Document No. D191-00-201-IS           Issue 1         03-06-2019                         Sheet 6 of 8

 

 

L

N

L L N N

L L N N

L L N N

 
 
 
 
 
 
 
 
 
 
 
 

 
Fig. 2 Accessing the Enclosure. 
 

On  completion  of  the  installation  the  flameproof  threads 
should  be  inspected  to  ensure  that  they  are  clean  and  that 
they  have  not  been  damaged  during  installation.  Ensure  the 
O-ring seal is in place and undamaged.  
 
When  fitting  the  flameproof  cover  ensure  the  thread  is 
engaged correctly. Fully tighten the cover all the way, ensure 
no  gap  is  visible between  the  cover and  base  of  the  beacon 
enclosure. 

 

7)  Selection of Cable, Cable Glands, Blanking 

Elements & Adapters 

 

 

When  selecting  the  cable  size,  consideration  must  be  given 
to the input current that each unit draws (see section 11), the 
number  of  beacons  on  the  line  and  the  length  of  the  cable 
runs.  The  cable  size  selected  must  have  the  necessary 
capacity  to  provide  the  input  current  to  all  of  the  beacons 
connected to the line.  
The entries are 2-off M20 x 1.5 thread & 3-

off ¾” NPT thread 

 
If  a  high  IP  (Ingress  Protection)  rating  is  required  then  a 
suitable sealing washer must be fitted under the cable glands 
or blanking plugs. 
 
For  use  in  explosive  dust  atmospheres,  a  minimum  ingress 
protection rating of IP6X must be maintained. 
 
For  use  in  explosive  gas  atmospheres,  a  minimum  ingress 
protection rating of IP54 must be maintained. 
NPT plugs should be greased before insertion. 
 
For high ambient temperatures the cable entry temperature 
or the cable branching point temperature may exceed 60ºC 
and therefore suitable heat resisting cables and cable glands 
must be used, with a rated service temperature of at least the 
values stated below: 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

8)  Cable Connections

 

 

The units have 2-off M20 x 1.5 threaded entries and 3-

off ¾” 

NPT x 14 threaded entries. 

 

Electrical  Connections  are  to  be  made  into  the  terminal 
blocks using solid or stranded wire, sizes 0.5-2.5mm2 / AWG 
20-14.  Wire  insulation  needs  to  be  stripped  6-7mm.  Wires 
may be fitted securely with crimped ferrules. Terminal screws 
need to be tightened down with a tightening torque of 0.4 Nm 
/ 3.5 Lb-in. 
See section 5 of this manual for access to the enclosure. 

 

9)  Wiring 

 

A  4-way  terminal  block  is  provided  on  the  DC  beacons  for 
power. There are 2-off +ve, 2-off 

–ve terminal and an internal 

Earth boss. 
 

9.1 

Wiring Diagrams 

 

Fig. 3 D1xB2X Simplified Block Diagram  

 
 

Terminals 
  -  -  +  + 

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 

Fig. 4 D1xB2XDC Terminals 

 

A  5-way  terminal  block  is  provided  on  the  AC  beacons  for 
power.  There  are  2-off  Live,  2-off  Neutral  and  an  Earth 
terminal. 

 
 
 
 
 
 
 
 
 
 

Fig. 5 D1xB2X Simplified Block Diagram  

Glass dome 
cover 

3/4" NPT 
Entry 
 

M20 Entry 

3/4" NPT 
Conduit 
Entry 

Содержание D1 B2X05 Series

Страница 1: ...NT AVOIR UN RACCORD D TANCH IT RACCORD MOINS DE 18 POUCES DE L ENFERMEMENT POUR SUBS QUENT LES CONDUITES DE CONDUIT LA DISTANCE ENTRE LA SURFACE DE LA MASSE DE REMPLISSAGE AU PLUS PR S DE L ENVELOPPE...

Страница 2: ...ABCD T4A Ta 55 C to 55 C Class II Div 1 Group EFG T4 Ta 55 C to 40 C Class III Div 1 Ta 55 C to 40 C The D1xB2X21DC024 D1xB2X21DC048 Xenon Beacons are rated as follows Class I Div 1 Group ABCD T3B Ta...

Страница 3: ...Beacons are rated as follows Ex db IIC T3 Ta 55 C to 80 C Ex db IIC T4 Ta 55 C to 65 C Ex tb IIIC T132 C Ta 55 C to 80 C The D1xB2X15AC115 D1xB2X15AC230 Xenon Beacons are rated as follows Ex db IIC T...

Страница 4: ...ent Dust Groupings Group IIIA Combustible Flyings Group IIIB Non conductive Dust Group IIIC Conductive Dust Maximum Surface Temperature for Dust Applications 104 C D1xB2X05DC 116 C D1xB2X05AC 135 c D1...

Страница 5: ...codes that may apply and should only be carried out by a competent electrical engineer who has the necessary training 4 1 Safe Installation Requirements To maintain the ingress protection rating and...

Страница 6: ...aling washer must be fitted under the cable glands or blanking plugs For use in explosive dust atmospheres a minimum ingress protection rating of IP6X must be maintained For use in explosive gas atmos...

Страница 7: ...500 Ohms Minimum Power 2 0W The resistor must be connected directly across the ve and ve terminals as shown in the following drawing Form the resistor legs as shown in Fig 7a fit the resistor across...

Страница 8: ...new lens cover Fig 10 Replacement of beacon lens cover Fit the wire guard back onto the housing over the new lens cover aligning the fixing holes of the guard lens cover and housing Refit the fixings...

Отзывы: