background image

9160-00

Page 2

60707-122

Check the appliance or tool nameplates for the current and
voltage to insure compatibility.  Remember that power taken
from receptacle C reduces the power available at both A and
B.  Any remaining 120 volt loads should be equally divided
between A and B.  Failure to split the load will cause
permanent damage to the stator.  Although circuit breakers
are provided, damage due to overloading constitutes abuse
and will not be warranted.

Starting Electric Motors - Electric motors require much
more current (amps) to start them than to  run them.  Some
motors, particularly low cost split-phase motors, are very hard
to start and require 5 to 7 times as much current to start them
as to run them.  Capacitor motors are easier to start and
usually require 2 to 4 times as much current to start them as
to run them.  Repulsion Induction motors are the easiest to
start and usually require 1 1/2 to 2 1/2 times as much to start
them as to run them.

Most fractional horsepower motors take about the same
amount of current to run them whether they are of Repulsion-
Induction (RI), Capacitor (Cap), or Split-Phase (SP) type.
The chart below shows the approximate current required to
start and run various types and sizes of 120 volt 60 cycle
electric motors under average load conditions.

       RUNNING

    STARTING AMPS

   HP

   AMPS        SP

CAP

        RI

1/6

 3.2

16 TO 22

 6 TO 13

 5 TO  8

1/4

 4.5

22 TO 32

 9 TO 18

 7 TO 12

1/3

 5.2

26 TO 35

10 TO 21

 8 TO 17

1/2

 7.2

NOT MADE 14 TO 29

11 TO 18

1

13.0

NOT MADE 26 TO 52

20 TO 33

The figures given above are for an average load such as a
blower or fan.  If the electric motor is connected to a hard
starting load such as an air compressor, it will require more
starting current.  If it is connected to a light load, or no load
such as a power saw, it will require less starting current.  The
exact requirement will also vary with the brand or design of
the motor.

Self-excited generators respond to severe overloading
differently than the power line.  When overloaded, the engine
is not able to supply enough power to bring the electric motor
up to operating speed. The generator responds with high
initial starting current, but the engine speed drops sharply.
The overload may stall the engine. If allowed to operate at
very low speeds, the electric motor starting winding will burn
out in a short time.  The generator winding might also be
damaged.

CAUTION: EQUIPMENT DAMAGE

RUNNING THE GENERATOR SET UNDER  THESE
CONDITIONS MAY RESULT IN DAMAGING THE
GENERATOR STATOR AS WELL AS THE MOTOR
WINDING.

Because the heavy surge of current required for starting
motors is required for only an instant, the generator will not
be damaged if it can bring the motor up to speed in a few
seconds of time.  If difficulty is experienced in starting motors,
turn all other electrical loads off and if possible reduce the
load on the electric motor.

INTENDED USES

These engine generator sets have been designed primarily
for portable use.  Both 120 and 240 volt AC receptacles are
provided in the 'control panel' to plug in your loads (lights,
portable tools, and small appliances).  These units are dual
wound generators, therefore the 120 Volt loads must be
equally split with 1/2 of the rated capacity available on
each of the two 120 Volt circuits. See unit capabilities for
further explanation.

These portable units require large quantities of fresh air for
cooling of both the engine and the generator.  Fresh air is
drawn from both the engine end and the generator end and
is exhausted at the center of the unit.  For safety, long life
and adequate performance, these units should never be
run in small compartments without positive fresh air flow.

RESTRICTED USES

DO NOT remove from the cradle assembly.  Removal of
the generator from the cradle assembly may cause
excessive vibration and damage to the engine generator
set.

DO NOT install and operate these portable generators in a
small compartment., i.e. generator compartment of
vehicles, motor homes or travel trailers.  These
compartments will not allow enough free flow fresh air to
reach the  engine generator set for cooling and will cause
the unit to overheat damaging both the engine and the
generator.  Small compartments will also develop hot spots
where there is very little air flow and may cause a fire.

DO NOT attempt to operate at 50 cycles.  These units are
designed and governed to operate at 60 cycles only.

UNIT CAPABILITIES

Generator Connections - The diagram below represents a
typical 5400 watt generator.  Receptacles A and B are the
two 120 Volt duplex receptacles. Up to 2700 watts at 120
volts (22.5 Amps) can be taken from the generator at each
of the receptacles. This generator produces 120 and 240
volt, 60 Hz (Hertz), AC (Alternating Current).

CAUTION: EQUIPMENT DAMAGE

CAUTION MUST BE EXERCISED TO PREVENT
OVERLOADING EITHER OF THE GENERATORS
120  VOLT OUTPUT CIRCUITS (A OR B).

Содержание CSADL6000I/E

Страница 1: ...INSTALLATION OPERATION and MAINTENANCE INSTRUCTIONS CSADL6000I E CSADL6000IE E ...

Страница 2: ...CTIONS Initial Starting 4 Starting 4 Starting Hints 4 Stopping And Storage 4 Operating Speed 5 Connecting The Loads 5 OPERATOR CARE AND MAINTENANCE Engine Care 6 Generator Care 6 Cleaning 6 Troubleshooting Things To Check BEFORE You Call For Service 7 Complete Unit Parts List 8 Receptacle Panel Parts List 9 Wiring Diagram 10 WARRANTY 10 Read and understand all instructions in the manual before sta...

Страница 3: ...RE HAZARD Gasoline and other fuels always present a hazard of possible explosion and or fire a Do not refuel when the engine is running or hot Allow the engine to cool at least two minutes before refueling b Keep fuel containers out of reach of children c Do not smoke or use open flame near the generator set or fuel tank d Keep a fire extinguisher nearby and know its proper use Fire extinguishers ...

Страница 4: ... The generator winding might also be damaged CAUTION EQUIPMENT DAMAGE RUNNING THE GENERATOR SET UNDER THESE CONDITIONS MAY RESULT IN DAMAGING THE GENERATOR STATOR AS WELL AS THE MOTOR WINDING Because the heavy surge of current required for starting motors is required for only an instant the generator will not be damaged if it can bring the motor up to speed in a few seconds of time If difficulty i...

Страница 5: ... is especially true if an unexpected shutdown would cause a safety hazard or serious inconvenience for the operator UNPACKING CAUTION EQUIPMENT DAMAGE THIS UNIT HAS BEEN SHIPPED WITHOUT OIL Failure to maintain the engine oil at the proper level will result in serious engine damage When you unpack your new ENGINE GENERATOR be sure to remove all the information sheets and manuals from the carton 1 T...

Страница 6: ... run position CAUTION EQUIPMENT DAMAGE Never permit the choke to remain on after the engine has run for a short time It is not necessary to choke the engine when it is warm Avoid over choking STARTING HINTS 1 Cold weather a Use the proper oil for the temperature expected b Use fresh winter grade fuel Winter grade gasoline is blended to improve starting Do not use summer gasoline 2 Hot weather a Us...

Страница 7: ...r sets are inherently self regulating based on engine speed The engine governor will automatically adjust itself to the load No harm to the generator will result if it is operated with no load connected Proper utilization of the receptacles located on the control panel is necessary to prevent damage to either the receptacles or the generator The generator is a limited source of electrical power th...

Страница 8: ...sembly from base b Remove foam pre cleaner by sliding it off the paper cartridge c Wash foam pre cleaner in liquid detergent and water d Wrap foam pre cleaner in cloth and squeeze dry e Saturate foam pre cleaner in engine oil Squeeze to remove excess oil f Install foam pre cleaner over paper cartridge Reassemble cover and screw down tight Replace the cartridge included with Dual Element Air Cleane...

Страница 9: ...itor Defective stator Defective rotor field Circuit Breaker Over Loaded Trips Defective receptacle Defective circuit breaker Too small long of drop cord Voltage too high Engine speed is too high Generator Overloaded overheating Insufficient ventilation No output voltage Short in load disconnect Broken or loose wire Defective receptacle No residual magnetism in generator Defective stator Defective ...

Страница 10: ...nts 4 16249 000 4 Locknut 5 16 18 5 16250 000 1 Flange Nut 3 8 16 6 464 000 1 Cap Screw 3 8 16 X 75 7 16335 007 1 Generator Support 8 15676 005 1 Battery Tray 1 NI 15767 005 1 Negative Battery Cable 1 NI 15767 016 1 Positive Battery Cable 1 NI 15807 000 1 Battery Holddown Kit 1 9 15617 003 1 End Cover Assembly 10 63073 031 1 Cradle Assembly 11 58684 011 1 Edge Trim ...

Страница 11: ...6 006 1 Complete Generator Assembly 14 15632 007 1 Engine B S Intek 1 210317 0191 B1 14 15632 008 1 Engine B S Intek 2 210312 0190 B1 15 468 000 2 Cap Screw 5 16 18 X 1 5 16 480 000 2 Lockwarsher 5 16 17 466 000 2 Cap Screw 1 4 20 X 75 18 512 000 2 1 4 Flat Washer 19 16133 000 2 Leather Washer 20 81018 008 1 Clamp 21 98771 000 1 Fuel Valve 22 62999 001 2 Fuel Line Clamp 23 40078 000 28 1 4 Fuel Li...

Страница 12: ...rior to placing the unit in service The user shall assume all risks and liability in connection with determining the suitability of the unit for its particular use Neither the manufacturer nor the seller shall be liable for any injury loss or damage arising out of improper use or operation of this unit In no event is WINCO liable for incidental or consequential damages Some states do not allow lim...

Отзывы: