background image

Page 5

60707-122

9160-00

Although individual units and models may vary slightly, the
normal voltage and frequency of the engine-generators
described in this book are approximately as follows, under
varying loads:

LOAD vs. OUTPUT

__________________________________________________________________________________________________________________

Generator       Frequency

Voltage

Load

           Speed

120V

Applied*

(RPM)

(Hz)

Recpt.

__________________________________________________________________________________________________________________

None

3750

62.5

126V

Half

3600

60.0

122V

Full

3540

59.0

119V

__________________________________________________________________________________________________________________

*Portion of plant’s rated output current.

The speed of the engine was carefully adjusted at the factory
so that the generator produces the proper voltage and
frequency.  For normal usage, the speed setting should not
be changed.  If the generator is being run continuously on a
very light load, it is often advisable to lower the operating
speed slightly.  Whenever making any speed adjustments
check the unit with a voltmeter or tachometer and be sure the
speed is correct.

Lower voltage may damage both the generator and any load
connected to it.  Running the engine at excessively high
speeds results in high voltage, which may significantly
shorten the life of appliances being used.

Output voltage should be checked periodically to ensure
continued proper operation of the generating plant and
appliances.  If the generator is not equipped with a voltmeter,
it can be checked with a portable meter.  Frequency can be
checked by using an electric clock with a sweep second
hand.  Timed against a  wrist watch or a stop watch the clock
should be correct /- 2 seconds per minute.

OPERATING YOUR GENERATOR

The engine-generators covered in this manual were designed
for portable use. DO NOT INSTALL OR OPERATE THIS
GENERATOR INDOORS. 
 The unit should be stored in a
warm dry location. During a power outage, move the unit
outdoors to a flat dry location such as a driveway or sidewalk.

Allow the engine to warm up for two or three minutes before
applying any load.  This will allow the engine to reach normal
operating temperature and oil to circulate throughout the
engine.  A short warm-up time will permit the engine to work
more efficiently when the load is applied and will reduce the
wear in the engine, extending its life.

Receptacles have been provided to allow loads to be
connected to the generator.  The loads should be added one
at a time.  If a large motor is being started or multiple motors
are being started, they should be started individually and the
largest should be started first

Most electric tools and appliances will have the voltage and
amperage requirements on their individual nameplates.
When in doubt consult the manufacturer or a local electrician.
The nameplate amperage rating for electric motors can be
misleading. See “Starting Electric Motors” in Unit Capabilities
(page 2).

These engine generator sets are inherently self regulating
based on engine speed.  The engine governor will
automatically adjust itself to the load.  No harm to the
generator will result if it is operated with no load connected.

Proper utilization of the receptacles located on the control
panel is necessary to prevent damage to either the
receptacles or the generator.  The generator is a limited
source of electrical power, therefore pay special attention
to the receptacle and generator ratings. The nameplate
rating can be obtained through a single receptacle as long
as the receptacle amperage rating is not exceeded.

HARD WIRING YOUR GENERATOR

Temporary Power

‘Hard Wiring’ this unit directly into a temporary construction
site electrical system is NOT A SIMPLE DO-IT-YOURSELF
JOB.  For your safety all wiring must be done by a qualified
electrician and conform to the National Electric Code and
comply with all state and local codes and regulations.
Check with local authorities before proceeding.

WARNING:  PERSONAL DANGER

A fully isolated, double pole double throw manual
transfer switch must be installed any time a generator is
being connected to an existing distribution system.

To connect these units directly to an un-powered, isolated
construction site TemPower panel, have your electrician
connect to the control panel using a 120/240 volt, four wire
twistlock plug (L14-30P).  The use of locking receptacles
and locking plugs provides the convenience of quick
disconnect, for moving, while allowing non electrical workers
to safely reconnect the power.  In addition they prevent the
plug from being accidentally removed by bumping or
vibration.

Home Standby

If the generator set is connected to existing (electrical)
wiring circuits it is permitted only through a fully isolated
manual transfer switch.  The transfer switch prevents
damage to the generator and other circuit components if
main line power is restored while the generator is
connected.  Installing a transfer switch also permits the use
of normal fusing.

Many homes and construction sites are wired for at least 60
to 100 Amp entrance service, much greater than the
capacity of these portable generators.  When installing the
generator at these sites, a secondary emergency distribution
panel may have to be installed, such as the Emergency
Transfer/Service (ET/S) system available through your
Winco dealer. The emergency distribution panel must be
installed by a licensed electrician according to all applicable
codes.  The electrician will move the critical circuits to be
powered during the outage to the emergency panel.  Keep
in mind only a limited amount of amperage is available from
the generator set.  Some circuit breakers may still have to
be turned off to prevent an overload on the generator during
the initial start up. See the nameplate on your generator for
the amperage capabilities of your unit.

CAUTION:  EQUIPMENT DAMAGE

Failure to properly limit and balance the load applied to
the generator will cause the generator to produce low
voltage and may damage the engine generator set.  It
may also cause severe damage to the loads connected
to the generator at that time.  Improper loading of the
generator set constitutes abuse and will not be covered
by warranty.

Содержание CSADL6000I/E

Страница 1: ...INSTALLATION OPERATION and MAINTENANCE INSTRUCTIONS CSADL6000I E CSADL6000IE E ...

Страница 2: ...CTIONS Initial Starting 4 Starting 4 Starting Hints 4 Stopping And Storage 4 Operating Speed 5 Connecting The Loads 5 OPERATOR CARE AND MAINTENANCE Engine Care 6 Generator Care 6 Cleaning 6 Troubleshooting Things To Check BEFORE You Call For Service 7 Complete Unit Parts List 8 Receptacle Panel Parts List 9 Wiring Diagram 10 WARRANTY 10 Read and understand all instructions in the manual before sta...

Страница 3: ...RE HAZARD Gasoline and other fuels always present a hazard of possible explosion and or fire a Do not refuel when the engine is running or hot Allow the engine to cool at least two minutes before refueling b Keep fuel containers out of reach of children c Do not smoke or use open flame near the generator set or fuel tank d Keep a fire extinguisher nearby and know its proper use Fire extinguishers ...

Страница 4: ... The generator winding might also be damaged CAUTION EQUIPMENT DAMAGE RUNNING THE GENERATOR SET UNDER THESE CONDITIONS MAY RESULT IN DAMAGING THE GENERATOR STATOR AS WELL AS THE MOTOR WINDING Because the heavy surge of current required for starting motors is required for only an instant the generator will not be damaged if it can bring the motor up to speed in a few seconds of time If difficulty i...

Страница 5: ... is especially true if an unexpected shutdown would cause a safety hazard or serious inconvenience for the operator UNPACKING CAUTION EQUIPMENT DAMAGE THIS UNIT HAS BEEN SHIPPED WITHOUT OIL Failure to maintain the engine oil at the proper level will result in serious engine damage When you unpack your new ENGINE GENERATOR be sure to remove all the information sheets and manuals from the carton 1 T...

Страница 6: ... run position CAUTION EQUIPMENT DAMAGE Never permit the choke to remain on after the engine has run for a short time It is not necessary to choke the engine when it is warm Avoid over choking STARTING HINTS 1 Cold weather a Use the proper oil for the temperature expected b Use fresh winter grade fuel Winter grade gasoline is blended to improve starting Do not use summer gasoline 2 Hot weather a Us...

Страница 7: ...r sets are inherently self regulating based on engine speed The engine governor will automatically adjust itself to the load No harm to the generator will result if it is operated with no load connected Proper utilization of the receptacles located on the control panel is necessary to prevent damage to either the receptacles or the generator The generator is a limited source of electrical power th...

Страница 8: ...sembly from base b Remove foam pre cleaner by sliding it off the paper cartridge c Wash foam pre cleaner in liquid detergent and water d Wrap foam pre cleaner in cloth and squeeze dry e Saturate foam pre cleaner in engine oil Squeeze to remove excess oil f Install foam pre cleaner over paper cartridge Reassemble cover and screw down tight Replace the cartridge included with Dual Element Air Cleane...

Страница 9: ...itor Defective stator Defective rotor field Circuit Breaker Over Loaded Trips Defective receptacle Defective circuit breaker Too small long of drop cord Voltage too high Engine speed is too high Generator Overloaded overheating Insufficient ventilation No output voltage Short in load disconnect Broken or loose wire Defective receptacle No residual magnetism in generator Defective stator Defective ...

Страница 10: ...nts 4 16249 000 4 Locknut 5 16 18 5 16250 000 1 Flange Nut 3 8 16 6 464 000 1 Cap Screw 3 8 16 X 75 7 16335 007 1 Generator Support 8 15676 005 1 Battery Tray 1 NI 15767 005 1 Negative Battery Cable 1 NI 15767 016 1 Positive Battery Cable 1 NI 15807 000 1 Battery Holddown Kit 1 9 15617 003 1 End Cover Assembly 10 63073 031 1 Cradle Assembly 11 58684 011 1 Edge Trim ...

Страница 11: ...6 006 1 Complete Generator Assembly 14 15632 007 1 Engine B S Intek 1 210317 0191 B1 14 15632 008 1 Engine B S Intek 2 210312 0190 B1 15 468 000 2 Cap Screw 5 16 18 X 1 5 16 480 000 2 Lockwarsher 5 16 17 466 000 2 Cap Screw 1 4 20 X 75 18 512 000 2 1 4 Flat Washer 19 16133 000 2 Leather Washer 20 81018 008 1 Clamp 21 98771 000 1 Fuel Valve 22 62999 001 2 Fuel Line Clamp 23 40078 000 28 1 4 Fuel Li...

Страница 12: ...rior to placing the unit in service The user shall assume all risks and liability in connection with determining the suitability of the unit for its particular use Neither the manufacturer nor the seller shall be liable for any injury loss or damage arising out of improper use or operation of this unit In no event is WINCO liable for incidental or consequential damages Some states do not allow lim...

Отзывы: