3101B MANUAL

02/08

MODEL 3101B

DELAY EGRESS SYSTEM

INSTALLATION  INSTRUCTIONS

705 Emmett Street    Bristol, CT 06010

 1-877-DynaLock    www.dynalock.com

INDICATOR & AUDIBLE DESCRIPTIONS

LED2 - WATCHDOG LED INDICATOR

(Located upper right corner of circuit board.)

Troubleshooting indicator - monitors proper 

operation of the microprocessor. 

LED1 - BI-COLOR LED INDICATOR

(Located at center of circuit board.) 

Indicates lock status and monitors 

door movement during egress sensor 

adjustment.

BUILT-IN KEYSWITCH OPERATION

CENTER

CLOCKWISE (SPRING LOADED)

COUNTER-CLOCKWISE

NORMAL / LOCKED

RESET AFTER DELAY EGRESS ALARM

BYPASS / UNLOCKED WITHOUT ALARM

POSITION

DESCRIPTION

CONDITION

AUDIBLE SIGNAL

LOCK 

LED 1

LED 2

DELAY EGRESS ALARM

One second pulse rate during 

delay cycle.

ON

BLINK RED

RED

DELAY EGRESS ALARM

Steady tone after delay until 

reset.

OFF

GREEN

RED

FIRE ALARM

RELEASE

Steady tone until fire alarm 

contacts are reset.

OFF

GREEN

RED

OPTIONAL REMOTE

AUTHORIZED BYPASS

(TERMINALS 7&8 / 9&10)

None, unless bypass audible 

is enabled (dip switch 2).  If 

door is held open past relock 

time, goes into delay egress 

alarm & requires reset.

OFF

GREEN

RED

FACTORY SERVICE

REQUIRED

Steady tone.

N/A

N/A

BLINK RED 

OR OFF

POOR MAGNETIC BOND Rapid pulse rate until problem 

is corrected (only functional 

with Dynastat Force Sensor 

option).

N/A

FAST BLINK RED RED

Содержание 3101B

Страница 1: ... other wiring is for selected options NOTE Please see Egress Sensor Adjustment page 8 before applying power Familiarize yourself with the door and frame conditions The lock must mount rigidly to the underside of the door frame header and against the vertical strike jamb The door mounted armature is supplied with hardware that allows it to pivot slightly and pull away from the door as part of the d...

Страница 2: ...ture Spacer 3 8 D x 0 360 L 1 Armature Spring Compression spring 4 Armature Mounting Plate Screws 10 x 1 phillips flat head sheet metal screw 4 Armature Housing Mounting Screws 8 32 x 3 8 phillips machine screw 1 Anti Tamper Cover Screwdriver 6 spanner key 1 Fas Trak Set Screw Wrench 1 8 ball head hex wrench 1 Armature Bolt Wrench 3 16 hex wrench 1 Thread Locking Compound Liquid 2 Bypass Reset Key...

Страница 3: ... tape in place Transfer all hole locations to both the door and header with a center punch then remove the template from the door Referring to the template drill two 1 8 dia lock mounting holes and one 9 16 dia wiring hole in the top of the frame at the transferred locations 1 2 3 4 Drill the remaining transferred holes in the face of the door to accept the Armature Mounting Plate Assembly a Four ...

Страница 4: ...x wrench The head of the armature mounting screw must not project beyond the face of the armature Failure to properly secure the Armature to the door could result in serious injury or possible security breach Check the installation by pushing in on a corner of the Armature it should move Although the mounting screw is tight the Armature should have approximately 1 4 of free play under slight sprin...

Страница 5: ...wn engaging the rear flange of the Fas Trak Fig B Rotate the lock up allowing one tab to pass through the corresponding notch in the top of the lock housing Slide the lock into position Close and latch the door Check that the armature and lock faces make full contact If any adjustment is required gently tap the housing with a soft mallet until full contact is achieved Open the door remove the lock...

Страница 6: ... panel tie in is not required leave jumper at factory setting N O Remove the Electronics Cover to expose the circuit board assembly Factory Setting Factory Setting 1 2 3 System Selector Switches The selector switches DS1 that control major system functions are factory set to the OFF position for basic lock operation Switch 1 will be used during sensor adjustment page 8 Switches 2 3 and 4 are only ...

Страница 7: ...7 8 or 9 10 SEE PAGE 11 Terminals 3 4 Fire Panel Input May be normally open N O or normally closed N C dry contacts from fire panel check fire alarm control jumper FA page 6 When the fire panel trips the 3101B will release the audible will sound a constant tone and the bi color LED LED1 will change to green When the fire panel is reset the 3101B will reset and lock NOTE DO NOT APPLY POWER TO TERMI...

Страница 8: ...ation later With the door closed observe the bi color LED LED1 on the circuit board It should be lit red If it is not lit rotate the adjustment wheel counter clockwise as necessary to ensure that it will contact and fully depress the ball plunger on the lock Rattle the door to ensure the LED remains lit With the door closed and LED1 lit red unlatch and slowly open the door The LED will shut off as...

Страница 9: ...L LOCKED RESET AFTER DELAY EGRESS ALARM BYPASS UNLOCKED WITHOUT ALARM POSITION DESCRIPTION CONDITION AUDIBLE SIGNAL LOCK LED 1 LED 2 DELAY EGRESS ALARM One second pulse rate during delay cycle ON BLINK RED RED DELAY EGRESS ALARM Steady tone after delay until reset OFF GREEN RED FIRE ALARM RELEASE Steady tone until fire alarm contacts are reset OFF GREEN RED OPTIONAL REMOTE AUTHORIZED BYPASS TERMIN...

Страница 10: ...our specific system requirements The normal factory setting is all switches off 1 Sensor Control The egress sensor may be disabled if you wish to trigger the lock via external remote contacts on input terminals 11 12 Position jumper J10 to disable the egress sensor as shown 3 Factory Setting C S A C A S 1 SYSTEM SET UP NORMAL SET UP MODE 2 BYPASS AUDIBLE DISABLED ENABLED 3 NUISANCE DELAY 1 SEC 3 S...

Страница 11: ...stitute means of triggering delayed egress if built in sensor initiation is not desired see page 10 note 3 INPUT DESCRIPTIONS WARNING DO NOT APPLY POWER TO INPUTS MARKED OR DAMAGE WILL OCCUR A C B D REMOTE BYPASS INPUT TIME DELAY Momentarily closing a normally open dry contact across terminals 9 10 will immediately release the lock without alarm The door will remain unlocked for a period of time c...

Страница 12: ...can also create an unsecure condition DSM OPTION OUTPUT Door position sensor monitoring SPDT dry relay contacts rated 0 5Amp 24 Volts Contacts change state to signal physical door position as either closed or open DSM is an independent circuit that does not require lock power to operate ATS OPTION OUTPUT Anti Tamper Switch monitoring SPDT dry relay contacts rated 0 5Amp 24 Volts Contacts change st...

Страница 13: ... SENSOR LOCK COIL ASSEMBLY 3101B CIRCUIT BOARD Harness connectors J3 and J6 are not polarity sensitive J3 J4 are interchangeable jumpers can go on J3 and coil can go on J4 Harnesses J6 and J8 are only present if the 3101B is equipped with the DYN Dynastat Force Sensor and or DSM Door Status Switch Options Observe polarity when re connecting the J5 J7 and J8 harness connectors Orient these connecto...

Страница 14: ... 3101B DELAY EGRESS SYSTEM INSTALLATION INSTRUCTIONS 705 Emmett Street Bristol CT 06010 1 877 DynaLock www dynalock com EXPLODED PARTS VIEW LEGEND ON NEXT PAGE 1 2 3 4 5 6 11 12 13 1 1 2 1 4 1 1 2 1 2 7 8 9 10 14 15 17 16 18 19 20 21 ...

Страница 15: ...8 6 1 4 28x1 4 Set Screw 300604 7 Electronics Cover 300353 8 6 32x1 2 Spanner Security Screw 700058 9 End Cover 300010 Part of Hardware Kit 301325 Refer to Page 14 for parts locations ITEM DESCRIPTION PART 10 Armature Mounting Plate Assy 301038 11 Sensor Adjustment Wheel Stud 301383 12 Wheel Stop 301003 13 8 32x1 2 Wheel Stop Screw 301005 14 10x1 FHS Mtg Plate Screw 15 Armature Housing w pads 3013...

Страница 16: ... PRODUCT SUPPORT AND PARTS ORDERING INFORMATION CONTACT DynaLock Corp 705 Emmett Street Bristol CT 06010 Bus 877 396 2562 Toll Free USA 860 582 4761 Fax 860 585 0338 DYNALOCK ON THE INTERNET E mail info dynalock com Website www dynalock com GWXT Auxiliary Lock FWAX Special Locking Arrangements CSFM California State Fire Marshal ...

Отзывы: