17-1) SIL 2 System Wiring for Fault Detection in Standby and Active Mode 

 4 Wire Installation 

(Recommended) 

 
The customer is required to wire into both the beacon power supply terminals and also the SIL 2 Relay terminals TB1. 
 
The power supply  terminals only need to have the supply power connected. This will be reverse polarity for monitoring mode and 
normal polarity for active mode. There is no need to fit an EOL resistor on the power supply terminal as the TB1 is configured to raise 
a fault alarm in any situation. 
 
Terminal block TB1 is the output from the SIL 2 monitoring relay. Relay RLY 1-2 provides a closed circuit between TB1 terminals 1 & 
2 whilst powered. On detection of a fault event this will become open circuit. 
 
The fault will be seen via the SIL 2 TB1 terminals as soon as the fault occurs in either Active or Standby modes. 
 
When no fault is detected the circuit to the SIL 2 TB1 terminals 1 & 2 will include a factory fitted 3.3K Ohm current sense resistor 
(CSR) in series. When the circuit is driven with 24Vdc the detection current seen is ~7.3mA @ 24V. 
 
The only other fault mode is if the cable goes short circuit where a short will be seen by the panel.  
 

Option:

 Should the fault event output of RLY1-2 be required to operate as a switch, header J1 can be set to link pins 1 & 2 (see Figure 

11) thereby removing the 3.3k Ohm current sense resistor (CSR) from the circuit. 
 

Note

: a cable short circuit will not be detectable in this configuration. 

 

 

 

For one unit only: 

Beacon power 

supply terminal 

block

 

Current  drawn 

(mA)

 

Active Mode 

190mA 

Standby Mode 

25mA 

 

 

SIL2 

TB1 Current 

Sense Resistor 

value

 

Current drawn 

(mA)

 

3.3kΩ

 

7.2mA 

On fault mode, current drops to 0 as 
circuit goes open. 

 
Figure 11: Schematic of SIL 2 system wiring for fault detection in standby and active mode 

 4 wire installation. 

 
If multiple SIL 2 alarm horn sounders are to be cabled in series, the monitoring connections differ from that of a single beacon. For 
more information see manual D197-00-621-IS available from the E2S website. 

 
 

17-2) SIL 2 System Wiring for Fault Detection in Standby Mode Only 

 2 Wire Installation 

 
Cabling is required to the positive '+' and negative '-' power input terminals only.  Monitoring will occur in standby mode only whilst 
power supply polarity is reversed. An EOL resistor may be added during installation or can be factory fitted. See Table  4 for EOL 
resistor value guidance. 
 
The SIL2 monitoring module contains a factory fitted Power Supply Fault Resistor 2.2k Ohm (FR). When a fault is detected the Fault 
Resistor  will  activated.  The  total  measurable  resistance  of  the  EOL  resistor  and  Fault  Resistor  across  the  power  terminals  which 

already has customer EOL resistor (2.2kΩ) in place. This will result in a total fault detection current of 41.8mA @ 24V but

 can only be 

detected when unit is in Standby Mode. 
 

Important

: - The 2 wire configuration will not warn of a fault whilst in Active mode. A fault will only be detectable in standby mode 

when power supply polarity is reversed. 
 

Important

: - The 2-wire configuration requires the J2 header pin to be set to position B (see figure 14). Factory default position is A. 

 

Содержание D1xB2X05-S

Страница 1: ...IQUE NETTOYER UNIQUEMENT AVEC UN CHIFFON HUMIDE HAUT TENSION RISK DE CHOC ATTENDEZ 5 MINUTES APRES AVOIR DEBRANCHE L ALIMENTATION AVANT D OUVRIR LA BOITIER NE PAS PEINTURER POUR R DUIRE LE RISQUE D IN...

Страница 2: ...ss III Div 1 Ta 55 C to 80 C Installation must be carried out in compliance with the National Electric Code Canadian Electric Code 2 4 NEC Class Zone ratings US The D1xB2X Xenon beacons comply with th...

Страница 3: ...t for a short time Zone 21 Explosive dust air mixture likely to occur in normal operation Zone 22 Explosive dust air mixture not likely to occur in normal operation and if it does it will only exist f...

Страница 4: ...14 Explosive atmospheres Electrical installations design selection and erection EN60079 10 1 IEC60079 10 1 Explosive atmospheres Classification of areas Explosive gas atmospheres EN60079 10 2 IEC6007...

Страница 5: ...in explosive gas atmospheres a minimum ingress protection rating of IP54 must be maintained NPT plugs should be greased before insertion For high ambient temperatures the cable entry temperature or t...

Страница 6: ...h conductor should be at least equal in size and rating to the incoming power conductors External earthing connections should be made to the M5 earth stud using a ring crimp terminal to secure the ear...

Страница 7: ...s MUST be fitted in the order shown above 13 Maintenance Overhaul Repair Maintenance repair and overhaul of the equipment should only be carried out by suitably qualified personnel in accordance with...

Страница 8: ...and Active mode Health status of power supply Beacons correct function and flash pattern The SIL 2 beacon operates as part of a SIL 2 system The beacon will after commissioning remain powered in Stan...

Страница 9: ...equire further investigation please contact your local E2S representative Commissioning System Functional start up of System Normally in reverse polarity mode When Commissioning system the power must...

Страница 10: ...h it is highly recommended that the unit is wired as stated in section 17 1 as a 4 Wire System J1 Header Current Sense Resistor CSR Shown in factory default position A see section 17 3 places TB1 Curr...

Страница 11: ...he circuit Note a cable short circuit will not be detectable in this configuration For one unit only Beacon power supply terminal block Current drawn mA Active Mode 190mA Standby Mode 25mA SIL2 TB1 Cu...

Страница 12: ...multiple SIL 2 alarm horn sounders are to be cabled in series the monitoring connections differ from that of a single beacon For more information see manual D197 00 621 IS available from the E2S webs...

Страница 13: ...tion B pins 2 3 linked Places power supply terminal Fault Resistor RLY 1 2 in circuit As used in 2 Wire Configuration Figure 14 J2 Header pin positions Fault Resistor FR 17 4 SIL 2 Hard Reset Function...

Страница 14: ...ndom Hardware Failures and Architectural constraints route 1H 2 As an unvoted item i e hardware fault tolerance of 0 at SIL 2 The product was assessed against failure modes Failure respond to an input...

Страница 15: ...specified when ordering The values of resistors available are shown in table 5 below Code Resistor Value Default resistor coding is as follows D1xB2X05DC024AS1S1R A AFZ Example of a custom requirement...

Страница 16: ...ATERIAL SHEET SCALE TITLE A3 IF IN DOUBT ASK DO NOT SCALE ALL DIMENSIONS IN MM DRAWING NUMBER A B C D E F G 10 9 G F E 7 8 6 5 D C 1 3 4 2 A B D191 06 621 M ABALOS B ISARD R N POTTS OF NTS 1 1 23 09 2...

Страница 17: ...Gb II 2D Ex tb IIIC T95 C T169 C Db Standards applied EN 60079 0 2018 EN 60079 1 2014 EN 60079 31 2014 IP6X Dust Protection to EN60079 0 EN60079 31 Directive 2014 30 EU Electromagnetic Compatibility...

Страница 18: ...Ex d IIC T6 T3 Gb II 2D Ex tb IIIC T95 C T169 C Db Standards applied EN 60079 0 2018 EN 60079 1 2014 EN 60079 31 2014 IP6X Dust Protection to EN60079 0 EN60079 31 Directive 2014 30 EU Electromagnetic...

Отзывы: