3101B MANUAL
02/08
MODEL 3101B
DELAY EGRESS SYSTEM
INSTALLATION INSTRUCTIONS
705 Emmett Street Bristol, CT 06010
1-877-DynaLock www.dynalock.com
BASIC WIRING
Terminals 1& 2 - Power Input. May be 12 or 24 Volts, AC or DC,
uninterrupted. Current requirement is 0.75 Amps for 12 Volts and 0.5 Amps
for 24 Volts (check voltage selection jumpers “V” - page 6).
DO NOT INTERRUPT INPUT POWER (TERMINALS 1 & 2) FOR
AUTHORIZED ACCESS/EGRESS. EXTERNAL ACCESS/EGRESS
CONTROLS (EX. KEYPAD, CARD READER, ETC.) SHOULD USE
DEDICATED BYPASS TERMINALS 7 & 8 or 9 & 10 (SEE PAGE 11).
Terminals 3 & 4 - Fire Panel Input. May be normally-open (N.O.) or
normally-closed (N.C.) dry contacts from fire panel (check fire alarm control
jumper “FA” - page 6).
When the fire panel trips, the 3101B will release, the audible will sound a
constant tone and the bi-color LED (LED1) will change to green. When the
fire panel is reset, the 3101B will reset and lock.
NOTE: DO NOT APPLY POWER TO TERMINALS 3 & 4 OR DAMAGE
WILL OCCUR.
Basic hook-up is shown below. For other system features hook-up see “Option Wiring” (page 11).
PROPER OPERATION OF THE 3101B REQUIRES
ADJUSTMENT OF THE EGRESS SENSOR
PROCEED TO EGRESS SENSOR ADJUSTMENT