mounting 

4

   

DBC410 Installation Manual Rev K.docx

 

 

 
Select a Suitable Location

 

This device is designed for indoor use only.  If 
installing in an external location, the DBC410 
must  be  housed  in  a  suitable  well-ventilated 
enclosure.  Choose a dry location, that will be 
accessible  after  the  installation  is  complete.  
The  DBC410  should  be  mounted 

vertically, 

the  right  way  up

.    The  DBC410  requires  an 

air gap of 100mm on each side and at the top 
and  bottom  of  the  device.    This  air  gap  is 
required  to  ensure  serviceability  of  the 
DBC410  without  complete  removal  from  the 
mounting  surface.    This  device  may  emit 
some  mechanical  noise.    Take  this  into 
account when deciding the mounting location. 
 

 
 
Fixing the Device 

The DBC410 has four mounting brackets that 
attach  to  the  rear  of  the  enclosure.    The 
brackets  are  designed  to  accommodate  4 
fixing  screws  up  to  8mm  diameter.    The 
DBC410  can  be  fixed  to  the  wall  without 
opening  the  cabinet  or  removing  covers.  
Make sure no dust or other debris enters the 
device  during  installation.    Do  not  leave  the 
front  cover  off  for  any  length  of  time.  
Excessive  dust  and  dirt  can  degrade  the 
cooling of internal components. 

 

 
 
Allow for Cable Entry 

Supply, load and load control cables enter the 
enclosure at the top.  If these cables are fed 
from  below  the  mounting  position,  they 
should  be  routed  around  the  enclosure  to 
enter at the top.  An alternative method is to 
stand  the  enclosure  off  from  the  mounting 
surface  by  mounting  it  on  a  cable  tray  or  a 
Unistrut  style  product.    The  cables  can  then 
be  routed  between  the  enclosure  and  the 
mounting surface, and enter the enclosure via 
the  cutout  provided  on  the  mounting  face.  
The control cables enter at the bottom of the 
enclosure.    Control  cables  should  never  be 
run  in  the  mains  voltage  sections  of  the 
enclosure. 

Содержание DBC410

Страница 1: ...er Installation Manual contents Warning 2 Hardware Controls 7 Features 2 Troubleshooting 8 Important Safeguards 2 Specification 8 Internal View 3 Mounting 4 Supply Load Cable Connections 5 Connecting Serial Control Cables 6 Supplied by ...

Страница 2: ...eck Connections Treat this device as a switchboard that has been shipped Tighten all load carrying screw connections as vibrations from transport can cause MCB and terminal block screws to become loose Power Sources This device should only be operated from the type of supply specified on the front panel This device must be earthed Output Circuits The load on a circuit should not exceed the specifi...

Страница 3: ...pply Connections Knock Out For Low Voltage Cable Entry Glands for Load Cables 225mm 320mm DyNet Network Connections Control CPU Relays Mounting Point Network Socket Service Switch EARTH LINK Depth 75mm Transformer SHEILD GND D D 12V AUX 0V CH 1 CH 2 CH 3 CH 4 N1 N2 N3 N4 LINE 4 LINE 3 LINE 2 LINE 1 For spare parts please call your nearest Dynalite Customer Service Centre and specify DBC410 ...

Страница 4: ...kets are designed to accommodate 4 fixing screws up to 8mm diameter The DBC410 can be fixed to the wall without opening the cabinet or removing covers Make sure no dust or other debris enters the device during installation Do not leave the front cover off for any length of time Excessive dust and dirt can degrade the cooling of internal components Allow for Cable Entry Supply load and load control...

Страница 5: ...rol Cables Load control cables can be terminated on the 2 x 4 way terminal strips located directly above the Load terminals The left terminal block is the output for 0 to 10V or DSI if selected by software setup Note that most types of 1 10V HF Fluorescent Ballast control wiring is polarity conscious The terminal of the ballast connects to the left terminal block and the terminal connects to the r...

Страница 6: ... pair paralleled for VE and one pair used for DATA and DATA Recommended Cable Colour Coding Green White pair paralleled for GND Orange White pair paralleled for VE Blue White pair Blue for DATA White for DATA Brown White pair Spare or for Join The colour coding scheme used is not critical as long as the same scheme is used throughout the installation Serial Cable Connecting Method The recommended ...

Страница 7: ...ervice Switch has three functions 1 push Transmit Network ID 3 pushes All Channels 100 Push hold for 4 sec Reboot Top Set This adjusts the maximum output that all other control sources can select ie if the Top Set is fully clockwise 100 selected by a control source will give 100 output If it is fully anti clockwise 100 selected by a control source will give 50 output This control is useful for ext...

Страница 8: ...ol cable from DBC410 to ballasts not installed Check ballast type Check actual wiring against ballast manufacturer s diagram Check 1 10V DSI cable and settings specification Supply 230V 14 50 60Hz Single Phase at 40A Outputs 4 x switched outputs at 10A 4 x signal control outputs selectable to 1 10VDC and DSI Optional Maintained Output 1 x Maintained NC output for testing battery packs in fixtures ...

Отзывы: