VENTILATION & COMBUSTION AIR

Provide combustion air and ventilation air in accordance 

with the section “Air for Combustion and Ventilation,” of 

the National Fuel Gas Code, ANSI Z223.1 / NFPA 54, or 

applicable provisions of local building codes. 

Provide make-up air where exhaust fans, clothes dryers, 

and kitchen ventilation equipment interfere with proper 

operation.
National Fuel Gas Code recognizes several methods 

of obtaining adequate ventilation and combustion air.  

Requirements of the authority having jurisdiction may 

override these methods.

• Engineered Installations.  Must be approved by 

authority having jurisdiction.

• Mechanical Air Supply.  Provide minimum of 0.35 

cfm per Mbh for all appliances located within space.  

Additional requirements where exhaust fans installed.  

Interlock each appliance to mechanical air supply 

system to prevent main burner operation when 

mechanical air supply system not operating.

• All Indoor Air.  Calculate minimum volume for all 

appliances in space.  Use a different method if 

minimum volume not available.
A.  Standard Method.  Cannot be used if known air 

infiltration rate is 0.40 air changes per hour.  See 

Table 3 for space with boiler only.  Use equation for 

multiple appliances.

Volume ≥ 50 ft

3

 x Total Input [Mbh]

B. 

Known Air Infiltration Rate.  See Table 3 for 

space with boiler only.  Use equation for multiple 

appliances.  Do not use an air infiltration rate 

(ACH) greater than 0.60.

Volume ≥

 

21 ft

3

⁄ACH x Total Input [Mbh] 

     

C.  Refer to National Fuel Gas Code for opening 

requirements between connected indoor spaces.

• All Outdoor Air.  Provide permanent opening(s) 

communicating directly or by ducts with outdoors.
A.  Two Permanent Opening Method.  Provide opening 

commencing within 12 inches of top and second 

opening commencing within 12 inches of bottom of 

enclosure.

 

…

Direct communication with outdoors or 

communicating through vertical ducts. Provide 

minimum free area of 1 in² per 4 Mbh of total 

input rating of all appliances in enclosure.

 

…

Communicating through horizontal ducts.  

Provide minimum free area of 1 in² per 2 

Mbh of total input rating of all appliances in 

enclosure.

B.  One Permanent Opening Method.  Provide opening 

commencing within 12 inches of top of enclosure.  

Provide minimum clearance of 1 inch on sides/back 

and 6 inches on front of boiler (does not supersede 

clearance to combustible materials).

• Refer to National Fuel Gas Code for additional 

requirements for louvers, grilles, screens and air ducts.

• Combination Indoor and Outdoor Air. Refer to National 

Fuel Gas Code for application information.

National Gas and Propane Installation Code Requires 

providing air supply in accordance with:

• Section 8.2 and 8.3 when combination of appliances 

has a total input of up to and including 400 Mbh (120 

kW).

• Section 8.4 when combination of appliances has total 

input exceeding 400 Mbh (120 kW).

• Refer to Natural Gas and Propane Installation Code 

for specific air supply requirements for enclosure 

or structure where boiler is installed, including air 

supply openings and ducts.

Table 3 - Minimum Room Volume, Indoor Air Only*

Input Mbh

Standard 

Method

Known Air Infiltration Rate Method ACH (Air Changes Per Hour)

0.1

0.2

0.3

0.4

0.5

0.6

75

3750

15750

7875

5250

3938

3150

2625

112.5

5625

23625

11813

7875

5906

4725

3938

150

7500

31500

15750

10500

7875

6300

5250

187.5

9375

39375

19688

13090

9844

7875

6563

255

11250

47250

23625

15750

11813

9450

7875

262.5

13125

55125

27563

18375

13781

11025

9188

299

14950

62790

31395

20930

15698

12558

10465

* Table values based on boiler only. Add volume for any additional appliances.

Содержание WPSB SERIES II

Страница 1: ...PSB 3D WPSB 3DP WPSB 4D WPSB 4DP WPSB 5D WPSB 5DP WPSB 6D WPSB 6DP WPSB 7D WPSB 7DP WPSB 8D WPSB 8DP WPSB 9D WPSB 9DP Manufactured by ECR International Inc 2201 Dwyer Avenue Utica NY 13501 web site ww...

Страница 2: ...L NUMBER DIMENSIONS INCH Boiler Volume Gallon FLUE DIAMETER A WIDTH WPSB 3 5 11 6 3 WPSB 4 6 14 8 1 WPSB 5 6 17 9 9 WPSB 6 7 21 11 7 WPSB 7 7 24 13 5 WPSB 8 7 27 15 3 WPSB 9 7 30 17 2 Add 5 to height...

Страница 3: ...ckup requirements such as intermittent system operation extensive piping systems etc 3 MBH 1 000 Btuh British Thermal Unit Per Hour Ratings marked Net AHRI Ratings indicate amount of remaining heat in...

Страница 4: ...efore beginning installation WARNING Keep boiler area clear and free from combustible materials gasoline and other flammable vapors and liquids DO NOT obstruct air openings to the boiler room Modifica...

Страница 5: ...t of another appliance such as water heater 8 Accessibility clearances take precedence over fire protection clearances An 18 inch clearance should be maintained on any side where passage is required t...

Страница 6: ...opening commencing within 12 inches of top and second opening commencing within 12 inches of bottom of enclosure Direct communication with outdoors or communicating through vertical ducts Provide min...

Страница 7: ...f the relief valve outlet over the entire length of discharge line Have no intervening shutoff valve between safety relief valve and discharge to atmosphere do not plug or place any obstruction in dis...

Страница 8: ...d medium is piped in parallel with heating boiler Appropriate valves must be used to prevent chilled medium from entering heating boiler See Figure 4 page 9 B Boiler connected to heating coils located...

Страница 9: ...9 Figure 4 Chilled Water Piping Figure 3 Typical Hot Water Piping CONNECTING SUPPLY AND RETURN PIPING...

Страница 10: ...igure 5 Bypass Piping Circulator On Supply BYPASS PIPING REQUIRED FOR HIGH MASS LARGE WATER CONTENT SYSTEMS CONTROL Control CONNECTING SUPPLY AND RETURN PIPING Figure 6 Bypass Piping Circulator On Ret...

Страница 11: ...plug supplied with vent damper 1 Position furnished vent damper on top of flue outlet collar Fasten damper securely to flue outlet collar with sheet metal screws Verify damper blade has clearance to o...

Страница 12: ...bathroom exhausts so they will operate at maximum speed Do not operate a summer exhaust fan Close fireplace dampers 4 Place in operation the appliance being inspected Follow the lighting instructions...

Страница 13: ...or points to open position See Figure 9 Turn thermostat or controller down again and check damper position indicator returns to closed position Vent Damper Manual Operation Vent damper may be placed i...

Страница 14: ...h or serious injury Pressure test boiler and gas connection before placing boiler in operation Pressure test over 1 2 psig 3 5 kPa Disconnect boiler and its individual gas shutoff valve from gas suppl...

Страница 15: ...ighting fixtures televisions a fireplace or a chimney 4 Check thermostat operation by raising and lowering thermostat setting as required to start and stop the burners 5 Instructions for the final adj...

Страница 16: ...WIRING DIAGRAMS Figure 11 Electronic Ignition Control WARNING Modification substitution or elimination of factory equipped supplied or specified components may result in personal injury or loss of li...

Страница 17: ...at process Repeat until you have covered every radiation units in the system ending up at highest unit in system If your units have automatic vents this manual venting is unnecessary but it will speed...

Страница 18: ...a qualified service technician to inspect appliance and to replace any part of control system and any gas control which has been under water LIGHTING PROCEDURE FOR BOILER WITH INTERMITTENT PILOT SYST...

Страница 19: ...eset by turning thermostat to lowest setting for one minute then back to normal setting ADJUST PILOT BURNER Pilot flame should surround 3 8 to 1 2 of the pilot sensor See Figure 16 If flame needs adju...

Страница 20: ...egrees C After setting limit control to limit setting check to see if it shuts off gas supply to burners Turn your thermostat up to call for heat and let boiler run until temperature of water reaches...

Страница 21: ...by qualified service agency prior to resuming operation 4 ECONOMY Active Indicates thermal targeting function is active and limit control is reducing boiler temperature to conserve fuel Economy featu...

Страница 22: ...wiring diagram This insures domestic water calls are prioritized If cable 2 is not used turn Economy Feature OFF House will not get or stay warm 1 Check for air bound radiators 2 Check thermostat sett...

Страница 23: ...over current protection Verify electric power supply circuit is ON Controls out of adjustment Reset according to instructions Radiators not heating Open radiator vents to expel air Check flow control...

Страница 24: ...YSTEM If system is to remain out of service during freezing weather always drain it completely water left in to freeze will crack pipes and or boiler CLEANING YOUR BOILER AND BURNERS Flue passages bet...

Страница 25: ...the same as pressure produced in system by automatic fill valve When system is first filled tank will contain little or no water As water is heated its pressure increases It expands into tank compress...

Страница 26: ...h will pop up Blocked vent safety switch must be reset manually after switch has cooled off by pushing reset button down Check venting system and chimney for blockage when restoring system to operatin...

Страница 27: ...NOTES...

Страница 28: ...reases This feature is equipped with an override which is provided primarily to permit the use of an external energy management system that serves the same function THIS OVERRIDE MUST NOT BE USED UNLE...

Отзывы: