Setup 3
3 - 2
Unit Number:
Each I/O Plexer Repeater is set to either
UNIT O
or
UNIT 1.
The sequential display indicates
Echo = followed by the unit number. When shipped from the factory, I/O Plexer Repeaters are
configured as
UNIT 1
(Echo = 1).
Input/ Output Separators:
Each
UNIT O
will require up to four input/ output separators to be set. This identifies which
modules are inputs and which are outputs for each chassis being used. For example,
UNIT O
could consist of its main chassis as well as up to three digital expander chassis. Upon
establishing communications,
UNIT O
Will automatically configure the
UNIT 1
separator
appropriately.
The first I/O separator, following the o in the sequential display, is the
UNIT O
main chassis
I/O separator. It should be set equal to the hex value of the lowest numbered module position
containing an output module (analog or digital) on the
UNIT O
main chassis. If
UNIT O
is full
(all 16 positions) of outputs, set the I/O separator to
O
. Refer to the worksheet found on page
2-9.
The second I/O separator, following the
°
in the sequential display, is the first digital
expander I/O separator. It should be set equal to the lowest numbered module position
containing a digital output module on the first expander chassis. Refer to the worksheet on
page 2-10. If the first digital expander is not being used, disregard this value.
The third separator, following the 1 in the sequential display, is the I/O separator for the
second digital expander. It should be set equal to the lowest numbered module position
containing a digital output module on the second expander chassis. Refer to the worksheet
found on page 2-11. If the second digital expander is not being used, disregard this value.
The last I/O separator, following the
11
in the sequential display, is the third digital expander
I/O separator. It should be set equal to the lowest numbered module position containing a
digital output module on the third digital expander chassis. Refer to the worksheet on page 2-
12. If the third expander is not being used, disregard this value.
Содержание I/O Plexer Repeater
Страница 1: ...Repeater MANUAL ...
Страница 2: ......
Страница 5: ...Table of Contents Sequential display 3 4 Communication Verification 3 5 Hardware error codes 3 5 ...
Страница 11: ...Introduction 1 1 6 ...
Страница 29: ...Installation 2 2 18 ...
Страница 35: ...Index The local RS 232 port 2 6 Thermocouple 1 4 2 13 UNIT O 2 8 3 1 UNIT1 2 8 ...