DutchWest 2478 Скачать руководство пользователя страница 10

10

Dutchwest

®

 Non-Catalytic Convection Heater

30002278

Procedure:

1.  Convert speciications to R-value:

i.  R-value given - no conversion needed.

ii.  k-factor is given with a required thickness (T) in 

inches:  

iii. K-factor is given with a required thickness (T) in 

inches:

iv. r-factor is given with a required thickness (T) in 

inches:  R = r x T 

2.  Determine the R-value of the proposed alternate 

loor protector:
i.  Use the formula in Step 1 to convert values not 

expressed as R.

ii.  For multiple layers, add R-values of each layer to 

determine overall R-value.

3.  If the overall R-value of the system is greater than 

the R-value of the speciied loor protector, the alter-

nate is acceptable.

EXAMPLE:

 The speciied loor protector should be 5/8-

inch thick material with k-factor of 0.84. The proposed 

alternate is 4” brick with an r-factor of 0.2 over 1/8” 

mineral board with a k-factor of 0.29
Step a: Use formula above to convert speciication to 

R-value:

Step b: Calculate R of proposed system. 
  4” brick of r = 0.2, therefore:
   R

brick

 = 0.2 x 4 = 0.8

  1/8” mineral board of k = 0.29, therefore
   R

mineralboard

 =         x 0.125 = 0.431 

   R

total

 = R

brick

 + R

mineralboard

 = 0.8 + 0.431 = 1.231

Step c: Compare proposed system Rtotal of 1.231 to 

speciied R of 0.744. Since proposed system Rtotal 

is greater than required, the system is acceptable.

Deinitions

To install the heater without legs as a ireplace insert, 

the loor must be completely noncombustible, such as 

an unpainted concrete loor over earth.
Many ireplaces do not satisfy the “completely non-

combustible” requirement because the brick or con-

crete hearth in front of the ireplace opening usually is 

supported by heavy wooden framing as in Figure 13.  

Because heat passes readily through brick or concrete, 

it can easily pass through to the wood. As a result, such 

ireplace hearths are considered a combustible loor. 

You may not install a heater on a combustible hearth 

without legs. Standard leg installations must include the 

bottom heat shield.  The  loor protector must also meet 

standard requirements for freestanding installations.

Floor Protection for Fireplace 

Installations with Standard Legs 

Fireplace installations with the standard legs and the 

bottom heat shield must have a loor protector of the 

same construction as that speciied for freestanding 

installations: use an approved 5/8” (16mm) noncom-

bustible hearth pad with K = 0.84 BTU/in ft

2

 hr °F or an 

equivalent material with an R-value of at least 0.744 

(that may be covered with a decorative noncombustible 

material if you desire).  (Refer to “How to Determine if 

Alternate Floor Protection Materials are Acceptable” 

section) The loor protector must extend at least 16” 

(406 mm) [18” / 457 mm in Canada] from the front of 

the stove and from the left (loading door) side, and at 

least 8” (203 mm) from the right side and rear.  It must 

also provide protection beneath any horizontal runs of 

the chimney connector, including 2” to either side.
Many raised hearths will extend less than the required 

distance from the front of the heater when it is installed.  

In such cases, suficient loor protection, as described 

above, must be added to extend the hearth 16” (406 

mm) [18” (457 mm) in Canada].
Hearth rugs do not satisfy the requirements for loor 

protection.  
Fireplace insert installations also have speciic clear-

ance requirements to the side walls, side decorative 

trim, and ireplace mantel.  This information is found in 

“Fireplace Installation Clearances” in this section. 

REMINDER- FIREPLACE INSERT INSTALLATIONS 

WITHOUT LEGS ARE PERMISSIBLE ONLY IF THE 

HEARTH IS COMPLETELY NONCOMBUSTIBLE, 

SUCH AS UNPAINTED CONCRETE OVER EARTH.

R =             x T

1

K x 12

R =    x T  =          x 0.625 = 0.744

1

k

1

0.84

1

0.29

(Btu)(ft)

(ft

2

)(hr)(°F)

 

K =                

 

k =                   = K x 12

(Btu)(in)

(ft

2

)(hr)(°F)

 

R = (ft

2

)(hr)(°F)

Btu

Fireplace Installations

The Dutchwest Model 2478 has a reversible lue collar 

to allow for either top exit or rear exit installations.
You may install your Dutchwest Model 2478 in an exist-

ing ireplace as a ireplace insert with no legs, or with 

the standard legs attached.

R =   x T

1

k

(ft

2

)(hr)(°F)

(Btu)(in)

1

k

=

r =

Содержание 2478

Страница 1: ...this heater is not properly installed operated and maintained a house ire may result For safety follow all installation operation and maintenance directions Contact local building oficials about rest...

Страница 2: ...to cause cancer birth de fects and other reproductive harm California Health Safety Code Sec 25249 6 Table of Contents Speciications 3 Installation 4 Clearances 10 Assembly 16 Operation 18 Maintenanc...

Страница 3: ...d or if you live in a more severe or more temper ate climate these igures may not apply Since so many variables affect performance consult your Dutchwest Authorized Dealer to determine realistic expec...

Страница 4: ...must be connected to 1 a chimney complying with the requirements for Type HT chimneys in the standard for Chimneys Fac tory Built Residential Type and Building Heating Appli ance UL 103 or 2 a code a...

Страница 5: ...himney Connector The chimney connector is the single wall pipe or listed and approved double wall pipe that connects the stove to the chimney The chimney itself is a masonry or prefabricated structure...

Страница 6: ...telescoping joints with at least three sheet metal screws 3 Secure the chimney connector to the chimney In structions for various installations follow below 4 Conirm that the installed stove and chim...

Страница 7: ...rises from the stove turns ninety degrees and goes back into the ireplace chimney The liner of the ireplace chimney should extend at least to the point at which the chimney connector enters the chimne...

Страница 8: ...all is cut away a sufi cient distance from the single wall connector to provide the required 12 305 mm clearance for the connector Any material used to close up the opening must be non combustible The...

Страница 9: ...rial with an R value of at least 0 744 Refer to How to Deter mine if Alternate Floor Protection Materials are Accept able section The loor protector may be covered with a decorative noncombustible mat...

Страница 10: ...installations must include the bottom heat shield The loor protector must also meet standard requirements for freestanding installations Floor Protection for Fireplace Installations with Standard Leg...

Страница 11: ...furnish ings and other combustible materials away from the stove as well In general a distance of 48 1220 mm must be maintained between the stove and moveable combustible items such as drying clothes...

Страница 12: ...the Stove and Chimney Connector Clearance Chart that follows For example the letter A gives the minimum side clear ance for installations in which the stove is not equipped with any heat shield and th...

Страница 13: ...P 7 heat shield 432 mm 381 mm 191 mm 178 mm 368 mm 178 mm Double wall connector Chimney Connector Clearance Single wall connector 20 14 No connector heat shield 508 mm 356 mm Single wall2 connector 10...

Страница 14: ...wall protector A B C E D F C F Chimney Connector Side Rear Corner Side Rear Corner Listed Approved A 30 B 13 C 18 D 21 E 12 F 18 Double wall with 762 mm 330 mm 470 mm 533 mm 318 mm 457 mm lue collar...

Страница 15: ...er Model 2478 48 1220 mm 60 1525 mm Spaced 1 25 mm from Floor ST802 Fig 17 Sidewall protection 60 1525 mm 48 1220 mm Spaced 1 25 mm from Floor ST803 Fig 18 Corner wall protection Wall Shields Meet at...

Страница 16: ...parts or using damaged parts A Bottom Heat Shield is required in many instal lations Refer to the loor protection information found in the Installation Section of this manual Attach the Legs and Heat...

Страница 17: ...owly to ensure the loor is not scratched Retighten all leg fastening hardware ST816 Fig 21 Reposition stove so one rear leg can be attached Rheostat Knob Rheostat Snapstat Pan Head Screws Fig 23 Fan i...

Страница 18: ...stove Fig 24 The lever operates two internal shut ters Opening the inlet shutters provides air for primary combustion To open the shutters turn the lever clockwise The shutters are all the way open wh...

Страница 19: ...quickly resulting in short burn time and dimin ished stove performance If you must burn it mix it in with greener wood to slow the burn Store your irewood under cover to keep it dry Even for short te...

Страница 20: ...empt to increase the iring rate of your heater by altering the air control adjustment range outlined in these directions In some newer homes that are well insulated and weather tight poor draft may re...

Страница 21: ...T THE FIRE DO NOT BURN GARBAGE OR FLAM MABLE FLUIDS SUCH AS GASOLINE NAPTHA OR ENGINE OIL Also never use gasoline type lantern fuel kerosene charcoal lighter luid or similar liquids to start or freshe...

Страница 22: ...on a noncombustible surface in a metal container with a tight itting lid ST438 ST805 Fig 29 Check the ash compartment before reloading the stove Safe Ash Handling Ashes may contain hot coals and must...

Страница 23: ...procedure Fig 31 1 Loosen the small locking nut with an open end wrench 2 Use the allen wrench included with the stove to turn the striker screw clockwise one quarter turn and close the door to test...

Страница 24: ...loosen and then remove the two 2 nuts on the threaded rods that secure the top plate to the inner top of the stove 2 Remove the top plate and open the damper 3 Loosen the adjusting bolt s lock nut Fi...

Страница 25: ...stove cool completely before you inspect the chimney Use a lash light and mirror to sight up the lue through the chimney clean out door or chimney connector inspection tee If no inspection access is...

Страница 26: ...tor and the elbows Clean the system if nec essary ANNUAL SPRING CLEANING Disassemble the chimney connector and take it outdoors for inspection and cleaning Replace weak sections of connector Inspect t...

Страница 27: ...m the high lue temperatures Because the insulation is less dense than masonry the inner steel liner warms up more quickly than a masonry chimney this makes the steel chimney support a good draft more...

Страница 28: ...re All of the installation characteristics that adversely affect chimney draft also promote creosote condensation Consequently you can minimize creosote accumulation with an effective chim ney design...

Страница 29: ...Conclusion Woodburning is more an art than a science Art in cludes technique and since installations homes and fuel vary the stove operator must also vary technique mostly timing to achieve satisfyin...

Страница 30: ...he right to make changes in design materials speciications prices and discontinue colors and products at any time without notice Dutchwest Convection Heater Model 2478 Ref Description 2478 1 Bottom 30...

Страница 31: ...85 Door Gasket Front Ash and Load Doors 1203589 26 Kaowool 30004711 27 Inner Door 30004710 28 Wood Handle w Lifter 30002787 29 Load Door to June 2005 30002084 Load Door II replaces above 30002439 When...

Страница 32: ...r any fuel not recommended in the Owners Guide 4 This warranty does not cover a stove repaired by someone other than a Dutchwest Authorized Dealer 5 Damage to the unit while in transit is not covered...

Отзывы: