background image

5

User Manual EE600 Differential Pressure Sensor

respect to safe installation and operation on the device. This operating manual contains information and 

warnings that must be observed by the user in order to ensure safe operation. 

 

ƒ

Mounting, start-up, operation and maintenance of the device may be performed by qualified staff 

only. Such staff must be authorised by the plant operator to carry out the mentioned activities. 

 

ƒ

The qualified staff must have read and understood this operating manual and must follow the 

instructions contained within. 

 

ƒ

All process and electrical connections shall be thoroughly checked by authorised staff before putting 

the device into operation. 

 

ƒ

Do not install or start-up a device supposed to be faulty. Make sure that such devices are not 

accidentally used by marking them clearly as faulty. 

 

ƒ

A faulty device may only be investigated and possibly repaired by qualified, trained and authorised 

staff. If the fault cannot be fixed, the device shall be removed from the process. 

 

ƒ

Service operations other than described in this operating manual may only be performed by the 

manufacturer. 

1.3  Environmental Aspects

Products from E+E Elektronik® are developed and manufactured observing of all relevant requirements 

with respect to environment protection. Please observe local regulations for the device disposal.
For disposal, the individual components of the device must be separated according to local recycling 

regulations. The electronics shall be disposed of correctly as electronics waste.

2  Scope of Supply 

 

ƒ

EE600 differential pressure sensor according to ordering guide

 

ƒ

Quick guide

 

ƒ

Test report according to DIN EN 10204-2.2

 

ƒ

Pressure connection set, including 2 m (6.6 ft) PVC hose with two ABS pressure connection nipples 

 

ƒ

Mounting material

 

ƒ

For digital version (ordering code J3): one additional M16x1.5 cable gland for daisy chain wiring 

Содержание EE600

Страница 1: ...BA_EE600 v1 6 Modification rights reserved User Manual EE600 Differential Pressure Sensor...

Страница 2: ...and found to comply with the limits for a Class A digital device pursuant to part 15 of the FCC Rules These limits are designed to provide reasonable protection against harmful interference when the...

Страница 3: ...5 1 5 Select the Output Signal with S8 10 5 1 6 Select the Source of Settings with S9 Auto zero Version Only 11 5 1 7 Outputs 11 5 2 Digital Version 11 5 2 1 RS485 Digital Interface Settings 11 5 2 2...

Страница 4: ...Avoid any unnecessary mechanical stress and inappropriate use Installation electrical connection maintenance and commissioning shall be performed by qualified personnel only Use the EE600 only as int...

Страница 5: ...y device may only be investigated and possibly repaired by qualified trained and authorised staff If the fault cannot be fixed the device shall be removed from the process Service operations other tha...

Страница 6: ...ressure connection nipples 2 DIP switches RS485 addressing 3 Terminals screw 4 Push buttons for zero point and span point adjustment 5 Status LED 6 Slide switch termination resistor 7 Service interfac...

Страница 7: ...al EE600 operates normally the measured data is within the selected measuring range One flash 2s Confirms adjustment or return to factory settings Off No power supply or electronics failure Fast flash...

Страница 8: ...the push buttons in order to prevent unintentional trigger of the span or zero point adjustment Close tightly the cable gland This is essential for the compliance with the IP65 NEMA 4X protection rati...

Страница 9: ...r to the chapters below 5 1 Analogue Version Each EE600 is delivered with the following factory settings all switches on 0 Measurement range 100 of the full scale 1 000 Pa or 10 000 Pa Response time 5...

Страница 10: ...600 HV53A7 S1 S2 Pa mbar inch WC kPa 0 0 10000 100 40 10 1 0 7500 75 30 7 5 0 1 5000 50 20 5 1 1 2500 25 10 2 5 Tab 1 DIP switch settings Measurement range 5 1 2 Select the Response Time with S3 and S...

Страница 11: ...re and the USB configuration adapter code HA011066 The device address can be overruled by setting the DIP switches see chapter 5 2 1 RS485 Digital Interface Settings Settings that can be changed with...

Страница 12: ...set via 1 PCS10 Product Configuration Software and the USB configuration adapter HA011066 2 Modbus protocol in the register 60001 0x00 and 60002 0x01 See Application Note Modbus AN0103 available on ww...

Страница 13: ...pressure kPa 1217 0x4C0 Differential pressure inch WC 1219 0x4C2 Air velocity m s 1041 0x410 Air velocity ft min 1043 0x412 Volume flow m3 h 1055 0x41E Volume flow l s 1057 0x420 Volume flow m3 s 105...

Страница 14: ...ode Byte count Register 1 value Hi Register 1 value Lo Register 2 value Hi Register 2 value Lo CRC Response Hex 2B 04 04 FB A5 43 F8 61 F3 For decoding of float values stored according standard IEEE75...

Страница 15: ...ed action Bit 0 Error Sensor not adjusted 1 Carry out zero point adjustment 2 Return to factory adjustment 2 Return the faulty unit to E E for service Bit 1 Error Pressure measurement faulty 1 Check t...

Страница 16: ...o lines without limit bar 5 4 PCS10 Product Configuration Software Only available with analogue version with auto zero and digital version For performing adjustment or changes in EE600 settings please...

Страница 17: ...in four different units m3 h m3 s ft3 min l s The default air density 20 value at standard conditions is defined as follows Air density 20 1 204 kg m3 T 20 C 68 F p 1 013 mbar 14 7 psi If the air den...

Страница 18: ...p soft cloth to remove deposits of dust or dirt from the exterior of the device and from the display Do not attempt to clean the interior of the device Do not use any solvents alcohol or abrasive clea...

Страница 19: ...seconds indicate that the span point adjustment did not succeed In this case repeat b f The span point adjustment b may not succeed because of a deviation higher than 5 of the original full scale of t...

Страница 20: ...2 s 4 s selectable with DIP switches Configurable in the range from 0 05 to 30 s with PCS10 Configurable in the range from 0 5 to 30 s with PCS10 Auto zero interval 24 h factory setting Configurable...

Страница 21: ...wer supply class III USA Canada Class 2 supply necessary max voltage 30 V DC 15 35 V DC or 24 V AC 20 Current consumption typ 0 Pa 0 psi 24 V DC Analogue output Digital interface Without display 23 mA...

Страница 22: ...pluse fr E E Elektronik Germany Obere Zeil 2 61440 Oberursel Tel 49 6171 69411 0 E mail info epluse de E E Elektronik India 801 Sakhi Vihar Road 400072 Mumbai Tel 91 990 440 5400 E mail info in epluse...

Отзывы: