SYSTEM RACK
4-7
4.2 FOUR SHELF 3000 SERIES SWITCH
The system rack is a framework for modules that
consists of up to 4-shelves with 13-slots per shelf. In
each shelf, 12-slots are for function modules and
1-slot is reserved for the power module. The power
supplies for the shelves are located in the lower
portion of the rack framework. The framework also
provides support for interconnection wiring, routed
between shelves, and external devices.
4.2.1 POWER CONSUMPTION
The following tables shows the average voltage,
current and power for each supply voltage per card
(based on loading of 48 cards).
Total watts including TIM-DID is 5.74W.
Excluding the TIM-DID provides a total of 4.3W for
normal modules. The total wattage of the terminal is
found by multiplying the wattage of a module by the
number of modules.
Total Watts x No. of Modules = Terminal Power
The wattage required by the power supply is
found by dividing the total wattage of the terminal by
the efficiency of the power supply (0.7).
Terminal Power
÷
0.7 = Wattage of Power Supply
The BTUs per hour are found by multiplying a known
value (3.6) by the wattage required by the power
supply.
3.6 x Wattage of Power Supply = Btu/Hr.
EXAMPLE:
4.3W x 48 = 206W
206W
÷
0.7 = 295W
3.6 x 295W = 1,061 Btu/Hr
4.2.2 EQUIPMENT REQUIRED
•
Digital Multimeter, voltmeter resolution to 0.001V.
•
Transmission test set, HP 3551A.
•
IBM NT compatible computer, with Call Processor
Software.
•
Two CIMs (023-3039-035).
4.2.3 4-SHELF POWER SUPPLY
The Power Supply has a 115/230V AC 50/60 Hz
input and 4 continuous duty outputs as follows:
+5V DC 24A.
-5V DC 6A.
+12V DC 3A.
-12V DC 5A.
The power supply can handle 2-shelves and has
the following connections:
4 se5V 2A connections.
2 separate -5V connections.
2 se12V connections.
2 separate -12V connections.
6 separate ground connections.
4.2.4 POWER SUPPLY REDUNDANT PLATE
The power supply drawer can be made redundant
by the use of the redundant diode plate (PN 023-3039-
553). The redundant plate allows two power supply
drawers to share the load via diodes. One of the power
supply drawers may be removed and the remaining
drawer will supply the full load (see Figure 4-10).
Table 4-6 AVERAGE VOLTAGE/CURRENT/
POWER
Voltage
Current
Power
+5V DC
0.50A
2.50W
+12V DC
0.10A
1.20W
-12V DC
0.05A
0.60W
-48V DC
0.03A*
1.44W
Total
5.74W
* DIDs only.
Содержание 3000 SERIES
Страница 2: ......
Страница 12: ...TABLE OF CONTENTS viii TABLE OF CONTENTS CONT D This page intentionally left blank ...
Страница 20: ...3000 SERIES SWITCH 2 6 This page intentionally left blank ...
Страница 26: ...ARCHITECTURE 3 6 This page intentionally left blank ...
Страница 58: ...CALL PROCESSOR 5 4 This page intentionally left blank ...
Страница 76: ...BASIC BOARD MODULE BBM 7 14 This page intentionally left blank ...
Страница 83: ...CHANNEL INTERFACE MODULE CIM 8 7 Figure 8 3 SUMMATION BOARD ALIGNMENT POINTS DIAGRAM ...
Страница 84: ...CHANNEL INTERFACE MODULE CIM 8 8 This page intentionally left blank ...
Страница 88: ...CONVENTIONAL CHANNEL MODULE CCM 9 12 This page intentionally left blank ...
Страница 92: ...DISPATCH CHANNEL MODULE DCM 10 4 This page intentionally left blank ...
Страница 100: ...DISPATCH INTERFACE MODULE DIM 11 8 This page intentionally left blank ...
Страница 142: ...TELEPHONE INTERFACE MODULE TIM 14 32 This page intentionally left blank ...
Страница 146: ...VOTER DIAGNOSTICS MODULE VDM 15 4 This page intentionally left blank ...
Страница 148: ...POWER TERMINATION MODULE PTM 16 2 Figure 16 1 POWER TERMINATION MODULE ALIGNMENT POINTS DIAGRAM ...
Страница 156: ...VOICE TONE MODULE VTM 18 4 This page intentionally left blank ...
Страница 164: ...WIDE AREA MODULE WAM 19 8 This page intentionally left blank ...
Страница 174: ...CONVENTIONAL PATCH MODULE CPM 21 4 This page intentionally left blank ...
Страница 178: ...POWER SUPPLY 22 4 Figure 22 6 POWER SUPPLY DRAWER ...
Страница 196: ...INTERCOM 24 2 This page intentionally left blank ...
Страница 200: ...ERROR MESSAGES A 4 This page intentionally left blank ...
Страница 214: ...Part Number 001 3139 005 10 03 Printed in U S A ...