INSTRUCTION MANUAL 

D1xB2X05-S, D1xB2X10-S, D1xB2X15-S 

Xenon Beacons 

 SIL2 

For use in Hazardous Locations 

 

E2S Warning Signals

      Impress House, Mansell Road, Acton, London W3 7QH

 

www.e2s.com

 

Tel: +44 (0)208 743 8880

 

Document No. D191-00-621-IS

 

Issue 1

 

27-10-22

 

 

Sheet 1 of 15

 

  

 
 

 

D1xB2X05-S 
D1xB2X10-S 
D1xB2X15-S 

 

 
 

1)  Warnings 

 

 DO NOT OPEN WHEN AN EXPLOSIVE 

ATMOSPHERE IS PRESENT 

 DO NOT OPEN WHEN ENERGISED 

 POTENTIAL ELECTROSTATIC CHARGING 

HAZARD - CLEAN ONLY WITH A DAMP 
CLOTH 

 HIGH VOLTAGE SHOCK HAZARD. WAIT 5 

MINUTES AFTER REMOVING POWER 
BEFORE OPENING THE ENCLOSURE 

 DO NOT PAINT 

 TO REDUCE THE RISK OF IGNITION OF 

HAZARDOUS ATMOSPHERES, THE FIRST 
CONDUIT RUN MUST HAVE A SEALING 
FITTING CONNECTED WITHIN 18 INCHES 
OF ENCLOSE. SUBSEQUENT CONDUIT 
RUNS MUST HAVE A SEALING FITTING 
CONNECTED AS CLOSE AS PRACTICAL TO 
THE WALL OF THE ENCLOSURE, BUT IN 
NO CASE MORE THAN THE SIZE OF THE 
CONDUIT OR 50MM, WHICHEVER IS THE 
LESSER. 

 TO PREVENT IGNITION OF GROUP A, B, C 

AND D ATMOSPHERES - SEE       
INSTRUCTION FOR CHEMICAL 
COMPATIBILITY 

 

Avertissement: 
 

 NE PAS OUVRIR UN PRESENCE 

D’ATMOSPHERE EXPLOSIVE

 

 NE PAS OUVRIR ENERGIE 

 DANGER POTENTIEL CHARGE 

ÉLECTROSTATIQUE - NETTOYER 
UNIQUEMENT AVEC UN CHIFFON HUMIDE 

 HAUT TENSION, RISK DE CHOC. 

ATTENDEZ 5 MINUTES APRES AVOIR 

DEBRANCHE L’ALIMENTATION AVANT 

D’OUVRIR LA BOITIER

 

 NE PAS PEINTURER 

 POUR RÉDUIRE LE RISQUE 

D'INFLAMMATION DES ATMOSPHÈRES 
DANGEREUSES, LE PREMIER CONDUIT DE 
CONDUIT DOIVENT AVOIR UN RACCORD 
D'ÉTANCHÉITÉ RACCORDÉ À MOINS DE 18 

POUCES DE L'ENFERMEMENT. POUR 
SUBSÉQUENT LES

 

CONDUITES DE 

CONDUIT LA DISTANCE ENTRE LA 
SURFACE DE LA MASSE DE REMPLISSAGE 

AU PLUS PRÈS DE L’ENVELOPPE DOIT 

ÊTRE AUSSI PETITE QUE CE QUI EST 
RÉALISABLE MAIS EN AUCUN CAS 
SUPÉRIEURE À LA PLUS PETITE DES 
DIMENSIONS CORRESPONDANT À LA 
TAILLE DU CONDUIT OU À 50 MM. 

 POUR PRÉVENIR L'INFLAMMATION DES 

ATMOSPHÈRES DES GROUPES A, B, C ET 
D-VOIR L'INSTRUCTION POUR LA 
COMPATIBILITÉ CHIMIQUE 

 

2)  Rating & Marking Information 

 

2.1 Fire Alarm Ratings 

 
The Following models are certified as visual alarm devices for 
fire  alarm  use 

  private  mode  only  when  used  with  Clear  or 

Red lens covers: 
 
D1xB2X05DC024 / D1xB2X10DC024 / D1xB2X15DC024 
 
On-axis light output per UL1638: 
 

Model 
D1xB2

 

Light Intensity in cd

 

Clear Lens

 

Red Lens 

X05DC024-S - 1Hz 

20.44

 

5.89

 

X05DC024-S - 1.33Hz 

14.47

 

4.17

 

X05DC024-S - 1.5Hz 

11.1

 

2.13

 

X10DC024-S - 1Hz 

69.81

 

23.66

 

X10DC024-S - 1.33Hz 

49.42

 

16.75

 

X10DC024-S - 1.5Hz 

35.71

 

8.57

 

X15DC024-S - 1Hz 

98.61

 

31.83

 

X15DC024-S - 1.33Hz 

69.81

 

22.53

 

X15DC024-S - 1.5Hz 

50.44

 

11.53

 

 

Содержание D1xB2X05-S

Страница 1: ...IQUE NETTOYER UNIQUEMENT AVEC UN CHIFFON HUMIDE HAUT TENSION RISK DE CHOC ATTENDEZ 5 MINUTES APRES AVOIR DEBRANCHE L ALIMENTATION AVANT D OUVRIR LA BOITIER NE PAS PEINTURER POUR R DUIRE LE RISQUE D IN...

Страница 2: ...ss III Div 1 Ta 55 C to 80 C Installation must be carried out in compliance with the National Electric Code Canadian Electric Code 2 4 NEC Class Zone ratings US The D1xB2X Xenon beacons comply with th...

Страница 3: ...t for a short time Zone 21 Explosive dust air mixture likely to occur in normal operation Zone 22 Explosive dust air mixture not likely to occur in normal operation and if it does it will only exist f...

Страница 4: ...14 Explosive atmospheres Electrical installations design selection and erection EN60079 10 1 IEC60079 10 1 Explosive atmospheres Classification of areas Explosive gas atmospheres EN60079 10 2 IEC6007...

Страница 5: ...in explosive gas atmospheres a minimum ingress protection rating of IP54 must be maintained NPT plugs should be greased before insertion For high ambient temperatures the cable entry temperature or t...

Страница 6: ...h conductor should be at least equal in size and rating to the incoming power conductors External earthing connections should be made to the M5 earth stud using a ring crimp terminal to secure the ear...

Страница 7: ...s MUST be fitted in the order shown above 13 Maintenance Overhaul Repair Maintenance repair and overhaul of the equipment should only be carried out by suitably qualified personnel in accordance with...

Страница 8: ...and Active mode Health status of power supply Beacons correct function and flash pattern The SIL 2 beacon operates as part of a SIL 2 system The beacon will after commissioning remain powered in Stan...

Страница 9: ...equire further investigation please contact your local E2S representative Commissioning System Functional start up of System Normally in reverse polarity mode When Commissioning system the power must...

Страница 10: ...h it is highly recommended that the unit is wired as stated in section 17 1 as a 4 Wire System J1 Header Current Sense Resistor CSR Shown in factory default position A see section 17 3 places TB1 Curr...

Страница 11: ...he circuit Note a cable short circuit will not be detectable in this configuration For one unit only Beacon power supply terminal block Current drawn mA Active Mode 190mA Standby Mode 25mA SIL2 TB1 Cu...

Страница 12: ...multiple SIL 2 alarm horn sounders are to be cabled in series the monitoring connections differ from that of a single beacon For more information see manual D197 00 621 IS available from the E2S webs...

Страница 13: ...tion B pins 2 3 linked Places power supply terminal Fault Resistor RLY 1 2 in circuit As used in 2 Wire Configuration Figure 14 J2 Header pin positions Fault Resistor FR 17 4 SIL 2 Hard Reset Function...

Страница 14: ...ndom Hardware Failures and Architectural constraints route 1H 2 As an unvoted item i e hardware fault tolerance of 0 at SIL 2 The product was assessed against failure modes Failure respond to an input...

Страница 15: ...specified when ordering The values of resistors available are shown in table 5 below Code Resistor Value Default resistor coding is as follows D1xB2X05DC024AS1S1R A AFZ Example of a custom requirement...

Страница 16: ...ATERIAL SHEET SCALE TITLE A3 IF IN DOUBT ASK DO NOT SCALE ALL DIMENSIONS IN MM DRAWING NUMBER A B C D E F G 10 9 G F E 7 8 6 5 D C 1 3 4 2 A B D191 06 621 M ABALOS B ISARD R N POTTS OF NTS 1 1 23 09 2...

Страница 17: ...Gb II 2D Ex tb IIIC T95 C T169 C Db Standards applied EN 60079 0 2018 EN 60079 1 2014 EN 60079 31 2014 IP6X Dust Protection to EN60079 0 EN60079 31 Directive 2014 30 EU Electromagnetic Compatibility...

Страница 18: ...Ex d IIC T6 T3 Gb II 2D Ex tb IIIC T95 C T169 C Db Standards applied EN 60079 0 2018 EN 60079 1 2014 EN 60079 31 2014 IP6X Dust Protection to EN60079 0 EN60079 31 Directive 2014 30 EU Electromagnetic...

Отзывы: