INSTRUCTION MANUAL
BExCTS110-05D-P& BExCTS110-05D-R-P
Combined Sounder & Beacon with Call Relay
ATEx/IECEx & UKEx Gas & Dust
European Safety Systems Ltd.
Impress House, Mansell Road, Acton, London W3 7QH
www.e2s.com
Tel: +44 (0)208 743 8880
Document No. D210-00-681-IS
Issue 5
09-05-2023
Sheet 1 of 8
BExCTS110-05D-P
BExCTS110-05D-R-P
1. Product Table
Unit Type Code
Nominal
Input
Voltage
Sounder
Nominal
Input Current
Beacon
Nominal
Input Current
Max I/P Voltage
Sound
Pressure Level
dB(A)
Max*
Nom
.†
BExCTS110-05DPDC012 /
BExCTS110-05DPDC012-R
12Vdc
195mA
750mA
14V
Flare:
117dB(A)
Radial:
115dB(A)
Flare:
110dB(A)
Radial:
110dB(A)
BExCTS110-05DPDC024 /
BExCTS110-05DPDC024-R
24Vdc
265mA
300mA
28V
BExCTS110-05DPDC048 /
BExCTS110-05DPDC048-R
48Vdc
130mA
180mA
54V
BExCTS110-05DPAC115 /
BExCTS110-05DPAC115-R
115Vac
110mA
140mA
126V
BExCTS110-05DPAC230 /
BExCTS110-05DPAC230-R
230Vac
56mA
55mA
253V
*Max = Tone 4
†
Nom. = Tone 44
The table shows the input current taken by the various units.
The current levels shown above are for the 440Hz Continuous tone @ nominal input voltage.
Nominal current at nominal voltage.
Table 1: Electrical Ratings.
It is important that a suitable power supply is used to run the equipment. The power supply selected must have the necessary capacity
to provide the input current to all of the units.
The above table shows the input current taken by the various sounders and shows the maximum voltage at which the sounders can
be operated:
The input current will vary according to the voltage input level and the frequency of the tone selected.
2. Warnings
•
DO NOT OPEN WHEN AN EXPLOSIVE ATMOSPHERE IS PRESENT
•
DO NOT OPEN WHEN ENERGIZED
•
POTENTIAL ELECTROSTATIC CHARGING HAZARD
– CLEAN ONLY WITH A DAMP CLOTH
•
COVER BOLTS CLASS A4-80
•
USE HEAT RESISTING CABLES AND CABLE GLANDS (RATED 110°C) AT AMB. TEMPERATURES OVER
40°C
Содержание BExCTS110-05D-P
Страница 16: ...Page left Intentionally blank...