SD-BOX INSTRUCTION MANUAL, CODE: DYN 81.01.00 
Date: 03/03/2020 

Version 00 

 

- 17 -

 

5.3. 

ELECTRICAL DIAGRAMS 

1  OUTPUT. Normally open (NO) for fault indicator/coil status. This contact is closed if there is 

a fault or the coil is activated. 

2  OUTPUT. Normally closed (NC) for fault indicator/coil status. This contact is open if there is 

a fault or the coil is activated. 

3  OUTPUT. Common for fault indicator. 

4  OUTPUT. SAFETY LINE: Common safety contact to connect to safety line. 

5  No connection. 

6  OUTPUT. SAFETY LINE: Normally open contact to connect to safety line. 

7-19 No connection. 

20  INPUT. External reset. 0 V 

21  INPUT. External reset, 24 V. If there is voltage, the reset action is performed. 

22  INPUT. Level 1. 0 V 

23  INPUT. Level 1. 24 V.  

24  INPUT. Level 2. 0 V 

25  INPUT. Level 2. 24 V.  

26  INPUT. Remote manual rescue, 0 V. 

27  INPUT. Remote manual rescue, 24 V. If there is voltage for more than 3 seconds, the manual 

or bypass rescue action is performed. 

28-31 No connection. 

32  INPUT. 24 V

DC

 power supply. 

33  INPUT. 0 V power supply. 

34  INPUT. Bat 

35  INPUT. Batteries - 

36  No connection. 

37  No connection. 

38  OUTPUT. Inductive sensor, 0 V power supply. 

39  INPUT. Inductive sensor, Detection. 

40  OUTPUT. Inductive sensor, 24 V

DC

 power supply. 

41  No connection. 

42  OUTPUT. Coil, 24 V

DC

 

43  OUTPUT. Coil, 0 V

DC

 

44-48 No connection. 

49  INPUT. Doors, 0 V 

Note: This manual displays partial information on the instructions for use and maintenance of this product. Please refer to the customer 

area in Dynatech’s website in order to consult the full manual; http://customers.dynatech-elevation.com/

Содержание SD-BOX

Страница 1: ...OVEMENT CONTROL SYSTEM SYSTÈME DE CONTRÔLE DU MOUVEMENT INCONTRÔLÉ DE LA CABINE KONTROLLSYSTEM FÜR UNBEABSICHTIGTE FAHRKORBBEWEGUNGEN SD BOX INSTRUCCIONES DE USO Y MANUTENCIÓN INSTRUCTIONS FOR USE AND MAINTENANCE INSTRUCTIONS D USAGE ET ENTRETIEN GEBRAUCHS UND WARTUNGSANLEITUNG ...

Страница 2: ......

Страница 3: ...ON 13 5 3 ELECTRICAL DIAGRAMS 17 6 OPERATING REQUIREMENTS 20 6 1 FIRST START UP 20 6 2 SETTING THE COIL DE ENERGISATION WAIT TIME WITH THE CAR AT LEVEL 20 6 3 SETTING THE FAILURE OUTPUT RELAY 20 6 4 AUTOCHECK TEST FUNCTION 20 6 5 VERIFICATION TESTS 20 7 MAINTENANCE 26 7 1 GENERAL 26 7 2 CLEANING 26 7 3 STORAGE CONDITIONS AND USEFUL LIFE 26 7 4 INSPECTIONS 26 7 5 SPARE PARTS 26 8 OPTIONS 27 8 1 BAT...

Страница 4: ...rnor Facing the appearance of an UCM a competent technician is needed to make the installation operational again Once the problem causing the UCM is resolved the RESET button on the SD BOX is pressed to re establish the safety line and make the system operational again No intervention of the lift control is needed to make the overspeed governor coil act as the system described acts directly on it ...

Страница 5: ...ccording to the EN 81 20 standard table A 1 section 5 12 1 4 a Control of levelling re levelling and preliminary controls or section 5 12 1 8 2 Device for bridging the landing door and car contacts 3 2 EXCLUSION OF LIABILITY DYNATECH DYNAMICS TECHNOLOGY SL will not be held responsible for damages caused by not observing any of the points in this document Strictly prohibited Intervening on any comp...

Страница 6: ...n the Ni Cd type 2 1A protection fuse is required 3 If the SD BOX is placed in locations 2000 4000m above sea level the maximum voltage at the door input is limited to 160VAC DC 4 If the SD BOX is placed in locations 2000 4000m above sea level the maximum voltage at the motor input is limited to 160VAC DC Power supply INPUT 24 VDC 1 5A max SELV PELV Rechargeable battery power INPUT 12 VDC 1 5 Ah1 ...

Страница 7: ...established MAX 10 minutes The maximum duration of this mode when the SD BOX is powered by batteries is 10 minutes whereupon the SD BOX automatically returns to a resting state To warn of the automatic disconnection the beep frequency increases during the final minute Application of bypass during the process of disengaging the safety gear After an UCM or a manual lock MANUAL TRIPPING the bypass mu...

Страница 8: ...ged on if it is charging and flashing when checking the battery status BATTERY FAILURE Flasing indicates a battery fault damaged and impossible to charge or battery disconnection FAILURE CONFIG Indicates the FAILURE output relay setting Off indicates the SD BOX will act on the relay if it detects any fault or error and on indicates the SD BOX will act on the relay according to the coil status FAIL...

Страница 9: ...is happens and not during normal stops The basic operation is as follows The following input signals are needed from the lift Doors closed DOORS 2 independent unlocking zone sensors LEVEL1 and LEVEL2 Motor contactor MOTOR When the car reaches a floor the level inputs are activated and the coil remains energised keeping the overspeed governor unlocked The doors open the closed doors signal is lost ...

Страница 10: ...ED DOORS CLOSED ON SAFETY LINE OPENS COIL DE ENERGISES Check the coil connection7 Coil disconnection or failure during travel LED COIL OFF LED INDUCTOR OFF LED MOTOR ON LED DOORS CLOSED ON SAFETY LINE OPENS COIL DE ENERGISES Check the coil connection7 F4 Incorrect detection of coil when going to rest situation LED COIL OFF LED INDUCTOR ON LED MOTOR OFF LED DOORS CLOSED ON OFF SAFETY LINE OPENS COI...

Страница 11: ...r after pressing the MANUAL TRIPPING button LED COIL ON LED INDUCTOR OFF LED MOTOR OFF LED DOORS CLOSED ON LED MANUAL TRIPPING ON SAFETY LINE OPENS COIL ENERGISES Disengage the safety gear Push the RESET button and make a call If the failure persists act in the same way as for a F1 fault if the overspeed governor is not released or as fault F4 if the overspeed governor does not lock F8 The coil ca...

Страница 12: ...NERGISES Check the DOORS connections terminals 49 50 and voltages 24 230 VAC DC are acceptable If the problem persists contact Dynatech E3 Lift SEPIC operation error SAFETY LINE OPENS COIL DE ENERGISES Contact Dynatech E4 PWM control operation error SAFETY LINE OPENS COIL DE ENERGISES Contact Dynatech E5 SAFETY LINE output relay 1 operation error SAFETY LINE OPENS COIL DE ENERGISES Contact Dynatec...

Страница 13: ... ENERGISES Contact Dynatech L0 EEPROM read write error SAFETY LINE OPENS COIL DE ENERGISES Contact Dynatech Note This manual displays partial information on the instructions for use and maintenance of this product Please refer to the customer area in Dynatech s website in order to consult the full manual http customers dynatech elevation com ...

Страница 14: ...ust be verified that the box has not been damaged during transport The box dimensions are Length 157 mm Width 90 mm Height 71 mm 5 2 ELECTRICAL CONNECTION Before the electrical connection check there is no safety risk for the installer Before connecting the batteries check the voltage at the battery s terminals is 11 13 V Having an UCM control can affect the lift maintenance work During lift maint...

Страница 15: ... 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 NO CM SAFETY LINE SAFETY LINE EXTERNAL RESET LEVEL 1 LEVEL 2 EXTERNAL MANUAL RESCUE 0V 0V 0V 0V 24V 0V 24V POWER BATTERY IND SENSOR IN COIL 0V 0V 24 230 AC DC 24 230 AC DC DOORS DOORS MOTOR MOTOR POWER BATTERY Note This manual displays partial information on the instructions for use and maintenance of this product Please refer to the customer area i...

Страница 16: ...ation Two unlocking zone sensors must be used one for LEVEL1 and another for LEVEL2 Optional installation inputs In addition to the physical MANUAL RESCUE and RESET buttons the SD BOX can be used for the optional inputs discussed below for a manual rescue or remote reset from the control panel or another controller Remote manual rescue signal EXTERNAL MANUAL RESCUE terminals 26 27 to implement a m...

Страница 17: ... this is powered the normally open NO 1 3 FAILURE relay contact will be closed and the normally closed contact NC 2 3 will open Overspeed governor connection components The action of the coil releases the overspeed governor and allows its free rotation If the coil is not powered a spring activated system locks the overspeed governor If there is no power reaching the coil with the car in motion the...

Страница 18: ...ormed 22 INPUT Level 1 0 V 23 INPUT Level 1 24 V 24 INPUT Level 2 0 V 25 INPUT Level 2 24 V 26 INPUT Remote manual rescue 0 V 27 INPUT Remote manual rescue 24 V If there is voltage for more than 3 seconds the manual or bypass rescue action is performed 28 31 No connection 32 INPUT 24 VDC power supply 33 INPUT 0 V power supply 34 INPUT Batteries 35 INPUT Batteries 36 No connection 37 No connection ...

Страница 19: ...1 No connection 52 No connection 53 INPUT Motor 0 V 54 INPUT Motor 24 230 VDC or 24 230 VAC If there is voltage the motor is running Note This manual displays partial information on the instructions for use and maintenance of this product Please refer to the customer area in Dynatech s website in order to consult the full manual http customers dynatech elevation com ...

Страница 20: ...ections Figure 2 Internal relays electrical connection Note This manual displays partial information on the instructions for use and maintenance of this product Please refer to the customer area in Dynatech s website in order to consult the full manual http customers dynatech elevation com ...

Страница 21: ... open depending on the coil status whether energised or at rest 6 4 AUTOCHECK TEST FUNCTION This test the proper operation of the SD BOX such as the LEDs relays and coil control 6 5 VERIFICATION TESTS Before commissioning and also periodically the following verification test procedure must be performed Test 1 Arrival at floor level and opening the doors Press the RESET button Make a call Wait for ...

Страница 22: ... X DOORS X MOTOR X LEVEL1 X LEVEL2 X INDUCTOR μSWITCH X COIL STATUS X Note This manual displays partial information on the instructions for use and maintenance of this product Please refer to the customer area in Dynatech s website in order to consult the full manual http customers dynatech elevation com ...

Страница 23: ...ng the travel X LEVEL2 Flashes when passing through each level during the travel X INDUCTOR μSWITCH X COIL STATUS X Test 3 Checking the battery charge This test should be carried out only if batteries are used as an auxiliary power source Press the RESET button Check the battery is properly connected to the corresponding terminals Check that the BATTERY CHARGING LED is on or off if it is fully cha...

Страница 24: ...s charging X if the battery is charged BATTERY FAILURE X if the battery is discharged or not connected X if the battery is charged and connected FAILURE CONFIGURATION X if configured to show system fault at output X if configured to show coil status at output MANUAL RESCUE BYPASS X MANUAL TRIPPING X UCM DETECTED X DOORS X MOTOR X LEVEL1 X LEVEL2 X INDUCTOR μSWITCH X COIL STATUS X Press the MANUAL ...

Страница 25: ...arged and connected FAILURE CONFIGURATION X if configured to show system fault at output X if configured to show coil status at output MANUAL RESCUE BYPASS X MANUAL TRIPPING X UCM DETECTED X DOORS X while waiting the doors can either be open or closed X while waiting the doors can either be open or closed MOTOR X LEVEL1 X LEVEL2 X INDUCTOR μSWITCH X COIL STATUS X Make a call Check the overspeed go...

Страница 26: ...ttery is discharged or not connected X if the battery is charged and connected FAILURE CONFIGURATION X if configured to show system fault at output X if configured to show coil status at output MANUAL RESCUE BYPASS X MANUAL TRIPPING X UCM DETECTED X Flashing DOORS X MOTOR X LEVEL1 X LEVEL2 X INDUCTOR μSWITCH X COIL STATUS X Reconnect floor level signals Press the RESET button Check the overspeed g...

Страница 27: ...ife of the component is considered to be at least 20 years and must be replaced when this time has been reached The SD BOX should not be used outside the previously established ranges or its useful life could be affected In addition exposure to environmental conditions other than those marked during operation has not been considered 7 4 INSPECTIONS Installation and commissioning Revision every 3 m...

Страница 28: ...e indicator will stay ON when performing a fast charge and will turn OFF when the battery is fully charged The SD BOX will perform a periodic test to check the status of the batteries if it detects they are damaged whereupon the BATTERY FAILURE LED will light up Important note Rechargeable batteries are required for proper operation but are not included in the SD BOX Important note The disposal of...

Отзывы: