Dwyer Instruments CAM Series Скачать руководство пользователя страница 2

ELECTRICAL CONNECTION

A suitably qualified electrician must connect the unit.  Voltage supplied
according to EN50178, SELV, PELV.  The device shall be supplied from
an isolating source and protected by an overcurrent device such that the
limited voltage circuit requirements in accordance with UL 508 are met.
Disconnect power before connecting the unit as follows in Figure 2.

Disconnect power before connecting the unit as follows:

INSTALLATION

Location: 

Select an area where the process temperature will remain between 32
and 140°F (0 to 60°C). Preferred mounting location is downstream from
the cold dryer, near the load. If compressed air is fed into the main pipe
through parallel pipes, the unit should be mounted in the main pipe.

Position:

The unit may be positioned vertically, horizontally, and on its

side with the pipe length left.  Avoid positioning the unit on its side with
the pipe length to the right.  This may jeopardize the accuracy:

Mounting:

To achieve the specified measurement accuracy, the follow-

ing mounting conditions must be adhered to:  defined inflow/outflow pipe
lengths, defined flow cross-sectional area, fixed installation depth and
correct positioning of the measuring elements. Integrate the pipe length
so that the direction of flow and the marking arrow show in the same
direction.  In case of disturbances at the inflow side additional baffled
pipes are recommended:

MAINTENANCE

After mounting, wiring and programming check whether unit operates
correctly. Unit is maintenance free for media which will not adhere to
measuring probes. Occasionally, probes should be visually checked for
build-up. If necessary, clean probes with a suitable liquid (e.g. alcoholic
solution). Avoid mechanical damage to measuring probes.

Figure 1

Figure 3

Core socket colors
1 = BN, 2 = WH (white), 3 = BU (blue), 4 = BK (black).

Figure 2

C-32:Magnesense bulletin  9/24/09  11:48 AM  Page 2

www.

GlobalTestSupply

.com

Find Quality Products Online at:

[email protected]

Содержание CAM Series

Страница 1: ...Steel 304S15 ceramics glass passivat ed PEEK polyester Fluoroelastomer anodized aluminum Response Time 0 1 seconds Temperature Limit 32 to 140 F 0 to 60 C Accuracy 1 41 3 0 3 FV 3 44 6 MV 0 6 FV Pressure Limit 232 psig 16 bar Humidity Limit 90 RH Power Requirements 19 30 DC Output Signal Output 1 PNP Open Collector VOUT max 30 VDC ISINK max 250mA Output 2 4 20mA scalable or PNP Open Collector Loop...

Страница 2: ...ng the unit on its side with the pipe length to the right This may jeopardize the accuracy Mounting To achieve the specified measurement accuracy the follow ing mounting conditions must be adhered to defined inflow outflow pipe lengths defined flow cross sectional area fixed installation depth and correct positioning of the measuring elements Integrate the pipe length so that the direction of flow...

Страница 3: ...ey Functions Figure 4 Chart 2 To decrease the value cycle past the maximum value and the setting will restart from the minimum www GlobalTestSupply com Find Quality Products Online at sales GlobalTestSupply com ...

Страница 4: ...www GlobalTestSupply com Find Quality Products Online at sales GlobalTestSupply com ...

Страница 5: ...able as the current count of the total izer possible data loss can be maximum 10 minutes Display indicates current measured values yellow LED s signal switching status of out puts Display unit can be temporarily changed press Set button briefly after 15 seconds unit returns to display unit set in menu point Uni Display Mode Indicates parameters and set parameter values When Mode Enter button is pu...

Страница 6: ...ween SPx and rPx SPx upper value rPx lower value Scaling measuring range analog output Analog start point ASP is the measured value at which the output sig nal 4 mA is defined Analog end point AEP is the measured value at which the output signal 20 mA is defined Minimum distance between ASP and AEP 25 of final measuring range value Output signal ranges from 4 to 20 mA in set measuring range Output...

Отзывы: