background image

8

CONNECTING SUPPLY AND RETURN PIPING

 WARNING

Burn and scald hazard.  Safety relief valve could  

discharge steam or hot water during operation.  

Install discharge piping per these instructions.

!

     

Figure 2 -  Temperature Pressure Gauge 

1. 

Install discharge piping from safety relief valve. See 

Warning, Page 7.

2. 

Install temperature pressure gauge.

• Apply pipe sealant to threads on shaft of gauge.
• Thread gauge into supply water tee. See Figure 2.

NOTICE

Do not tighten gauge by hand. Gauge should be 

tightened using crescent wrench or 9/16” open end 

wrench. See Figure 2.

3. 

Connect supply and return lines to boiler. Connections 

may require additional fittings and parts, as shown on 

diagrams.  

4. 

Boiler is equipped with 1

 

1/4” supply and return 

connections on both left and right sides of boiler.

Verify clean water supply is available to water inlet valve. 

Install sand strainer when water supply is from a well or 

pump.
Install hot water boiler above radiation level or as 

required by Authority having jurisdiction install low water 

cutoff device at time of installation. Periodic inspection 

is necessary, as is flushing of float type devices, per 

manufacturers specific instruction.

FOR USE WITH COOLING UNITS

A.  Boiler used in connection with refrigeration system, 

must be installed so that chilled medium is piped in 

parallel with heating boiler. Appropriate valves must be 

used to prevent chilled medium from entering heating 

boiler. See Figure 4 page 9.

B.  Boiler connected to heating coils located in air handling 

units where they may be exposed to refrigerated air 

circulation, piping system shall be equipped with flow 

control valves or other automatic means to prevent 

gravity circulation of boiler water during cooling cycle. 

LOW WATER TEMPERATURE AND LARGE WATER 

CONTENT SYSTEM (

See Figures 5 and 6, Page 10.)

Significant condensation may form in boiler and/or 

venting system if boiler is operated for long period of 

time with return temperatures of less than 120

° F.

Condensate is corrosive and can cause severe 

damage to boiler and venting system. Minimum 

design return water temperature to prevent 

condensation in boiler and venting is 120°F.  

Minimum high limit setting is 140°F.

1. 

Boiler used in heating system where design water 

temperatures below 140°F are desired (e.g. radiant 

floor heating), 4-way mixing valve or suitable 

alternative is required to prevent low temperature low 

return water from entering boiler.  Follow mixing valve 

manufacturer’s instructions.

2. 

Boiler connected to system having large water content 

(such as former gravity system), install system bypass. 

See Figures 5 and 6, page 10.

3. 

Boiler water reset control is used to operate boiler, 

minimum reset supply water temperature setpoint 

must be at least 140°F, unless mixing valve is used as 

in (1) above.

Содержание WPSB SERIES II

Страница 1: ...PSB 3D WPSB 3DP WPSB 4D WPSB 4DP WPSB 5D WPSB 5DP WPSB 6D WPSB 6DP WPSB 7D WPSB 7DP WPSB 8D WPSB 8DP WPSB 9D WPSB 9DP Manufactured by ECR International Inc 2201 Dwyer Avenue Utica NY 13501 web site ww...

Страница 2: ...L NUMBER DIMENSIONS INCH Boiler Volume Gallon FLUE DIAMETER A WIDTH WPSB 3 5 11 6 3 WPSB 4 6 14 8 1 WPSB 5 6 17 9 9 WPSB 6 7 21 11 7 WPSB 7 7 24 13 5 WPSB 8 7 27 15 3 WPSB 9 7 30 17 2 Add 5 to height...

Страница 3: ...ckup requirements such as intermittent system operation extensive piping systems etc 3 MBH 1 000 Btuh British Thermal Unit Per Hour Ratings marked Net AHRI Ratings indicate amount of remaining heat in...

Страница 4: ...efore beginning installation WARNING Keep boiler area clear and free from combustible materials gasoline and other flammable vapors and liquids DO NOT obstruct air openings to the boiler room Modifica...

Страница 5: ...t of another appliance such as water heater 8 Accessibility clearances take precedence over fire protection clearances An 18 inch clearance should be maintained on any side where passage is required t...

Страница 6: ...opening commencing within 12 inches of top and second opening commencing within 12 inches of bottom of enclosure Direct communication with outdoors or communicating through vertical ducts Provide min...

Страница 7: ...f the relief valve outlet over the entire length of discharge line Have no intervening shutoff valve between safety relief valve and discharge to atmosphere do not plug or place any obstruction in dis...

Страница 8: ...d medium is piped in parallel with heating boiler Appropriate valves must be used to prevent chilled medium from entering heating boiler See Figure 4 page 9 B Boiler connected to heating coils located...

Страница 9: ...9 Figure 4 Chilled Water Piping Figure 3 Typical Hot Water Piping CONNECTING SUPPLY AND RETURN PIPING...

Страница 10: ...igure 5 Bypass Piping Circulator On Supply BYPASS PIPING REQUIRED FOR HIGH MASS LARGE WATER CONTENT SYSTEMS CONTROL Control CONNECTING SUPPLY AND RETURN PIPING Figure 6 Bypass Piping Circulator On Ret...

Страница 11: ...plug supplied with vent damper 1 Position furnished vent damper on top of flue outlet collar Fasten damper securely to flue outlet collar with sheet metal screws Verify damper blade has clearance to o...

Страница 12: ...bathroom exhausts so they will operate at maximum speed Do not operate a summer exhaust fan Close fireplace dampers 4 Place in operation the appliance being inspected Follow the lighting instructions...

Страница 13: ...or points to open position See Figure 9 Turn thermostat or controller down again and check damper position indicator returns to closed position Vent Damper Manual Operation Vent damper may be placed i...

Страница 14: ...h or serious injury Pressure test boiler and gas connection before placing boiler in operation Pressure test over 1 2 psig 3 5 kPa Disconnect boiler and its individual gas shutoff valve from gas suppl...

Страница 15: ...ighting fixtures televisions a fireplace or a chimney 4 Check thermostat operation by raising and lowering thermostat setting as required to start and stop the burners 5 Instructions for the final adj...

Страница 16: ...WIRING DIAGRAMS Figure 11 Electronic Ignition Control WARNING Modification substitution or elimination of factory equipped supplied or specified components may result in personal injury or loss of li...

Страница 17: ...at process Repeat until you have covered every radiation units in the system ending up at highest unit in system If your units have automatic vents this manual venting is unnecessary but it will speed...

Страница 18: ...a qualified service technician to inspect appliance and to replace any part of control system and any gas control which has been under water LIGHTING PROCEDURE FOR BOILER WITH INTERMITTENT PILOT SYST...

Страница 19: ...eset by turning thermostat to lowest setting for one minute then back to normal setting ADJUST PILOT BURNER Pilot flame should surround 3 8 to 1 2 of the pilot sensor See Figure 16 If flame needs adju...

Страница 20: ...egrees C After setting limit control to limit setting check to see if it shuts off gas supply to burners Turn your thermostat up to call for heat and let boiler run until temperature of water reaches...

Страница 21: ...by qualified service agency prior to resuming operation 4 ECONOMY Active Indicates thermal targeting function is active and limit control is reducing boiler temperature to conserve fuel Economy featu...

Страница 22: ...wiring diagram This insures domestic water calls are prioritized If cable 2 is not used turn Economy Feature OFF House will not get or stay warm 1 Check for air bound radiators 2 Check thermostat sett...

Страница 23: ...over current protection Verify electric power supply circuit is ON Controls out of adjustment Reset according to instructions Radiators not heating Open radiator vents to expel air Check flow control...

Страница 24: ...YSTEM If system is to remain out of service during freezing weather always drain it completely water left in to freeze will crack pipes and or boiler CLEANING YOUR BOILER AND BURNERS Flue passages bet...

Страница 25: ...the same as pressure produced in system by automatic fill valve When system is first filled tank will contain little or no water As water is heated its pressure increases It expands into tank compress...

Страница 26: ...h will pop up Blocked vent safety switch must be reset manually after switch has cooled off by pushing reset button down Check venting system and chimney for blockage when restoring system to operatin...

Страница 27: ...NOTES...

Страница 28: ...reases This feature is equipped with an override which is provided primarily to permit the use of an external energy management system that serves the same function THIS OVERRIDE MUST NOT BE USED UNLE...

Отзывы: