0 1 0 0 1 0 1 1 0 0 1 1 1 1 0 0 1 0 0 0 1...

Страница 17: ...OUT Common ve IN Common ve OUT Stage 2 ve Stage 1 ve IN Stage 1 ve OUT Common ve IN Common ve OUT Stage 2 ve Stage 3 ve EOL EOL S2 EOL S2 S3 Stage 1 ve IN Stage 1 ve OUT Stage 1 ve IN Stage 1 ve OUT...

Страница 18: ...S NTS SWITCHES FOR STAGE OPERATION CUSTOMER SUPPLIED Stage 2 ve Common ve IN Common ve OUT Stage 1 ve OUT Stage 3 ve Stage 1 ve IN H2 H1 OF 2 2 EOL S2 S3 OPTIONAL LINE MONITORING RESISTOR CUSTOMER SUP...

Страница 19: ...warden Industrial Park Hawarden Deeside CH5 3US UK Quality Assurance Notification Module D SIRA 05 ATEX M342 Provisions fulfilled by the equipment II 2G Ex db IIC T6 T3 GB II 2D Ex tb IIIC T82 C 145 C...

Страница 20: ...e and Place of Issue London 10 02 2022 EU Declaration of Conformity On behalf of European Safety Systems Ltd I declare that on the date the equipment accompanied by this declaration is placed on the m...

Страница 21: ...CH4 9JN UK Quality Assurance Notification Module D CSAE 22UKQAN0046 Provisions fulfilled by the equipment II 2G Ex db IIC T6 T3 GB II 2D Ex tb IIIC T82 C 145 C Db Standards applied EN 60079 0 2018 EN...

Страница 22: ...te and Place of Issue London 24 02 2022 UKCA Declaration of Conformity On behalf of European Safety Systems Ltd I declare that on the date the equipment accompanied by this declaration is placed on th...

Отзывы: