20
Byte
Type
Range
Description
Action commands 0
byte
0 ... 255
116 = reset trip counter
118 = reset device parameters to factory settings including
CPC12
1)
131 = back to box
2)
132 = adopt device type
configurations to connected devices
(see chapter 9.2.3).
192 = reset statistics minimum values
196 = reset statistics maximum values
220 = reset statistics mean values
Other values will not be accepted.
fig. 19: Action commands CPC12
1)
The command »118 = reset device parameters to factory settings including CPC12« within the action commands for the
CPC12 shall reset the following data:
• parameters (current ratings = 10 A, limit value load current = 80 %) of each channel
• PLC lock bit of each channel (default = True, i.e. Channel not to be controlled by the PLC)
•
not the configured device types
•
not the statistical values (min, max, avg) of the channels
•
not the error memory, trip counter and trip reason of the channels
• configuration data
- power saving mode = False = LEDs normal
- behavior of load outputs after fieldbus interruption = True = status is maintained
- writing via web server permitted = True
2)
The command »131 = back-to-box« within the action commands for the CPC12 shall reset the following data:
• Parameters (rated current = 10 A, limit value load current = 80 %) of each channel
• PLC lock bit of each channel (default = True, i.e. Channel not controllable by PLC)
• configured device types (default = REX12D-TA1 = 0x9009 = 36873)
• the statistical values (min, max, avg) of the channels
• the error memory, trip counter and trip reason of the channels
• configuration data
- power saving mode = False = LEDs normal
- behavior of the load outputs on fieldbus interruption = True = Status is maintained
- Writing via web server permitted = True
• IP configuration of the third ETH port X1
- IP address = 192.168.1.1
- Netmask = 255.255.255.0
- gateway = 192.168.1.254
- DHCP = False
• User data
- Name = »admin«
- Password = »admin«
9.1.3 Action commands CPC12 controller
The action commands of the controller consist of 1 byte. All action commands being sent to the CPC12 carry out the action for
all channels.
Class ID = 100, Instance ID = 1 and Attribute ID = 4
Service Code: Set_Attribute_Single (16)
Action commands with possible conditions are described in the following table.