background image

 

 

European Safety Systems Ltd.

   Impress House, Mansell Road, Acton, London W3 7QH

www.e2s.com

 

Tel: +44 (0)208 743 8880

Document No. D210-00-601-IS

 

Issue 8

 

12-09-2022

Sheet 4 of 7

 

8.  Selection of Cable. Cable Glands, Blanking 

Elements & Adapters 

 

When selecting the cable size, consideration must be given to 
the input current that each unit draws (see table above), the 
number  of  sounders  on  the  line  and  the  length  of  the  cable 
runs.  The  cable  size  selected  must  have  the  necessary 
capacity  to  provide  the  input  current  to  all  of  the  sounders 
connected to the line.  

 

For  ambient  temperatures  over  +40ºC  the  cable  entry 
temperature  may  exceed  +70ºC  and  therefore  suitable  heat 
resisting cables and cable glands must be used, with a rated 
service temperature of at least 110ºC 

 

The dual cable gland entries have an M20 x 1.5 entry thread. 
To  maintain  the  ingress  protection  rating  and  mode  of 
protection, the cable entries must be fitted with suitably rated 
ATEX / IECEx or UKEx certified cable glands and/or suitably 
rated ATEX / IECEx or UKEx certified blanking devices during 
installation according to EN / IEC60079-14. 

 

If  a  high  IP  (Ingress  Protection)  rating  is  required  then  a 
suitable sealing washer must be fitted under the cable glands 
or blanking plugs.  

 

For  use  in  explosive  dust  atmospheres,  a  minimum  ingress 
protection rating of IP6X must be maintained. 

 

The  BEx  combined  sounder/beacon  range  can  be  supplied 
with the following types of adapters: 

 

M20 to ½” NPT 
M20 to ¾” NPT 
M20 to M25 
It is important to note that stopping plugs cannot be fitted onto 
adapters, only directly onto the M20 entries. 
 
Any other adapters used must be suitably rated and ATEX / 
IECEx or UKEx certified adapters. 

 

9.  Earthing 

 

Both AC and DC sounder units must be connected to an earth. 
The  units  are  provided  with  internal  and  external  earth 
terminals  which  are  both  located  on  the  terminal  chamber 
section of the unit. 

 

Fig. 3 Internal View of Cover 

 

When  using  the  internal  earth  terminal  ensure  that  the 
stainless steel M4 flat washer is between the incoming earth 
wire and the enclosure.  

 

Internal earthing connections should be made to the Internal 
Earth terminal in the base of the housing using a ring crimp 

terminal to secure the earth conductor under the earth clamp. 
The earth conductor should be at least equal in size and rating 
to the incoming power conductors. Tighten M4 Earth screw to 
1Nm. 

 

External earthing connections should be made to the M5 earth 
stud, using a ring crimp terminal to secure the earth conductor 
to the earth stud. The external earth conductor should be at 
least 4mm² in size.

 

Tighten the Earth nut to 3Nm. Please firmly 

tighten the external grounding terminal so that the stud does 
not  become  loose  and  lay  the  ground  wire  so  that  it  is  not 
caught by twisting and sagging. 

 

10.  Cable Connections 

 

Electrical connections are to be made into the terminal blocks 
on the PCBA located in the flameproof enclosure. See section 
7 of this manual for access to the flameproof enclosure.  

 

Wires  having  a  cross  sectional  area  between  0.5  mm²  to 
2.5mm² can be connected to each terminal way. If an input and 
output wire is required the 2-off Live/Neutral or +/- terminals 
can be used. If fitting 2-off wires to one terminal way the sum 
of the 2-off wires must be a maximum cross sectional area of 
2.5mm².  Strip  wires  to  8mm.  Wires  may  also  be  fitted  using 
ferrules.  Terminal  screws  need  to  be  tightened  down  with  a 
tightening torque of 0.45 Nm / 5 Lb-in. When connecting wires 
to the terminals great care should be taken to dress the wires 
so that when the cover is inserted into the chamber the wires 
do not exert excess pressure on the terminal blocks. This is 
particularly  important  when  using  cables  with  large  cross 
sectional areas such as 2.5mm². 
 

11.  AC Wiring 

 

 

 

 

Fig. 4a AC Terminals 

 

 

External Earthing 

Internal 
Earthing 

Internal 
Bonding 
Wire 
Terminal 

2-off M20 
Cable 
Entries 

DIP Switch 

Volume Control 

Stage 

Terminals 

AC 

Terminals 

S2 

 

S3 

 

 

N  

 

Содержание BExCS110-05

Страница 1: ...05DPAC230 BExCS110 05DPAC230 R 230Vac 56mA 55mA 253V Max Tone 4 Nom Tone 44 The table shows the input current taken by the various units The current levels shown above are for the 440Hz Continuous to...

Страница 2: ...air mixture not likely to occur in normal operation and if it does it will only exist for a short time Gas Groupings Group IIA Propane Group IIB Ethylene Temperature Classification for Gas Application...

Страница 3: ...it cannot move in service Fig 1a Fixing Location for Combined Flare Fig 1b Fixing Location for Combined Radial 7 Access to the Flameproof Enclosure To access the Ex d chamber remove the four M6 hexago...

Страница 4: ...section of the unit Fig 3 Internal View of Cover When using the internal earth terminal ensure that the stainless steel M4 flat washer is between the incoming earth wire and the enclosure Internal ear...

Страница 5: ...m power rating of 0 5 watts or a minimum resistance value of 500 and a minimum power rating of 2 watts The resistor must be connected directly across the ve and ve terminals as shown in the following...

Страница 6: ...sounder on stage one simply connect the supply voltage to the normal supply terminals ve and ve for DC units L and N for AC units Refer to wiring schematics D210 06 601 DC or D210 06 605 AC Default To...

Страница 7: ...Repair Maintenance repair and overhaul of the equipment should only be carried out by suitably qualified personnel in accordance with the current relevant standards EN60079 19 IEC60079 19 Explosive at...

Страница 8: ...mittent 660Hz 1 8s on 1 8s off 1 0 0 0 1 0 2 5 19 1400Hz to 1600Hz sweeep up over 1s 0 1 0 0 1 0 2 5 1600Hz to 1400Hz sweep down over 0 5s 20 Continuous 660Hz 1 1 0 0 1 0 2 5 21 Alternating 554 440Hz...

Страница 9: ...Page left Intentionally blank...

Страница 10: ...ER SUPPLIED 500 MIN 2W MIN OR 3K3 MIN 0 5W MIN MINIMUM VALUES R1 Single Stage Configuration Config 1a Line Monitoring Set to negative switching default Stage 1 Apply Power to Stage 1 ve Stage 1 ve Two...

Страница 11: ...RFACE FINISH MATERIAL ALTERNATIVE MATERIAL SHEET SCALE TITLE A3 IF IN DOUBT ASK DO NOT SCALE ALL DIMENSIONS IN MM DRAWING NUMBER A B C D E F G 10 9 G F E 7 8 6 5 D C 1 3 4 2 A B D210 06 605 R S RAIT B...

Страница 12: ...cation Conformity to EU type based on quality assurance of the production process Module D Sira Certification Service Notified Body No 2813 CSA Group Netherlands B V Utrechtseweg 310 6812 AR Arnhem Ne...

Страница 13: ...te and Place of Issue London 21 05 2020 EU Declaration of Conformity On behalf of European Safety Systems Ltd I declare that on the date the equipment accompanied by this declaration is placed on the...

Страница 14: ...X2639X Notified Body for Quality Assurance Notification Conformity to EU type based on quality assurance of the production process Module D Sira Certification Service Notified Body No 0518 Rake Lane E...

Страница 15: ...nd Place of Issue London 12 09 2022 UKCA Declaration of Conformity On behalf of European Safety Systems Ltd I declare that on the date the equipment accompanied by this declaration is placed on the ma...

Страница 16: ...Page left Intentionally blank...

Отзывы: