Introduction 1
1 - 2
I/O Plexer Repeaters can be used to convert signals from one type to another. For example, a
thermocouple at the remote site can be converted to a standard process current (4-20mA)
signal at the local site.
Communications:
DuTec supports several standards for transmitting serialized I/O data between I/O Plexer
repeaters. In addition to hard wiring, built in modem control lines allow the use of telephone,
fiber optic, and radio modems at baud rates to 38,400.
Maximum Distance
Serial Link
Feet
Meters
RS-232
50
15
RS-422
5,000
1,524
RS-485
5,000
1,524
Modem
Unlimited
Unlimited
Response Time
:
Under full load (sixteen analog and 48 digital signals), the average response time between an
input event and resulting output is less than 250mS @9600 Baud.
Easy Setup:
The I/O Plexer Repeater has its own power supply, no need to purchase or reserve space for
an external supply. A push-button and on board LED indicator configure the baud rate and
Input/ Output separators. Removable terminal strips allow the attachment/ removal of
multiple cable sets in one step. This modularity greatly reduces troubleshooting and upgrade
delays.
Содержание I/O Plexer Repeater
Страница 1: ...Repeater MANUAL ...
Страница 2: ......
Страница 5: ...Table of Contents Sequential display 3 4 Communication Verification 3 5 Hardware error codes 3 5 ...
Страница 11: ...Introduction 1 1 6 ...
Страница 29: ...Installation 2 2 18 ...
Страница 35: ...Index The local RS 232 port 2 6 Thermocouple 1 4 2 13 UNIT O 2 8 3 1 UNIT1 2 8 ...