8
fig. 9: Signalling RJ45 connectors
3.7.4 PROFINET interfaces with integral switch, connection
sleeve XF1, XF2
XF1
Connection to bus system PROFINET
Type: RJ45
When wiring and connecting to the bus system PROFINET the installation and wiring
regulations of the PROFIBUS User Organisation (PNO) have to be observed.
XF2
Connection to bus system PROFINET
Type: RJ45
When wiring and connecting to the bus system PROFINET the installation and wiring
regulations of the PROFIBUS User Organisation (PNO) have to be observed
LED
colour
description
US1
green
Normal duty, SF or BF possible.
orange
The breaker is in the start-up phase.
red blinking Firmware update is presently carried out.
BF
orange
The breaker is in the start-up phase.
red blinking Firmware update is presently carried out.
red
Bus error
SF
orange
The breaker is in the start-up phase.
red blinking Firmware update is presently carried out.
red
System error
ACT
OFF
No activity
blinking
yellow
Activity available
LNK
OFF
No link available
green
blinking
PROFINET devices localisation
green
Link available
XF2
LED ACT
LED LNK
LED ACT
LED LNK
XF1
3.7.5 ETHERNET interface, connection sleeve X1
X1
connection with bus controller CPC20
Type: RJ45
3.7.6 LED status indication
Содержание ControlPlex CPC20
Страница 1: ...User Manual ControlPlex CPC20PN Controller...
Страница 31: ...31 Notes...