13

DANGER: 

When making electrical connections, make sure 

that there is no charge in the electrical line.

CONNECTIONS
Water Connection Instructions

Before the installation of your boiler, water circuit must be cleaned with suitable/approved chemi-

cals. To not damage the metal, plastic and rubber parts of the pipings and fittings, use neutral based, 

non-acidic and non-alcalic cleaners. When using these chemicals, please follow the instructions. Any 

dirt, blockages, welding residuals, burr, flug etc. particules left inside the pipes will affect the boiler’s 

performance. These residuals will cause boiler to overheat, noisy operating etc. Any damage or 

failure caused by unfit piping system is out of warranty coverage.

Condensate Water Connection

Electrical Connections

The condensate water formed during normal operation of E.C.A. 

F

eli

s

 boiler should be discharged 

according to the instructions. In gas burning condensing boilers condensate water is an acidid fluid 

with a pH value between 4-5. Burning 1 m3 natural gas forms approx. 1,7 liters of condensate water. 

There is a siphon mounted to the condensate water outlet to prevent the flue gas to leak into the 

surrounding air. Galvanised and copper alloy parts should not be used in the pipes and connection 

parts, all parts of condensate drain should be in plastic. If the drain hose would be connected to a 

drain out of the building, isolating the hose might be necessary to prevent the hose to freeze. For a 

good operation, all horizontal parts of the condensate drain should have a 2⁰-3⁰ downwards slope.

Supply cable of the appliance must be connected to a grounded plug that can supply the required 

voltage (230V AC, 50 Hz). Mainboard failures due to voltage fluctations and unfit grounding is not 

covered by warranty.

• Appliance must be connected to a grounded 230V AC, 50 Hz plug. If the supply cable is damaged,

it should be replaced by E.C.A. authorized services.
• A 2A double pole breaker with minimum 3mm contact clearance mut be used for electrical

connection of the boiler.

INFORMATION

INFORMATION

• Water used in the boiler circuit must have a pH value between 7,5 - 9,5.

If there are aluminum parts on the water circuit, pH value must be lower

than 8,5.
• Water used in the boiler circuit must have a hardness value between 5⁰f

- 15⁰f. If necessary, water in the circuit must be conditioned using

chemicals according to the water connections instructions above.

Содержание FELIS Series

Страница 1: ...FELIS WALL HUNG CONDENSING BOILER FELIS FL 50 65 100 125 150 HM INSTALLATION AND USER MANUAL...

Страница 2: ......

Страница 3: ...ProductFeatures 4 I Product Notation and Technical Dimensions 5 I Detailed Drawings and List of Components 6 I Technical Specification Table 9 I Packaging 11 11 17 I 17 I 19 I 19 I INSTALLATION and CO...

Страница 4: ...tilizing your boiler s complete features and to use your appliance safely for a long time please read the manual carefully Please keep all the documents that come with your appliance for future refere...

Страница 5: ...n using these chemicals please follow the instructions Any dirt blockages welding residuals burr flug etc particules left inside the pipes will affect the boiler s performance These residuals will cau...

Страница 6: ...id underneath the appliance First startup of the appliance must be done by the authorized service Natural gas usage must be approved by the related gas company prior to the first startup The gas type...

Страница 7: ...em that supports multiple languages with descrpitive menus White backlighted LCD screen shows information about working mode CH and DHW set points real time temperatures fault codes with descriptions...

Страница 8: ...nection Lid Siphon Connection Lid Dimensions A B C D E F G H I Felis FL 50 HM DG 501 mm 835 mm 525 mm 145 mm 304 mm 80 125 mm 1 1 4 1 1 4 3 4 Felis FL 65 HM DG 501 mm 835 mm 590 mm 145 mm 304 mm 80 12...

Страница 9: ...C TEMP SENSOR OUTLET 13 CONDENSATION HOSE 4 IGNITION TRANSFORMER 14 BOILER OUTLET PIPE HOT 5 HEAT EXCHANGER 15 BOILER INLET PIPE COLD 6 AIR PURGER 16 HEAT EXCHANGER HANGING BRACKET 7 FLUE GAS SENSOR 1...

Страница 10: ...7 Felis 65 Figure 2b Felis 65 Detailed Drawings...

Страница 11: ...8 Felis 100 125 150 Figure 2c Felis 100 125 150 Detailed Drawings...

Страница 12: ...6 4 84 3 87 8 87 1 87 5 Efficiency 30 Output at Low Temperature Regime 1 97 2 97 5 97 4 97 1 97 2 Electrical Consumption at Full Load elmax Watt 75 115 139 226 297 Electrical Consumption at Part Load...

Страница 13: ...Figure 3 Electronic Board Circuit Diagram 10 Electrical Board Circuit Diagram...

Страница 14: ...ure It must be connected to a heating circuit suitable for its capacity and nominal output Felis boilers are suitable with flue types C13 x C33 x C43 x C63 x and C93 x therefore its flue system is sep...

Страница 15: ...service maintenance and usage spaces required around the appliance is indicated in Figure 5 E C A Felis condensing boiler must be hung to a brick wall with the supplied hanging bracket For installatio...

Страница 16: ...e water outlet to prevent the flue gas to leak into the surrounding air Galvanised and copper alloy parts should not be used in the pipes and connection parts all parts of condensate drain should be i...

Страница 17: ...s gaskets should be mounted correctly to prevent flue gas leakage to the fresh air intake Horizontal flue kit must be installed with a 3 slope towards the appliance to keep the condansate water flowin...

Страница 18: ...d d l Figure 7 Flue Types 15 I I I I...

Страница 19: ...ostats can be used for heating control of the system Figure 8a Figure 8c E C A On Off Room Thermostat Wireless 7006907522 Wired 7006907519 Figure 8d Figure 8b E C A On Off Room Thermostat T6360 700690...

Страница 20: ...of the appliance and system with its wide LCD screen and multi language support while allowing full control on the appliance Figure 9 Felis Control Panel and Buttons By pressing Info button user can s...

Страница 21: ...n be manually reset from the reset button on the slave appliances For more information please refer to Cascading Applications section of this manual 18 Figure 11 User Interface for Slave Appliances Wi...

Страница 22: ...time program and parameters 501 506 decides the times of the day for the heating to switch on and off You can see the arranged time program as a line chart in the bottom of the LCD screen TIME PROGRAM...

Страница 23: ...ive Automatic summer winter changeover ECO functions and 24 hour heating limit inactive in the case of continuous operation with Comfort setpoint Continuous operation When using protection mode the he...

Страница 24: ...wer outside temperatures If you can t achieve desired room temperature heating curve slope must be adjusted Increasing the slope increases water temperature in lower outside temperatures Decreasing th...

Страница 25: ...rams After activating manual operation mode pressing Return button goes back to main screen When maintenance special operation symbol appears on the screen user can press Info button to change to the...

Страница 26: ...the Frost Protection setpoint applies Time program 4 DHW When using this setting a specific time program is available for DHW heating For every weekday a time program with a maximum of 3 on phases ca...

Страница 27: ...y 1642 When using this setting heating up to the Legionella setpoint takes place on the selected weekday independent of previous storage tank temperatures This setting is intended primarily for plant...

Страница 28: ...tive in Automatic operation In the other operating modes they are started and run in the background to become active whenever Automatic operation is selected When a holiday period has elapsed the cont...

Страница 29: ...consistencies occured during these controls will be shown as error and fault codes on the LCD screen and will be indicated with a bell sign on the upper left Some detailed information for the possible...

Страница 30: ...27...

Страница 31: ...28...

Страница 32: ...29...

Страница 33: ...30...

Страница 34: ...ing any chemical substances Usage of chemicals like detergents etc could cause rust and scratches ALL RIGHTS RESERVED Our company reserves the right to make changes on the products installation and us...

Страница 35: ...105 mm 235 mm 65 mm 240 mm 330 mm 435 mm 1 SIPHON 2 CH RETURN 1 3 4 CH FLOW 1 GAS 5 FLUE 80 125mm 1 2 3 4 2 1 3 4 145 mm 220 mm 5 5 FELIS 50 kW CIRCUIT AND FLUE CONNECTIONS 32...

Страница 36: ...105 mm 260 mm 65 mm 240 mm 435 mm 445 mm 1 SIPHON 2 CH RETURN 1 3 4 CH FLOW1 GAS 5 FLUE 80 125mm 1 2 3 4 2 1 3 4 145 mm 220 mm 5 5 33 FELIS 65 kW CIRCUIT AND FLUE CONNECTIONS...

Страница 37: ...98 mm 130 mm 185 mm 290 mm 71 mm 93 mm 280 mm 405 mm 145 mm 236 mm 1 2 3 4 5 5 1 2 4 3 1 SIPHON 2 CH RETURN 1 3 4 CH FLOW 1 GAS 1 5 FLUE 100 150mm 34 FELIS 100 kW CIRCUIT AND FLUE CONNECTIONS...

Страница 38: ...98 mm 130 mm 185 mm 365 mm 71 mm 93 mm 280 mm 405 mm 145 mm 236 mm 1 2 3 4 5 5 1 2 4 3 1 SIPHON 2 CH RETURN 1 3 4 CH FLOW 1 GAS 1 5 FLUE 100 150mm 35 FELIS 125 kW CIRCUIT AND FLUE CONNECTIONS...

Страница 39: ...98 mm 210 mm 437 mm 71 mm 93 mm 270 mm 405 mm 145 mm 236 mm 1 2 3 4 5 5 1 2 4 3 1 SIPHON 2 CH RETURN 1 3 4 CH FLOW 1 GAS 1 5 FLUE 100 150mm 36 FELIS 150 kW CIRCUIT AND FLUE CONNECTIONS...

Страница 40: ......

Страница 41: ...37 INFORMATION ABOUT REGULATIONS EU 811 2013 AND EU 813 2013 FEL S FL 50 65 100 125 150 HM Product Fiches and Package Label Calculations...

Страница 42: ...for installation assembly and maintanence are described in the installation and service manual Specific precautions for assembly installation and maintanence Rated heat output Prated Annual energy con...

Страница 43: ...this fiche may not correspond to its actual energy efficiency once installed in a building as this efficiency is influenced by further factors such as heat loss in the distribution system and the dim...

Страница 44: ...sup 1 2 II package without hot water storage tank II package with hot water storage tank 0 0 0 0 1 0 3 0 37 0 2 0 55 0 70 0 3 0 75 0 85 0 4 0 85 0 94 0 5 0 95 0 98 1 The intermediate values are calcul...

Страница 45: ...61000 4 4 61000 4 5 61000 4 6 61000 4 11 A a da imzas bulunan irketimiz yukar da ad tipi ve modeli belirlenen cihazlar ekte yer alan B 18 05 2708 EU numaral rapor dahilinde ilgili standartlara AT Gaz...

Страница 46: ......

Страница 47: ...Gas Fueled Boiler E C A Serial No Delivery Place and Date Maximum Repair Period 2 0 Work Days Warranty Period 3 Years AUTHORIZED SERVICE Installation Date Date Signature and Stamp Phone Fax FREE INITI...

Страница 48: ...Sanayi B lgesi 3 K s m Mustafa Kemal Bulvar No 13 45030 MANISA Mustafa Kemal Bulvar No 13 45030 MANISA TURKEY Tel 90 236 213 00 21 Tel 90 236 213 00 21 Fax 90 236 213 08 59 Fax 90 236 213 08 59 email...

Отзывы: