Info-3:   To  connect  the  outdoor  NTC  probe,  firstly  PP15  Outdoor  sensor  type  parameter’s  value  must  be 

changed  to  Outdoor  sensor  available  (1).  Outdoor  temperature  measurement  starts  only  if  PP15  is 
selected as 1. If PP15 is selected as 1 and outdoor NTC probe is not connected F6 error code is shown 
on the display but boiler keeps working. 

When the power supply is switched ON, OC, showed on LCD display, means that the probe is correctly 
connected and the function enabled  

Parameter 

No 

Parameter Name 
Parameter Value Definition 

Factory 

Setting 

Range 

PP15 

Outdoor Sensor Type 

0 - 1 

0: Outdoor sensor not available 
1: Outdoor sensor available 

 

5.

 

CONNECTION DIAGRAM 

 

1.  Room Thermostat ON-OFF

 

2.  Gas Valve Modulator 
3.  CH Flow NTC Probe 
4.  Water Pressure Sensor

  

5.  Over Temperature Protector 
6.  APS 
7.  DHW NTC Probe

 

8.  Flowmeter

 

9.  Outdoor NTC probe (Ops.) 
10. Pump 
11. Fan 

12. Gas Valve

 

13. Power Supply

 

14. 3 Way Valve

 

15. DHW Potentiometer 
16. CH Potentiometer

 

17. On/Off/Reset/Summer/Winter 

Potentiometer

 

18. Fuse

 

19. LCD

 

20. Error LED

 

21. Ignition and Ionization Electrode

 

Содержание GP11

Страница 1: ...GP 11 13 16 20 24 kW HM HERMETIC MONOTERMIC COMBI BOILER SERVICE MANUAL...

Страница 2: ...n System The appliance must be on stand by to activate the frost protection Water Flow Inspection Pump Dry Run Protection System 3 Way Valve Anti sticking Function Automatic Air Vent Expansion Vessel...

Страница 3: ...ter 7500 hours Service reminder time is cleared and 7500 hours counting is restarted if 20 is written to PP31 Parameter No Parameter Name Parameter Value Definition Factory Setting Range PP31 Paramete...

Страница 4: ...correctly connected and the function enabled Parameter No Parameter Name Parameter Value Definition Factory Setting Range PP15 Outdoor Sensor Type 0 0 1 0 Outdoor sensor not available 1 Outdoor sensor...

Страница 5: ...that mode frost protection is ready to activate When device gave a fault turn knob to OFF position and wait 3 second for fixing the fault and then turn previous mode When this knob turns to left devi...

Страница 6: ...t for 5 seconds Display will show the parameter value To change the parameter value move P3 to WINTER position Move P1 DHW knob to modify the value of selected parameter Move P3 to OFF position Wait f...

Страница 7: ...8 SERVICE PARAMETER LIST...

Страница 8: ...9 OPERATION PARAMETERS...

Страница 9: ...four times and then leave knob in WINTER position Fault history menu is entered with displaying L0 For example if the latest occurred error is F01 it is logged in L0 and seen as below To increase the...

Страница 10: ...not given during CH operation CH flow NTC probe error F3 If CH flow NTC probe is open or short circuit or it is damaged this error is given Both DHW and CH demand is stopped during this error Normal o...

Страница 11: ...is not DHW demand this fuction is activated If DHW heat demand is available on power on firstly DHW demand is supplied air purge is started after DHW is closed If the device is in OFF position on powe...

Страница 12: ...displayed on LCD Flame symbol is ON if the flame is available DHW INSTANTENOUS HEATING MODE The DHW Instantaneous function has higher priority than the central heating function DHW Instantaneous Heati...

Страница 13: ...TC probe firstly PP15 Outdoor sensor type parameter s value must be changed to Outdoor sensor available 1 Outdoor temperature measurement starts only if PP15 is selected as 1 If PP15 is selected as 1...

Страница 14: ...ting is restarted if 20 is written to PP31 ANTIFREEZE FUNCTION If the water temperature measured by the CH flow NTC probe is under the low limit for No frost ON temperature in table 1 the burner is tu...

Страница 15: ...m and maximum heating capacity becomes adjusted by the determination of operation pressure range 15 SERVICE MODE Power off the control board Adjust the knob positions to P1 maximum P2 minimum P3 OFF P...

Страница 16: ...r is completely tightened Setting the minimum outlet pressure The device is taken to minimum operation by removing one of the gas modulation cables Gas outlet pressure measurement port s screw is loos...

Страница 17: ...as control The minimum and maximum operating pressures can be adjusted mechanically via the gas valve The modulation valve is set with the maximum output pressure the maximum pressure regulator adjust...

Страница 18: ...ween 1 0 1 5 bars filling tap can be closed Disassemble of filling tap Firstly disassemble the flow manifold and turn the tap Assemble of filling tap Turn the tap until closing the filling tap Pump Pu...

Страница 19: ...r is needed the 3 way motorized valve directs the central heating water from the main exchanger to the plate heat exchanger The plate heat exchanger allows heat to be transferred to the domestic hot w...

Страница 20: ...erature increases or the sensor resistance increases as the temperature decreases NTC sensors are usually identified with nominal resistance values of 25 C However this value does not fully define the...

Страница 21: ...t the start of operation the differential air pressure switch is on In the first stage the fan starts to run when the pressure difference rises above the set value within a certain period of time the...

Страница 22: ......

Отзывы: