![DutchWest 2478 Скачать руководство пользователя страница 10](http://html1.mh-extra.com/html/dutchwest/2478/2478_homeowners-installation-and-operating-manual_2543490010.webp)
10
Dutchwest
®
Non-Catalytic Convection Heater
30002278
Procedure:
1. Convert speciications to R-value:
i. R-value given - no conversion needed.
ii. k-factor is given with a required thickness (T) in
inches:
iii. K-factor is given with a required thickness (T) in
inches:
iv. r-factor is given with a required thickness (T) in
inches: R = r x T
2. Determine the R-value of the proposed alternate
loor protector:
i. Use the formula in Step 1 to convert values not
expressed as R.
ii. For multiple layers, add R-values of each layer to
determine overall R-value.
3. If the overall R-value of the system is greater than
the R-value of the speciied loor protector, the alter-
nate is acceptable.
EXAMPLE:
The speciied loor protector should be 5/8-
inch thick material with k-factor of 0.84. The proposed
alternate is 4” brick with an r-factor of 0.2 over 1/8”
mineral board with a k-factor of 0.29
Step a: Use formula above to convert speciication to
R-value:
Step b: Calculate R of proposed system.
4” brick of r = 0.2, therefore:
R
brick
= 0.2 x 4 = 0.8
1/8” mineral board of k = 0.29, therefore
R
mineralboard
= x 0.125 = 0.431
R
total
= R
brick
+ R
mineralboard
= 0.8 + 0.431 = 1.231
Step c: Compare proposed system Rtotal of 1.231 to
speciied R of 0.744. Since proposed system Rtotal
is greater than required, the system is acceptable.
Deinitions
To install the heater without legs as a ireplace insert,
the loor must be completely noncombustible, such as
an unpainted concrete loor over earth.
Many ireplaces do not satisfy the “completely non-
combustible” requirement because the brick or con-
crete hearth in front of the ireplace opening usually is
supported by heavy wooden framing as in Figure 13.
Because heat passes readily through brick or concrete,
it can easily pass through to the wood. As a result, such
ireplace hearths are considered a combustible loor.
You may not install a heater on a combustible hearth
without legs. Standard leg installations must include the
bottom heat shield. The loor protector must also meet
standard requirements for freestanding installations.
Floor Protection for Fireplace
Installations with Standard Legs
Fireplace installations with the standard legs and the
bottom heat shield must have a loor protector of the
same construction as that speciied for freestanding
installations: use an approved 5/8” (16mm) noncom-
bustible hearth pad with K = 0.84 BTU/in ft
2
hr °F or an
equivalent material with an R-value of at least 0.744
(that may be covered with a decorative noncombustible
material if you desire). (Refer to “How to Determine if
Alternate Floor Protection Materials are Acceptable”
section) The loor protector must extend at least 16”
(406 mm) [18” / 457 mm in Canada] from the front of
the stove and from the left (loading door) side, and at
least 8” (203 mm) from the right side and rear. It must
also provide protection beneath any horizontal runs of
the chimney connector, including 2” to either side.
Many raised hearths will extend less than the required
distance from the front of the heater when it is installed.
In such cases, suficient loor protection, as described
above, must be added to extend the hearth 16” (406
mm) [18” (457 mm) in Canada].
Hearth rugs do not satisfy the requirements for loor
protection.
Fireplace insert installations also have speciic clear-
ance requirements to the side walls, side decorative
trim, and ireplace mantel. This information is found in
“Fireplace Installation Clearances” in this section.
REMINDER- FIREPLACE INSERT INSTALLATIONS
WITHOUT LEGS ARE PERMISSIBLE ONLY IF THE
HEARTH IS COMPLETELY NONCOMBUSTIBLE,
SUCH AS UNPAINTED CONCRETE OVER EARTH.
R = x T
1
K x 12
R = x T = x 0.625 = 0.744
1
k
1
0.84
1
0.29
(Btu)(ft)
(ft
2
)(hr)(°F)
K =
k = = K x 12
(Btu)(in)
(ft
2
)(hr)(°F)
R = (ft
2
)(hr)(°F)
Btu
Fireplace Installations
The Dutchwest Model 2478 has a reversible lue collar
to allow for either top exit or rear exit installations.
You may install your Dutchwest Model 2478 in an exist-
ing ireplace as a ireplace insert with no legs, or with
the standard legs attached.
R = x T
1
k
(ft
2
)(hr)(°F)
(Btu)(in)
1
k
=
r =