background image

_______________________________________________________________________________________________________________________________ 

European Safety Systems Ltd.

   Impress House, Mansell Road, Acton, London W3 7QH           [email protected]              Tel: +44 (0)208 743 8880 

                                                                                                                                                             www.e2s.com             Fax: +44 (0)208 740 4200 
Document No. D191-00-201-IS           Issue 1         03-06-2019                         Sheet 2 of 8

 

 

2.3 NEC & CEC Class / Division Ratings for US / Canada 

 
The D1xB2X Xenon beacons comply with the following 
standards: 
 

UL 1203 (Ed. 5) 2018 
UL1638A (Ed. 1) 2016 
UL1638 (Ed. 5) 2017 
CSA C22.2 No. 30-M1986 (Ed. 3) 2016 
CSA C22.2 No. 25 (Ed. 4) 2017 
CSA C22.2 No. 205 (Ed. 3) 2017 

 
The D1xB2X05DC012, D1xB2X05DC024 & 
D1xB2X05DC048 Xenon Beacons are rated as follows: 

 

Class I Div 1 Group ABCD T5 Ta -55°C to +80°C 
Class I Div 1 Group ABCD T6 Ta -55°C to +65°C 
Class II Div 1 Group EFG T5 Ta -55°C to +80°C 
Class III Div 1 Ta -55°C to +80°C 
 

The D1xB2X05AC115 & D1xB2X05AC230 Xenon Beacons 
are rated as follows: 
 

Class I Div 1 Group ABCD T4A Ta -55°C to +70°C 
Class I Div 1 Group ABCD T5 Ta -55°C to +55°C 
Class I Div 1 Group ABCD T6 Ta -55°C to +40°C 
Class II Div 1 Group EFG T4 Ta -55°C to +40°C 
Class III Div 1 Ta -55°C to +40°C 
 

The D1xB2X10DC024 & D1xB2X10DC048 Xenon Beacons 
are rated as follows: 

 

Class I Div 1 Group ABCD T4 Ta -55°C to +80°C 
Class I Div 1 Group ABCD T4A Ta -55°C to +70°C 
Class I Div 1 Group ABCD T5 Ta -55°C to +50°C 
Class II Div 1 Group EFG T4 Ta -55°C to +80°C 
Class III Div 1 Ta -55°C to +80°C 

 

The D1xB2X10AC115 & D1xB2X10AC230 Xenon Beacons 
are rated as follows: 

 

Class I Div 1 Group ABCD T4 Ta -55°C to +70°C 
Class I Div 1 Group ABCD T4A Ta -55°C to +55°C 
Class II Div 1 Group EFG T4 Ta -55°C to +40°C 
Class III Div 1 Ta -55°C to +40°C 

 

The D1xB2X15DC024 & D1xB2X15DC048 Xenon Beacons 
are rated as follows: 

 

Class I Div 1 Group ABCD T3C Ta -55°C to +80°C 
Class I Div 1 Group ABCD T4 Ta -55°C to +55°C 
Class II Div 1 Group EFG T4 Ta -55°C to +80°C 
Class III Div 1 Ta -55°C to +80°C 

 

The D1xB2X15AC115 & D1xB2X15AC230 Xenon Beacons 
are rated as follows: 

 

Class I Div 1 Group ABCD T4 Ta -55°C to +70°C 
Class I Div 1 Group ABCD T4A Ta -55°C to +55°C 
Class II Div 1 Group EFG T4 Ta -55°C to +40°C 
Class III Div 1 Ta -55°C to +40°C 

 

The D1xB2X21DC024 & D1xB2X21DC048 Xenon Beacons 
are rated as follows: 

 

Class I Div 1 Group ABCD T3B Ta -55°C to +80°C 
Class I Div 1 Group ABCD T3C Ta -55°C to +75°C 

Class I Div 1 Group ABCD T4 Ta -55°C to +50°C 
Class II Div 1 Group EFG T3C Ta -55°C to +40°C 
Class III Div 1 Ta -55°C to +40°C 

 

The D1xB2X21AC115 & D1xB2X21AC230 Xenon Beacons 
are rated as follows: 

 

Class I Div 1 Group ABCD T3C Ta -55°C to +60°C 
Class I Div 1 Group ABCD T4 Ta -55°C to +55°C 
Class I Div 1 Group ABCD T4A Ta -55°C to +40°C 
Class II Div 1 Group EFG T4 Ta -55°C to +40°C 
Class III Div 1 Ta -55°C to +40°C 

 

Installation must be carried out in compliance with the 
National Electric Code / Canadian Electric Code 
 

2.4 NEC Class / Zone ratings US 

 
The D1xB2X Xenon beacons comply with the following 
standards: 

 

UL 60079-0 (Ed. 6) 2017 
UL 60079-1 (Ed. 7) 2015 
UL 60079-31 (Ed. 2) 2015 
 

The D1xB2X05DC012, D1xB2X05DC024 & 
D1xB2X05DC048 Xenon Beacons are rated as follows: 

 

Class I Zone 1 AEx db IIC T4 Ta -55°C to +80°C 
Class I Zone 1 AEx db IIC T5 Ta -55°C to +75°C 
Class I Zone 1 AEx db IIC T6 Ta -55°C to +60°C 
Zone 21 AEx tb IIIC T99°C Ta -55°C to +80°C 
 

The D1xB2X05AC115 & D1xB2X05AC230 Xenon Beacons 
are rated as follows: 
 

Class I Zone 1 AEx db IIC T4 Ta -55°C to +70°C 
Class I Zone 1 AEx db IIC T5 Ta -55°C to +50°C 
Zone 21 AEx tb IIIC T153°C Ta -55°C to +70°C 

 
The D1xB2X10DC024 & D1xB2X10DC048 Xenon Beacons 
are rated as follows: 

 

Class I Zone 1 AEx db IIC T4 Ta -55°C to +80°C 
Class I Zone 1 AEx db IIC T5 Ta -55°C to +45°C 
Zone 21 AEx tb IIIC T132°C Ta -55°C to +80°C 

 

The D1xB2X10AC115 & D1xB2X10AC230 Xenon Beacons 
are rated as follows: 

 

Class I Zone 1 AEx db IIC T3 Ta -55°C to +70°C 
Class I Zone 1 AEx db IIC T4 Ta -55°C to +65°C 
Zone 21 AEx tb IIIC T153°C Ta -55°C to +70°C 

 

The D1xB2X15DC024 & D1xB2X15DC048 Xenon Beacons 
are rated as follows: 

 

Class I Zone 1 AEx db IIC T3 Ta -55°C to +80°C 
Class I Zone 1 AEx db IIC T4 Ta -55°C to +65°C 
Zone 21 AEx tb IIIC T132°C Ta -55°C to +80°C 

 

The D1xB2X15AC115 & D1xB2X15AC230 Xenon Beacons 
are rated as follows: 

 

Class I Zone 1 AEx db IIC T3 Ta -55°C to +70°C 
Class I Zone 1 AEx db IIC T4 Ta -55°C to +65°C 
Zone 21 AEx tb IIIC T153°C Ta -55°C to +70°C 

Содержание D1 B2X05 Series

Страница 1: ...NT AVOIR UN RACCORD D TANCH IT RACCORD MOINS DE 18 POUCES DE L ENFERMEMENT POUR SUBS QUENT LES CONDUITES DE CONDUIT LA DISTANCE ENTRE LA SURFACE DE LA MASSE DE REMPLISSAGE AU PLUS PR S DE L ENVELOPPE...

Страница 2: ...ABCD T4A Ta 55 C to 55 C Class II Div 1 Group EFG T4 Ta 55 C to 40 C Class III Div 1 Ta 55 C to 40 C The D1xB2X21DC024 D1xB2X21DC048 Xenon Beacons are rated as follows Class I Div 1 Group ABCD T3B Ta...

Страница 3: ...Beacons are rated as follows Ex db IIC T3 Ta 55 C to 80 C Ex db IIC T4 Ta 55 C to 65 C Ex tb IIIC T132 C Ta 55 C to 80 C The D1xB2X15AC115 D1xB2X15AC230 Xenon Beacons are rated as follows Ex db IIC T...

Страница 4: ...ent Dust Groupings Group IIIA Combustible Flyings Group IIIB Non conductive Dust Group IIIC Conductive Dust Maximum Surface Temperature for Dust Applications 104 C D1xB2X05DC 116 C D1xB2X05AC 135 c D1...

Страница 5: ...codes that may apply and should only be carried out by a competent electrical engineer who has the necessary training 4 1 Safe Installation Requirements To maintain the ingress protection rating and...

Страница 6: ...aling washer must be fitted under the cable glands or blanking plugs For use in explosive dust atmospheres a minimum ingress protection rating of IP6X must be maintained For use in explosive gas atmos...

Страница 7: ...500 Ohms Minimum Power 2 0W The resistor must be connected directly across the ve and ve terminals as shown in the following drawing Form the resistor legs as shown in Fig 7a fit the resistor across...

Страница 8: ...new lens cover Fig 10 Replacement of beacon lens cover Fit the wire guard back onto the housing over the new lens cover aligning the fixing holes of the guard lens cover and housing Refit the fixings...

Отзывы: