LED INDICATIONS
FRONT PANEL LED INDICATIONS
LED Appearance
Condition/Failure
Not in Auto LED is ON.
Unit is in OFF state.
No LED’s ON
“OFF”, no +12/24VDC to “Auto” terminal.
Steady Low Oil LED
Low Oil Pressure Failure
Flashing Low Oil LED
Auxiliary Input Failure
Steady High Temperature LED
Over Temperature Failure
Steady Overcrank LED
Engine would not start after specified
Crank tries.
Steady Overspeed LED
Speed Signal present above Overspeed
setting
Flashing Overspeed LED
Was Engine Cranking?
Was Engine Running?
No speed signal available while Cranking
The speed signal was Zero while running.
The engine has stalled, or the speed signal
has been lost.
Steady Engine Running LED
Engine Controller is in running mode of
operation.
Flashing Engine Running LED
Crank Rest period. Cranking will resume
soon.