European Safety Systems Ltd.

   Impress House, Mansell Road, Acton, London W3 7QH           [email protected]              Tel: +44 (0)208 743 8880 

                                                                                                                                                             www.e2s.com             Fax: +44 (0)208 740 4200 
Document No. D190-00-301-IS-SC     Issue:  8                        24-04-19               Sheet 1 of 8 

 

INSTRUCTION & SERVICE MANUAL 

D1xC COMBINED ALARM HORNS & STROBES 

 For Use In Hazardous Locations - Gas 

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

1) 

Introduction 

 
The D1xC1 & D1xC2 range are UL Classified combined alarm 
horns  and  strobes  which  produce  a  loud  warning  signal  in  a 
hazardous  area.  Sixty-Four  first  stage  alarm  sounds  can  be 
selected  by  internal  switches  and  each  one  can  be  externally 
changed  to  a  second,  third  or  fourth  stage  alarm  sound.  The 
alarm  horn  may  be  used  for  Gas  applications  in  Class  I 
Division 1  &  2  as  well  as  Class  I  Zone  1  &  2.  The  D1xC1X05 
variants  are  also  ATEx  /  IECEx  certified  and  can  be  used  for 
gas applications in Zones 1 & 2.  D1xS1 & D1xS2 alarm horns 
and  D1xL1  &  D1xL2  Loudspeakers  are  also  available  as  well 
as variants for Explosive Dust Atmospheres. 

 

2)  Warnings 

 
CAUTION 
TO REDUCE THE RISK OF IGNITION OF HAZARDOUS 
ATMOSPHERES: 
DISCONNECT FROM SUPPLY BEFORE OPENING. 
KEEP TIGHTLY CLOSED WHEN IN OPERATION. 
WARNING 
FIT SEALING FITTING IN CONDUIT RUNS WITHIN 18 
INCHES FROM ENCLOSURE. 
EQUIPMENT MUST NOT BE INSTALLED WITH THE HORN 
FACING UPWARDS OF HORIZONTAL 
DO NOT OPEN WHEN AN EXPLOSIVE ATMOSPHERE IS 
PRESENT 

 

DO NOT OPEN WHEN ENERGISED  
POTENTIAL ELECTROSTATIC CHARGING HAZARD - 
CLEAN ONLY WITH A DAMP CLOTH  
 
ATTENTION 
P

OUR REDUIRE LE RISQUE D’INFLAMMATION  DES 

ATMOSPHÈRES DANGEREUSES: 
COUPER L 'ALIMENTATION AVANT OUVERTURE. 
CONSERVER FERMÉ PENDANT LE FONCIONNEMENT. 
AVERTISSEMENT 
CONDUITS DOIVENT ÊTRE SCELLÉS EN MOINS DE 18 
POUCES. 
ÉQUIPEMENT NE DOIT PAS ÊTRE INSTALLÉ AVEC LE 
KLAXON TOURNÉE VERS LE HAUT DE HORIZONTAL. 
NE PAS OUVRIR UN PRESENCE D’ATMOSPHERE 
EXPLOSIVE  
NE PAS OUVRIR ENERGIE  
DANGER POTENTIEL CHARGE ÉLECTROSTATIQUE - 
NETTOYER UNIQUEMENT AVEC UN CHIFFON HUMIDE  

 
 
 
 
 
 
 
 
 

3)  Ratings and Markings 

 
The  D1xC1  and  D1xC2  combined  alarm  horns  and  strobes 
comply with the following standards for hazardous locations:  

 

UL 1203 
CSA C22.2 NO. 30-M1986 

 

The  D1xC1  and  D1xC2  combined  alarm  horns  and  strobes 
also  comply  with  the  following  standards  for  signaling 
equipment:  

 

UL464, UL1638 
CSA C22.2 NO. 205-12 

 

3.1 Class / Division Ratings for US & Canada 

 

The  D1xC1X05-DC024  /  D1xC1X05-AC115  combined  alarm 
horns and strobes are rated as follows: 
Class I Div 1 

ABCD 

T5 

Ta -40°C to +70°C 

Class I Div 1 

ABCD 

T6 

Ta -40°C to +55°C 

 

The D1xC1X05-AC230 combined alarm horns and strobes are 
rated as follows: 
Class I Div 1  

ABCD 

T6 

Ta -40°C to +55°C 

 

The  D1xC1X10  /  D1xC2X05  /  D1xC2X10  combined  alarm 
horns and strobes are rated as follows: 
Class I Div 1 

ABCD 

T5 

Ta -40°C to +55°C 

Class I Div 1  

ABCD 

T6 

Ta -40°C to +50°C 

 

Installation must be carried out in compliance with the National 
Electric Code / Canadian Electric Code 
 

3.2 Class / Zone ratings for US & Canada

 

 
The  D1xC1X05-DC024  /  D1xC1X05-AC115  combined  alarm 
horns and strobes are rated as follows: 
Class I Zone 1 

IIC 

T5 

Ta -40°C to +70°C 

Class I Zone 1 

IIC 

T6 

Ta -40°C to +55°C 

 
The D1xC1X05-AC230 combined alarm horns and strobes are 
rated as follows: 
Class I Zone 1 

IIC 

T6 

Ta -40°C to +55°C 

 
The  D1xC1X10  /  D1xC2X05  /  D1xC2X10  combined  alarm 
horns and strobes are rated as follows: 
Class I Zone 1 

IIC 

T5 

Ta -40°C to +55°C 

Class I Zone 1 

IIC 

T6 

Ta -40°C to +50°C 

 
Installation must be carried out in compliance with the National 
Electric Code / Canadian Electric Code 

 
 
 
 
 

The D1xC1 & D1xC2 combined alarm horns & 

strobes are classified by UL as Audible 

Signaling Appliances for General Signaling 

and Public Mode Fire Alarm use in 

Hazardous Locations 

 

Содержание D1xC1 Series

Страница 1: ...S DE 18 POUCES ÉQUIPEMENT NE DOIT PAS ÊTRE INSTALLÉ AVEC LE KLAXON TOURNÉE VERS LE HAUT DE HORIZONTAL NE PAS OUVRIR UN PRESENCE D ATMOSPHERE EXPLOSIVE NE PAS OUVRIR ENERGIE DANGER POTENTIEL CHARGE ÉLECTROSTATIQUE NETTOYER UNIQUEMENT AVEC UN CHIFFON HUMIDE 3 Ratings and Markings The D1xC1 and D1xC2 combined alarm horns and strobes comply with the following standards for hazardous locations UL 1203 ...

Страница 2: ...th the following standards for hazardous locations EN60079 0 2018 IEC60079 0 ed 7 0 2017 EN60079 1 2014 IEC60079 1 ed 7 0 2014 The D1xC1X05DC024 Combined Alarm Horns are rated as follows Ex db IIC T4 Gb Ta 40 C to 75 C Ex db IIC T5 Gb Ta 40 C to 60 C Ex db IIC T6 Gb Ta 40 C to 45 C The D1xC1X05AC115 Combined Alarm Horns are rated as follows Ex db IIC T4 Gb Ta 40 C to 75 C Ex db IIC T5 Gb Ta 40 C t...

Страница 3: ...40Vac 60Hz D1xC2X05 DC024 24Vdc 924 mA 323 mA 1247 mA 20 28Vdc 1477 mA 20Vdc D1xC2X05 AC115 115Vac 60Hz 268 mA 130 mA 398 mA 110 120Vac 50 60Hz 446 mA 110Vac 60Hz D1xC2X05 AC230 230Vac 50Hz 159 mA 79 mA 238 mA 220 240Vac 50 60Hz 255 mA 220Vac 60Hz D1xC2X10 DC024 24Vdc 924 mA 673 mA 1597 mA 20 28Vdc 1984 mA 20Vdc D1xC2X10 AC115 115Vac 60Hz 268 mA 247 mA 515 mA 110 120Vac 50 60Hz 604 mA 120Vac 60Hz ...

Страница 4: ...ree 7mm fixing holes The enclosure provides IP66 protection and is suitable for installation in exterior locations providing it is positioned so that water cannot collect in the horn and the cable entry is sealed 4 4 Installation procedure a Secure the D1x alarm horn to a flat surface via the three 7mm fixing holes in the mounting bracket b Remove the explosionproof cover of the alarm horn by unsc...

Страница 5: ...es on first and second stages and which tones are available for the third and fourth stages dependent on the Stage 1 DIP switch setting 8 Stage Switching Polarity DC Units Only The D1xC2 and D1xC1 DC alarm horns have the facility to use either ve or ve switching to change the tone to the second third and fourth stages For ve switching connect the two headers on the pcb to the left hand marked ve a...

Страница 6: ...witch 1 alters stage 4 tone Fig 8 DC Terminals 11 Earthing The unit has both a primary internal and secondary external earth fixing point Internal earth connections should be made to the internal Earth terminal see Fig 3 and 4 It should be fitted to the internal earth point using a ring crimp terminal to secure the earth conductor In addition external earth connections can be made to the M5 earth ...

Страница 7: ... 9 34 1 10 1000Hz 1s on 1s off x7 7s on 1s off IMO Code 1a 1 0 0 1 0 0 10 34 1 11 420Hz 0 5s on 0 5s off x3 1s gap ISO 8201 Temporal Pattern 0 1 0 1 0 0 11 1 8 12 1000Hz 0 5s on 0 5s off x3 1s gap ISO 8201 Temporal Pattern 1 1 0 1 0 0 12 1 8 13 422 775Hz 0 85 on 0 5 off x3 1s gap NFPA Temporal Coded 0 0 1 1 0 0 13 1 8 14 1000 2000Hz 1Hz Singapore 1 0 1 1 0 0 14 3 35 15 300Hz Continuous 0 1 1 1 0 0...

Страница 8: ... 0 1 48 24 12 49 560 1055Hz 0 18Hz Sweeping 0 0 0 0 1 1 49 24 12 50 560 1055Hz 3 3Hz Sweeping 1 0 0 0 1 1 50 24 12 51 600 1250Hz 0 125Hz Sweeping 0 1 0 0 1 1 51 24 12 52 660 1200Hz 1Hz Sweeping 1 1 0 0 1 1 52 24 12 53 800 1000Hz 1Hz Sweeping 0 0 1 0 1 1 53 24 12 54 800 1000Hz 7Hz Sweeping 1 0 1 0 1 1 54 24 12 55 800 1000Hz 50Hz Sweeping 0 1 1 0 1 1 55 24 12 56 2400 2900Hz 7Hz Sweeping 1 1 1 0 1 1 ...

Отзывы: