7
3.7.1 Terminals for voltage supply
supply XD1
Voltage ratings: DC 24 V (± 10 % 18 ... 30 V)
Rated current: typically 160 mA
Terminal design: 4 x push-in terminals (+/+/0V/0V)
Max. cable cross section rigid
0.2 – 2.5 mm
2
flexible with wire end ferrule (with plastic sleeve)
0.2 – 2.5 mm
2
flexible with wire end ferrule (without plastic sleeve) 0.2 – 2.5 mm
2
stripping length
11 mm
Using a supply voltage outside the indicated operating range can cause
malfunctions or destruction of the device.
The CPC20 has a direct and fixed connection between the housing shield of
the RJ45 connectors (XF1, XF2 and X1) and the 0V of X41.
3.7.2 Connector for the additional ELBus
®
X2
Direct connection with 18plus (no wiring required)
X52COM-2: Connection for the second power distribution system 18plus
Cable length max. 3 m
typically H07V-K 1.5 mm²
15: Data line
ELBus
®
COM
16: Addressing
Use of the terminals for applications not provided for in the operation manual
or improper connection can lead to malfunction or destruction of the device.
3.7.3 USB service and maintenance interface, terminal X3)
The USB interface serves for connection of the service computer. The available user
software
ControlPlex
®
Views provides the option to carry out firmware updates.
X2
18plus-TM03
connection
sleeve
16. Supply voltage
ELBus
®
+ 24 V
15. Data line
ELBus
®
15
16
fig. 8: ELBus
®
connection
130±0,8
42,5
13,5
7,5
Содержание ControlPlex CPC20
Страница 1: ...User Manual ControlPlex CPC20PN Controller...