1)  Introduction 

The  Appello  tone  and  speech  annunciation 
sounder has three different styles in AC and DC. 

 

A121AX Sounder 

 

MV121 Sounder 

 

AL121AXH High Output LED 
Sounder-Beacon Combination unit 

 

AL121AXX Xenon Strobe 
Sounder-Beacon Combination unit 
 

These  Sounder  units  share  a  common  set  of 
functions:- 

 

4  stages,  each  stage  can  record  up  to  30 
seconds of CD quality audio. 

 

Facility to record via an on board microphone 
or a line in input. 

 

The  recorded  message  can  be  played  back 
proceeded  either  with  or  without  the  choice 
of one of forty five tones. 
 

The Beacon functions are either:- 

 

Xenon Strobe - 1Hz flash rate 

 

LED - Either Steady or 2Hz blink rate 

2)  Operating and Marking 

 
All 

units 

have 

the 

following 

operating 

requirements and limitations. 
 
Unit Type No.     Voltage    Range          Current 
Sounder only outputs 
A121AX DC  

24Vdc    14-30Vdc      1.51A  

& MV121 DC 
 

 

Max Current 1.85A @ 30Vdc 

A121AX AC 

115Vac   90-260Vac   542mA 

& MV121 AC 

230Vac   90-260Vac   517mA 

 

 

Max Current 668mA @ 90Vac 

 
AL121AXH / AL121AXX combined unit - Add 
selected sounder & beacon currents to calculate 
total current required. 
  
 

 

Beacon only outputs 

AL121AXH DC   24Vdc    10-30Vdc      157mA 
 

 

Max Current 166mA @ 30Vdc 

AL121AXH AC 

115Vac  90-260Vac    60mA 

 

 

230Vac  90-260Vac    35mA 

 

 

Max Current 60mA @ 90Vac 

 
AL121AXX DC   12Vdc    10-14Vdc      500mA 
 

 

24Vdc    20-28Vdc      250mA 

AL121AXX AC   /-10%Vac     100mA 
 

 

/-10%Vac     50mA 

 
 
 

Operating Temp:  -20 to +55

All units IP Rating: Type 4 / 4X / 3R / 13 , IP66 
MV121    

additional IP Rating: IP67 

 

Marking:  

 

 

 

 

3)  Installation & Wiring Requirements

 

 
A121AX 

 

 
 
AL121AXH / AL121AXX 

 

 
MV121 

 

A121AX 
UNIT 

AL121AXH / 
AL121AXX 
UNITS 

MV121 
UNIT 

Содержание APPELLO A121AX

Страница 1: ...ice of one of forty five tones The Beacon functions are either Xenon Strobe 1Hz flash rate LED Either Steady or 2Hz blink rate 2 Operating and Marking All units have the following operating requirements and limitations Unit Type No Voltage Range Current Sounder only outputs A121AX DC 24Vdc 14 30Vdc 1 51A MV121 DC Max Current 1 85A 30Vdc A121AX AC 115Vac 90 260Vac 542mA MV121 AC 230Vac 90 260Vac 51...

Страница 2: ...emove header for steady mode Keep header in standard position for 2Hz flashing mode 5 Unit Set up and Recording The unit will need to be configured to suit the end user If recording either via the onboard microphone or the in line connector the unit will need to be supplied with power DC units can be powered when completing recording and set up Warning During set up on AC units care must be taken ...

Страница 3: ...ge to the second third or fourth stage tone link the ve supply line to terminal relevant stage terminal Ie for Stage 2 link the ve supply to the S2 terminal for Stage 3 link the ve supply to the S3 terminal etc AC Units Second Third and Fourth Stage Selection The Appello unit uses Live switching to change the tone to the second third and fourth stages To change to the second third or fourth stage ...

Страница 4: ...tup Guide The following guide is designed to get the user quickly interfacing with the Appello unit The Appello unit can be set up to either play an attention seeking tone and then a recorded message or just play the recorded message The user can o Record on each of the 4 stages using either the Line In or Microphone inputs o Select the required alarm tone o Delete unwanted messages To re record a...

Страница 5: ...Stage 3 Switch 2 Off Switch 3 Off Alarm Stage 4 3 Stage selection switch 4 Line In selected On board Microphone selected 5 Program Record Erase Mode ON Playback Record Erase Mode OFF 6 Message Tone Playback Message only Playback 7 Single Message or Mass Erase Mode OFF Single Message or Mass Erase Mode ON Quick Ref Playback Mode Stage 1 illustrated 1 For Stage 1 Set Switch S2 positions 1 2 3 5 to O...

Страница 6: ...e 3 Set Switch S2 positions 2 4 to ON For Stage 4 Set Switch S2 position 4 to ON To record from Line in instead of the on board microphone follow above step 1 but set Switch S2 position 4 to OFF 2 Switch on power or Press reset button 3a Press action button Start recording 3b Speak into microphone or plug line in It is suggested that a 5cm gap is maintained to the microphone The peak detector L E ...

Страница 7: ...3 16 11 22 Sheet 7 of 10 Quick Ref Erase Single stage Mode Stage 1 illustrated 1 For Stage 1 Set Switch S2 positions 2 3 7 to ON Alternatively for For Stage 2 Set Switch S2 positions 3 7 to ON For Stage 3 Set Switch S2 positions 2 7 to ON For Stage 4 Set Switch S2 position 7 to ON 2 Switch on power or Press reset button 3a Press action button Erase will begin 3b erase complete ...

Страница 8: ...740 4200 Document No D165 00 001 IS_Issue_3 16 11 22 Sheet 8 of 10 Quick Ref Mass Erase Mode Erases All Stages 1 Set Switch S2 position 7 to ON 2 Set jumper ME to ON position centre and bottom pin connected 3 Switch on power or Press reset button 4a Press action button Erase will begin 4b erase complete 5 Reset Jumper ME to OFF position ...

Страница 9: ...jumper to SY on Set jumper MA on Master unit to master position on Set jumper MA on Slave unit to slave position off Position of S2 switch does not affect synch operation 3 Switch on power onto the Master unit first Then switch power onto the Slave unit Master Unit Slave Unit 4a Press action button on the Master Unit Synchronisation will begin Duration 13 Minutes Master Unit Slave Unit 4b Synchron...

Страница 10: ...one 19 1 4KHz 1 6KHz 1s 1 6KHz 1 4KHz 0 5s NFC48 265 Tone 2 Tone 5 Tone 29 Tone 20 660Hz Continuous Tone 2 Tone 5 Tone 29 Tone 21 554Hz 440Hz 1Hz Alternating Tone 2 Tone 5 Tone 29 Tone 22 544Hz 0 875 sec Intermittent Tone 2 Tone 5 Tone 29 Tone 23 800Hz 2Hz Intermittent Tone 6 Tone 5 Tone 29 Tone 24 800 1000Hz 50Hz Sweeping Tone 29 Tone 5 Tone 29 Tone 25 2400 2900Hz 50Hz Sweeping Tone 29 Tone 5 Ton...

Отзывы: