background image

 

 

 

European Safety Systems Ltd.

  

Impress House, Mansell Road, Acton, London W3 7QH    

 

 

[email protected]

     Tel: +44 (0)208 743 8880 

                                                                                                                                                        

www.e2s.com

    Fax: +44 (0)208 740 4200 

Document No. D165-00-001-IS_Issue_3    16-11-22 
 

Sheet 8 of 10 

Quick Ref - Mass Erase Mode (Erases All Stages)

 

 

Set 

Switch ‘S2’ position  

7 to 'ON' 

 

 

Set jumper 
‘ME’ to ON position 
(centre and bottom pin 
connected) 

 

 

Switch on power or  
Press reset button 

 

 

4a 

Press action button: 
Erase will begin 

 

 

4b 

- - - - erase complete 

 

 

Reset Jumper  
‘ME’ to OFF position 

 

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

Содержание APPELLO A121AX

Страница 1: ...ice of one of forty five tones The Beacon functions are either Xenon Strobe 1Hz flash rate LED Either Steady or 2Hz blink rate 2 Operating and Marking All units have the following operating requirements and limitations Unit Type No Voltage Range Current Sounder only outputs A121AX DC 24Vdc 14 30Vdc 1 51A MV121 DC Max Current 1 85A 30Vdc A121AX AC 115Vac 90 260Vac 542mA MV121 AC 230Vac 90 260Vac 51...

Страница 2: ...emove header for steady mode Keep header in standard position for 2Hz flashing mode 5 Unit Set up and Recording The unit will need to be configured to suit the end user If recording either via the onboard microphone or the in line connector the unit will need to be supplied with power DC units can be powered when completing recording and set up Warning During set up on AC units care must be taken ...

Страница 3: ...ge to the second third or fourth stage tone link the ve supply line to terminal relevant stage terminal Ie for Stage 2 link the ve supply to the S2 terminal for Stage 3 link the ve supply to the S3 terminal etc AC Units Second Third and Fourth Stage Selection The Appello unit uses Live switching to change the tone to the second third and fourth stages To change to the second third or fourth stage ...

Страница 4: ...tup Guide The following guide is designed to get the user quickly interfacing with the Appello unit The Appello unit can be set up to either play an attention seeking tone and then a recorded message or just play the recorded message The user can o Record on each of the 4 stages using either the Line In or Microphone inputs o Select the required alarm tone o Delete unwanted messages To re record a...

Страница 5: ...Stage 3 Switch 2 Off Switch 3 Off Alarm Stage 4 3 Stage selection switch 4 Line In selected On board Microphone selected 5 Program Record Erase Mode ON Playback Record Erase Mode OFF 6 Message Tone Playback Message only Playback 7 Single Message or Mass Erase Mode OFF Single Message or Mass Erase Mode ON Quick Ref Playback Mode Stage 1 illustrated 1 For Stage 1 Set Switch S2 positions 1 2 3 5 to O...

Страница 6: ...e 3 Set Switch S2 positions 2 4 to ON For Stage 4 Set Switch S2 position 4 to ON To record from Line in instead of the on board microphone follow above step 1 but set Switch S2 position 4 to OFF 2 Switch on power or Press reset button 3a Press action button Start recording 3b Speak into microphone or plug line in It is suggested that a 5cm gap is maintained to the microphone The peak detector L E ...

Страница 7: ...3 16 11 22 Sheet 7 of 10 Quick Ref Erase Single stage Mode Stage 1 illustrated 1 For Stage 1 Set Switch S2 positions 2 3 7 to ON Alternatively for For Stage 2 Set Switch S2 positions 3 7 to ON For Stage 3 Set Switch S2 positions 2 7 to ON For Stage 4 Set Switch S2 position 7 to ON 2 Switch on power or Press reset button 3a Press action button Erase will begin 3b erase complete ...

Страница 8: ...740 4200 Document No D165 00 001 IS_Issue_3 16 11 22 Sheet 8 of 10 Quick Ref Mass Erase Mode Erases All Stages 1 Set Switch S2 position 7 to ON 2 Set jumper ME to ON position centre and bottom pin connected 3 Switch on power or Press reset button 4a Press action button Erase will begin 4b erase complete 5 Reset Jumper ME to OFF position ...

Страница 9: ...jumper to SY on Set jumper MA on Master unit to master position on Set jumper MA on Slave unit to slave position off Position of S2 switch does not affect synch operation 3 Switch on power onto the Master unit first Then switch power onto the Slave unit Master Unit Slave Unit 4a Press action button on the Master Unit Synchronisation will begin Duration 13 Minutes Master Unit Slave Unit 4b Synchron...

Страница 10: ...one 19 1 4KHz 1 6KHz 1s 1 6KHz 1 4KHz 0 5s NFC48 265 Tone 2 Tone 5 Tone 29 Tone 20 660Hz Continuous Tone 2 Tone 5 Tone 29 Tone 21 554Hz 440Hz 1Hz Alternating Tone 2 Tone 5 Tone 29 Tone 22 544Hz 0 875 sec Intermittent Tone 2 Tone 5 Tone 29 Tone 23 800Hz 2Hz Intermittent Tone 6 Tone 5 Tone 29 Tone 24 800 1000Hz 50Hz Sweeping Tone 29 Tone 5 Tone 29 Tone 25 2400 2900Hz 50Hz Sweeping Tone 29 Tone 5 Ton...