When connecting the power supply and after 15 s approx. warm-up time –stabilisation- the output sign goes from the minimum to the maximum 
to finally be stablished in the value corresponding to the existing gas concentration.

At 1.5 m over the horizontal points of gas consumption or smoke output avoiding air flows. It is not possible to interconnect detectors in serial 
or parallel.

  TECHNICAL CHARACTERISTICS

  FUNCTIONING

  INSTALLATION

FIDEGAS S/3-2

Detector for Explosive Gases

Calibrated with specific target gas to measure from 0 to 100% from L.E.I. (Low Explosive Limit)

Do not expose to SILICONE, TRCHLOROETHYLENE, SULPHUR DIOXIDE or HYDROGEN SULPHIDE,

otherwise it hill be damaged.

Voltage Supply

 

12V / 24V  CC

Consumption 

 

120 mA  12V CC / 65 mA  24V CC

Fault Alarm

 

0mA

Warming time

 

15 s

Type of Sensor

 

Catalítyc -Pellistor-

Useful life

 

4 years

Coverage area

 

15 m

2

Measurement range

 

From 0 to 100% L.E.L.

Response speed

 

T90 < 60 s

Working and/or storage temperature

 

From -5 to 50 ºC

Working and/or storage humidity

 

From 5 to 90% RH

Pressure Limits

 

From 95 to 110 kPa

Dimensions  -mm-

 

170 x 110 x 70  

Weight -gr-

 

950

Protection grade

 

I.P. 435

Code of Explosive Atmosphere

 

EEx d II C T6  

Detector for

 explosive gases 

that can be connected to 

EUROSONDELCO, SIEMENS CC62P

 -using interface-, 

FIDEGAS CA

 -ATEX Certificated- and 

any other system provided with 

4-20mA

 standard input 3 wires. The detector gives 4-20mA output proportional to the gas concentration in the 

range of 

0 to 100% L.E.L.

 -Low Explosive Limit- of the calibration gas.

EEx d II C T6

EN 50014: 1997 + A1: 1999 + A2: 1999

EN 50018: 2000 + A1: 2002

GAS

Height of Installation

Methane, Hydrogen, Acetylene, Ethylene, Ammonia (Exp)

15 cm from ceiling 

Butane, Propane, Isopropilic Alcohol, Hexane, Gasoline Octane

15 cm from floor