European Safety Systems Ltd.
Impress House, Mansell Road, Acton, London W3 7QH
www.e2s.com
Tel: +44 (0)208 743 8880
Document No. D210-00-681-IS
Issue 5
09-05-2023
Sheet 5 of 8
11. AC Wiring
Four connections must be made to the BExCTS110-05D AC
unit. A power supply input cable should enter the enclosure via
one of the M20 entries and a telephone signal cable should
enter through the other M20 entry.
Connect the power input (L) to the telephone board (L/+)
terminal in the sounder section & power input (N) to the beacon
board (N) terminal in the beacon section.
Connect the telephone signal input to (TB1) on the telephone
board in the sounder section. See Figure 4
Fig 4 BExCTS110-05D AC Wiring Diagram
Fig. 5a Sounder AC Terminals
Fig. 5b Beacon AC Terminals
12. DC Wiring
Four connections must be made to the BExCTS110-05D DC
unit. A power supply input cable should enter the enclosure via
one of the M20 entries and a telephone signal cable should
enter through the other M20 entry.
Connect the power input (+) to the telephone board (L/+)
terminal in the sounder section & power input (-) to the beacon
board (-) terminal in the beacon section.
Connect the telephone signal input to (TB1) on the telephone
board in the sounder section. See Figure 5
Fig 6 BExCTS110-05D DC Wiring Diagram
DIP Switch
Volume Control
Stage
Terminals
AC
Terminals
S2
S3
C
N
L
L
L
N
N
Interconnecting Terminals
to sounder PCB
(simultaneous
mode of operation)
TB1 Telephone
Signal
Input Terminals
TB3 Sounder
Mains Supply
Output L
Telephone Setting DIP Switch
TB2 Beacon
Mains Supply
Output L
LLTerminals
L and N