Connecting Terminal

Power ON LED
Diagnostic port

Connections and LED indicator

Important Notes

IMPORTANT: 

Assembly  /  maintenance  of  the  appliance  must  be  carried  out  by  qualified  personnel  and  in 

accordance with applicable laws and regulations. 

The manufacturer assumes no responsibility for the use of products that have to comply with particular 

environmental and / or installation standards.

IMPORTANT: 

Before connecting the equipment, it is recommended that you read the instruction manual

carefully and keep it for future reference. 

Electrical Connections

IMPORTANT: 

Before connecting to the mains power, ensure the voltage is correct. Carefully follow the 

instructions and the connections according to Regulations in force, keeping in mind that the signal cables should 

be laid separate from the power cables.

CONNECTING TERMINAL 

1. Positive Suplly Voltage

2. 0V

3. Return Sensor Voltage

POWER ON LED 

This LED illuminates Green when power is ON and the sensor has a power 

supply from the controller.

Flashing red indicates gas is being detected.

Constant red indicates alarm state.

Constant Amber indicates fault condition.

DIAGNOSTIC PORT

This can be connected to a A hand-held datalogger that can printout 

information about the sensor (serial number, powering up information, 

sensor condition, alarm activations, expected lifespan, auto adjusts made 

and the preset calibration state.

Tuning the Sensor to the Installation

Upon completion of the install measure the DC voltage between terminals 2 

and 3 in the sensor plug. This is located at the top right hand corner of the 

SGM595 printed circuit board. If the reading is not between 0.8 - 0.9vDC you 

will need to trim JP1.

JP1 is located on the PCB to the left of the PCB lower securing screw. Using 

a wire link briefly short the two terminals of JP1 until the power green LED 

flashes. When the power green LED flashes remove the link. Once the LED has 

stopped flashing recheck the voltage between terminals 2 and 3 on the sensor 

plug. If the voltage is still outside 0.8-0.9vDC conduct the procedure again.

 

Содержание SGM595

Страница 1: ...rise then the main alarm relay is activated to break the electrical supply to a safety shut off valve and is fixed at 20 LEL of Natural Gas or LPG The SGM595 microprocessor conducts both self diagnostics and automatically calibrates the sensor when ambient conditions vary thus avoiding false alarms SGM595 Natural Gas Propane Sensor 4 20mA IP55 Propane Natural Gas SPECIFICATION Power Power Supply 1...

Страница 2: ...maging the sensor Disabling the sensor or the controller must be carried out by a suitably trained technician Every year a more accurate check must be performed by qualified personnel Please call Duomo UK on 01905 797989 Overall Dimensions mm Important Notes IMPORTANT Assembly maintenance of the appliance must be carried out by qualified personnel and in accordance with applicable laws and regulat...

Страница 3: ...ON LED This LED illuminates Green when power is ON and the sensor has a power supply from the controller Flashing red indicates gas is being detected Constant red indicates alarm state Constant Amber indicates fault condition DIAGNOSTIC PORT This can be connected to a A hand held datalogger that can printout information about the sensor serial number powering up information sensor condition alarm ...

Страница 4: ...0V 230V 230V 230V 4 20mA Input Self Diagnostic Manual Test Internal Alarm Emergency Stop Function Alarm Stages Pre Alarm Main Alarm 1st Alarm 2nd Alarm Main Alarm 1st Alarm 2nd Alarm Main Alarm 1st Alarm 2nd Alarm Main Alarm 1st Alarm 2nd Alarm Main Alarm Pre Alarm Main Alarm O2 Monitoring Positive Safety IP Rating IP42 IP44 IP44 IP44 IP44 IP65 Extended Guarantee 3 Year 3 Year 3 Year 3 Year 3 Year...

Страница 5: ...tory on 01905 797989 or email us sales duomo co uk Important Notes Always check the wiring before powering up the system When replacing sensors never seperate a sensing head from its PCB The sensor will have been calibrated using this particular board and therefore will not function correctly with any other Do not test this sensor with anything other than Duomo test gas Concentrations above this w...

Страница 6: ...shooting and FAQs become apparent If your issue is not listed here please call Duomo UK on 01905 797989 and inform us so we can list your issue and associated solution here In case of alarm Extinguish any naked flames Do not switch lights or electrical devices on or off Open all windows and door to increase ventalation If the ALARM LED is off the levels of gas have dropped A responsible qualified ...

Страница 7: ...g is successful A Duomo Commissioning Certificate is provided A certificate from the original maufacturer ensures that the commisioning or servicing carried out is at a high professional standard by a competent and qualified service engineer It is prudent to make electrical connection to the detector terminal plus when withdrawn and leave the plug off the detector so that the Duomo Engineer is the...

Страница 8: ...cestershire WR9 9AH DuomoUK linkedin com company duomo uk SGM595 11032021 rev2 This document is protected by copyright No changes by others are permitted without prior authorisation by Duomo UK Ltd Duomo UK Ltd reserve the right to modify and revise this datasheet without notification GAS SAFETY CONTROLS ...

Отзывы: