User Manual EE600 Differential Pressure Sensor
3.3 Electrial Connection
Important note:
The manufacturer cannot be held responsible for personal injuries or damage to property as a result of
incorrect handling, installation, wiring, power supply and maintenance of the device.
Analogue version (A7)
Digital version (J3)
15 - 35 V DC
24 V AC ±20 %
V+
GND
V+
A (=D+)
RS485
B (=D-)
GND
AV
1
2
3
1
2
3
4
+
-
~
~
+
-
~
~
V / mA
15 - 35 V DC
24 V AC ±20 %
Fig. 3
Connection diagram
3.4 User Interface
3.4.1 LED Indication
Red LED
Flashing (1s
interval)
= The measured data is out of
the selected range (overload
or reversed pressure
connection)
One flash (2s)
= Indicates the failure of the
attempt to adjust zero point
or span point, or to return to
factory adjustment
Green LED
Flashing (1s
interval)
= EE600 operates normally, the
measured data is within the
selected measuring range
One flash (2s)
= Confirms adjustment or return
to factory settings
Off
= No power supply or
electronics failure
Fast flashing
(0.2 s interval)
= Auto-zero is executed, first
time 10 s after start / reset.
3.4.2 Display
The optional display shows the measured value(s) together with a bar graph or in two lines and has a
configurable backlight. It is also indicated when the measured value is out of range.
In the factory setting, the display shows the measured differential pressure in Pascal [Pa].See chapter
5.3 Display Settings for changing the display settings.
inch WC
40.15
919.0
Pa
7580
m³/h
Fig. 4
Display examples
In case of differential pressure out of the measuring range or negative pressure due to inverse pressure
connection the display indicates:
out of range
out of range
∆
p < scale value low,
-5 % of span
∆
p > scale value high,
+5 % of span
Fig. 5
Out of range indication