background image

Dyer Environmental Controls Ltd

RZN 4402/04-K V2 Troubleshooting Guide

Operational faults
Fire alarm interface

:

• 

Confirm signal from interface is normally open volt free.

• 

1kΩ triggering resistor installed as detailed on previous page.

• 

10kΩ end of line resistor installed as detailed on previous page

Smoke detector

:

• 

Ensure the 10kΩ end of line resistor is installed as detailed on previous page.

•  Turn smoke detector head clockwise until a click is heard and a physical connection is made between head 

and base.

Breakglass

:

• 

10kΩ end of line resistor installed and connections as detailed on previous page.

• 

Confirm the breakglass terminal connector is firmly secured onto the PCB.

•  Check external signal fuse is present and has not blown.

Drive

:

•  Check MOT terminal connections in the control panel and local connection point.

•  Test power supply from terminals A and B in control panel, minimum of 24v DC should be present on operation 

(fire).

•  If voltage is present on operation and connections are correct, the issue is with the drive(s) and not the controls, 

see drive information for assistance. 

•  If no voltage is present on operation, check 1.6 Amp (4402) / 3.15 Amp (4404) fuse is present and has not blown. 

DIP-Switches

:

•  For operational set-up (including one-touch reset of system) see information on control panel data sheet.

Dyer Environmental Controls Ltd, Unit 10, Lawnhurst Trading Estate, Cheadle Heath, Stockport, Cheshire SK3 0SD   

         Page 2 of 2

www.dyerenvironmental.co.uk      +44 (0)161 491 4840      Registered in England 02670985      VAT No. 611329279   

 

        V1

Отзывы: