Safety notes

Safety extra low voltage 24 V DC!

Do not connect directly to the mains supply!

- Connection must be carried out by a certified

electrical technician

- Danger of crushing hands and fingers!

- Keep people away from the operating area of the

drive

- Keep children away from the control

- Observe pressure load diagram of the chain

- Use only in dry rooms

- Suitable for indoor mounting only. Use rain

detector in locations if there is a risk of rain

- Use unmodified original D+H parts only

- Observe mounting instructions of bracket set!

Observe enclosed red safety note!

Intended use

- Chain drive for electric opening and closing of

windows and flaps in the facade and roof area

- Operating voltage 24 V DC

- Useable for smoke ventilation as well as daily

natural ventilation

- Suitable for indoor mounting only

CDC-0252-1-TMS+

CDC-0252-1-TMS+

7/20

99.827.61 1.0/01/18

English

Technical Data

* Programmable with software SCS   ** + approx. 20 % switch-off reserve (temporary)

C3*

250 N

Opening and Closing Ranges

O1*

C1*

C2*

O2*

O3*

23 mm

150 N

77 mm

150 N

23 mm

250 N

15 mm

250 N

250 N

Type

CDC-0252-0350-1-TMS+ -R

CDC-0252-0600-1-TMS+ -R

CDC-0252-0800-1-TMS+ -R

Power supply
Nominal force

24 V DC / ± 15 %

250 N**

Nominal current

0,6 A

0,8 A

1,0 A

Nominal stroke length*

350 mm ± 2 %

600 mm ± 2 %

800mm ± 2 %

Running speed: ventilation (SHEV high-speed function)*

O1, O2
O3
C3
C2, C1

6,7 mm/s (9,4 mm/s)
6,7 mm/s (6,7 mm/s)

5 mm/s
5 mm/s

6,7 mm/s (13,6 mm/s)

6,7 mm/s (6,7 mm/s)

6,7 mm/s

5 mm/s

6,7 mm/s (15,0 mm/s)

6,7 mm/s (6,7 mm/s)

6,7 mm/s

5 mm/s

Nominal locking force
Service life
Duty cycle
Housing
Ingress protection
Temp. range
Fire stability
Ambient humidity
Emission sound pressure level
Additional functions*

approx. 1500 N

>20.000 double strokes

30% (with cycle time 10 min.)

Aluminium powdercoated (~ RAL 9006)

IP 32

-5 ... +75 °C

30 min / 300 °C

≤ 90 %, not condensing

LpA   35 dB(A)

Closing edge protection = activated (3 repetitions of stroke);

Locking relief  = activated (retraction lift max. 0,2 mm)

WARNING

Read all safety warnings, instructions, illustrations 

and specifications provided with this product.

Failure to follow all instructions listed below may 

result in electric shock, fire and/or serious injury.

Save all warnings and instructions for future 

reference.

Observe maximum pressure load of the chain!

Maximum pressure load of chain is not automatically 

identical with maximum pressure force of the drive!

100

200

300

400

500

600

700

800

250

300

200
150
100

50

0

Pressure load (N)

Stroke (mm)

Pressure load diagram

Main closing edge

Beside closing edge

Beside

closing edge

Closing edge protection

In  the  "CLOSE"  direction  the  drive  has  an  active 

protection for the main closing edge. If there is an 

overload in the closing ranges C3 and C2, the drive 

runs "OPEN" for 10 seconds, then "CLOSE" again. If 

closing is not possible after three attempts, the drive 

remains in this position.

In  addition,  the  drive  is  equipped  with  passive 

protection. The closing speed in closing range C2 

and C1 is reduced to 5 mm/s.

Significantly greater forces can be

exerted at the secondary closing

edges. Danger of crushing hands and

fingers!

Scope of supply

Drive unit with 2.5 m silicone cable.

Depending on the type of window, different bracket 

sets are available separately.

Performance features

- Micro processor controlled electronics

- Individually programmable via Powerline (PLP1

and SCS)

- Stroke programming with magnets

- Outstanding quiet performance thanks to acoustic

decoupling of the drive components and reduced

speed in ventilation mode

- Connection via plug connector

- Tandem-safety function for operation of two

CDC-0252-1-TMS+ drives on one sash

Up to two CDC-0252-1-TMS+ drives and one locking 

drive can be used in tandem. Combined TMS and 

BRV signal.

The  BRV  signal  is  only  output  when  in  the  end 

position - this prevents locking drives and modules 

from malfunctioning.

During  the  learning  phase,  the  activated  stroke  is 

transferred  to  the  tandem  drive  via  the  TMS+ 

function.

TMS+ / -BRV function

Содержание CDC-0252 1-TMS+ Series

Страница 1: ...CDC 0252 1 TMS instructions Please order bracket sets separately ...

Страница 2: ...shock fire and or serious injury Save all warnings and instructions for future reference Observe maximum pressure load of the chain Maximum pressure load of chain is not automatically identical with maximum pressure force of the drive 100 200 300 400 500 600 700 800 250 300 200 150 100 50 0 Pressure load N Stroke mm Pressure load diagram Scope of supply Drive unit with 2 5 m silicone cable Dependi...

Страница 3: ...ity Ambient humidity Emission sound pressure level Additional functions approx 1500 N 20 000 double strokes 30 with cycle time 10 min Aluminium powdercoated RAL 9006 IP 32 5 75 C 30 min 300 C 90 not condensing LpA 35 dB A Closing edge protection activated 3 repetitions of stroke Locking relief activated retraction lift max 0 2 mm Main closing edge Beside closing edge Beside closing edge Closing ed...

Страница 4: ...formation 23 mm X Stroke limiting with magnets Voltage must continue to be applied to the drive when moving in the CLOSE direction Hold the magnet next to the drive as shown in the diagramme 2 sec until you hear a pulsating ton The drive is now in learning mode The magnet can now be removed and the drive no longer has to be under voltage Close drive Allow the drive to run OPEN until you reach the ...

Страница 5: ...e at D H MechatronicAG D 22949Ammersbek Dirk Dingfelder Maik Schmees Member of the Board Authorized signatory Technical Director 29 01 2018 Maintenance and cleaning Maintenance work is only allowed when the device is in a de energized condition Inspection and maintenance has to be carried out according to D H maintenance notes Only original D H spare parts may be used Repairistobecarriedoutexclusi...

Страница 6: ... 1 2 3 4 5 L 6 N 7 Z A E X a b LT Group MOT BK BK OG 2x47kW End mod ul Term inal mod ule Mod ule term inal EM 47 K OG YE GN WH Mot a BN Mot b HS TMS n c CDC 0252 1 TMS GY n c Junction box High Speed High Speed High Speed Mot b BN Mot a WH 24 V DC 24 V DC Monitoring Normal mode SHEV fast running 1 drive Connection PinAssignment 6x 0 5 mm Ø 7 1 0 5 mm WH white BN brown OG orange YE yellow GN green G...

Страница 7: ...b 1 2 3 4 5 L 6 N 7 Z A E X a b LT Group MOT BK BK OG 2x47kW End mod ul Term inal mod ule Mod ule term inal EM 47 K OG YE YE GN GN WH BN Mot a Mot b HS HS TMS TMS n c n c CDC 0252 1 TMS CDC 0252 1 TMS GY n c Junction box GY n c BN Mot b WH Mot a Monitoring OG ...

Страница 8: ...252 0350 1 TMS CDC 0252 0600 1 TMS CDC 0252 0800 1 TMS A B C Dimensions 30 mm 3 5 m m A Dyer Environmental Controls Ltd Unit 10 Lawnhurst Trading Estate Cheadle Heath Stockport SK3 0SD Tel 44 0 161 491 4840 E Mail enquiry dyerenvironmental co uk www dyerenvironmental co uk ...

Отзывы: