9 Non-cyclical data
Explicit EtherNet/IP messages allow exchange of further data with the CPC12 controller and the circuit protectors. Access also
allows direct addressing of a circuit protector. EtherNet/IP Class, Instance and Attribute are required. For reading and editing
CPC12 data, Class 100 is used. Class 101 is used for reading and editing the data of circuit protectors. The access to the circuit
protectors is divided into channels. Two channels are provided per circuit protector.
The non-cyclical access to the data of CPC12 is divided as follows:
Class 100 and Class 101 support only service codes Get_Attribute_Single (14) and Set_Attribute_Single (16).
The non-cyclical access to the data of circuit protectors and/or channels is divided as follows:
Class
ID
Instance
ID
Attribute
ID
Number of
data bytes
Reading (R)
writing (W)
Description
100
1
1
19
R
Device information of CPC12 controller
(see chapter 9.1.1).
100
1
3
5
R/W
Configuration data of CPC12 controller
(see chapter 9.1.2).
100
1
4
1
W
Action commands for all channels and the CPC12 controller
(see chapter 9.1.3).
100
1
2
4
R
Dynamic information of CPC12 controller
(see chapter 9.1.4).
Class
ID
Instance
ID
Attribute
ID
Number of
data bytes
Reading (R)
writing (W)
Description
101
01 … 32
3
2
R/W
Device parameters of a channel
(see chapter 9.2.1).
101
01 … 32
1
19
R
Device information of a channel
(see chapter 9.2.2).
101
01 … 32
6
2
R/W
Configuration data of a channel
(see chapter 9.2.3).
101
01 … 32
5
1
R
Event message of a channel
(see chapter 9.2.4).
101
01 … 32
4
1
W
Action commands for a channel
(see chapter 9.2.5).
101
01 … 32
2
22
R
Diagnosis data of a channel
(see chapter 9.2.6).
fig. 15: CPC12 Object Attributes
fig. 16: Channel Object Attributes