Boilers connecting to gas vents or chimneys, vent 

installations shall be in accordance with “Venting of 

Equipment”, of the National Fuel Gas Code, ANSI Z223.1/

NFPA 54, or applicable provisions of local building codes.

Check Your Chimney

It must be clean, right size, properly constructed and in 

good condition.  

Chimney Sizing

Chimney sizing, and vent installation must be in accordance 

with the National Fuel Gas Code, ANSI Z223.1/NFPA 54, or 

applicable provisions of local building codes.

This is a high efficiency boiler with low stack temperature. 

Following recommendations are in addition to requirements 

of the National Fuel Gas Code.
1. Type B double wall vent pipe is recommended for 

vent connector. Single wall vent connectors should 

not be used unless following conditions are true:

a) Except for basement, boiler is not installed in 

unheated space.

b) Total horizontal portion of vent connector, not 

including elbows is less than 5 feet in length.

2. Outside chimneys (i.e. chimneys exposed to 

outdoors below roof line) should not be used unless 

they are:
a) enclosed in a chase, or

b) lined with type B vent pipe, or listed flexible 

vent liner, or other certified chimney lining system. 

3. Where possible it is recommended to common vent 

boiler and water heater.

4. For multiple boiler installations, consult boiler  

manufacturer for venting recommendations.

Connecting The Vent Damper And Vent Connector

Refer to Dimensions, page 2 for size and location of 

vent (flue opening). 

 

NOTICE

Damper blade on furnished vent damper has 1/2 

square inch hole (approximately 3/4” diameter). 

Boilers equipped with intermittent ignition, hole 

should be plugged by using plug supplied with vent 

damper.

1. 

Position furnished vent damper on top of flue outlet 

collar. Fasten damper securely to flue outlet collar with 

sheet metal screws. Verify damper blade has clearance 

to operate inside of diverter. Do not modify either draft 

diverter or vent damper during installation.

As An Option

Damper may be installed in a horizontal or 

vertical position, closer to flue outlet collar 

preferred. See Figures 7, 8 and 9, and Vent 

Damper Instructions.

2. 

Install vent damper to service only single boiler for 

which it is intended. Damper position indicator shall be 

in visible location following installation. Locate damper 

so it is accessible for servicing.

3. 

Damper must be in the open position when appliance 

main burners are operating.

4. 

Boiler is equipped with factory wired harness that plugs 

into vent damper.

5. 

Slope pipe up from boiler to chimney not less than 1/4” 

per foot.

6. 

Run pipe as directly as possible with as few elbows as 

possible.

7. 

Do not connect to fireplace flue.

8. 

End of vent pipe must be flush with inside face of 

chimney flue. Use a sealed-in thimble for chimney 

connection.

Sections of vent pipe should be fastened with sheet 

metal screws to make piping rigid. Horizontal potions of 

vent system must be supported to prevent sagging. Use 

stovepipe wires every 5’ to support pipe from above. If 

vent pipe must go through crawl space, double wall vent 

pipe should be used. Where vent pipe passes through 

combustible wall or partition, use ventilated metal thimble. 

Thimble should be 4 inches larger in diameter than vent 

pipe.

Minimum Vent Pipe Clearance

Wood and other combustible materials must not be closer 

than 6” from any surface of single wall metal vent pipe. 

Listed Type B vent pipe or other listed venting systems 

shall be installed in accordance with their listing.

CHIMNEY AND VENT PIPE CONNECTION

Содержание WPSB SERIES II

Страница 1: ...PSB 3D WPSB 3DP WPSB 4D WPSB 4DP WPSB 5D WPSB 5DP WPSB 6D WPSB 6DP WPSB 7D WPSB 7DP WPSB 8D WPSB 8DP WPSB 9D WPSB 9DP Manufactured by ECR International Inc 2201 Dwyer Avenue Utica NY 13501 web site ww...

Страница 2: ...L NUMBER DIMENSIONS INCH Boiler Volume Gallon FLUE DIAMETER A WIDTH WPSB 3 5 11 6 3 WPSB 4 6 14 8 1 WPSB 5 6 17 9 9 WPSB 6 7 21 11 7 WPSB 7 7 24 13 5 WPSB 8 7 27 15 3 WPSB 9 7 30 17 2 Add 5 to height...

Страница 3: ...ckup requirements such as intermittent system operation extensive piping systems etc 3 MBH 1 000 Btuh British Thermal Unit Per Hour Ratings marked Net AHRI Ratings indicate amount of remaining heat in...

Страница 4: ...efore beginning installation WARNING Keep boiler area clear and free from combustible materials gasoline and other flammable vapors and liquids DO NOT obstruct air openings to the boiler room Modifica...

Страница 5: ...t of another appliance such as water heater 8 Accessibility clearances take precedence over fire protection clearances An 18 inch clearance should be maintained on any side where passage is required t...

Страница 6: ...opening commencing within 12 inches of top and second opening commencing within 12 inches of bottom of enclosure Direct communication with outdoors or communicating through vertical ducts Provide min...

Страница 7: ...f the relief valve outlet over the entire length of discharge line Have no intervening shutoff valve between safety relief valve and discharge to atmosphere do not plug or place any obstruction in dis...

Страница 8: ...d medium is piped in parallel with heating boiler Appropriate valves must be used to prevent chilled medium from entering heating boiler See Figure 4 page 9 B Boiler connected to heating coils located...

Страница 9: ...9 Figure 4 Chilled Water Piping Figure 3 Typical Hot Water Piping CONNECTING SUPPLY AND RETURN PIPING...

Страница 10: ...igure 5 Bypass Piping Circulator On Supply BYPASS PIPING REQUIRED FOR HIGH MASS LARGE WATER CONTENT SYSTEMS CONTROL Control CONNECTING SUPPLY AND RETURN PIPING Figure 6 Bypass Piping Circulator On Ret...

Страница 11: ...plug supplied with vent damper 1 Position furnished vent damper on top of flue outlet collar Fasten damper securely to flue outlet collar with sheet metal screws Verify damper blade has clearance to o...

Страница 12: ...bathroom exhausts so they will operate at maximum speed Do not operate a summer exhaust fan Close fireplace dampers 4 Place in operation the appliance being inspected Follow the lighting instructions...

Страница 13: ...or points to open position See Figure 9 Turn thermostat or controller down again and check damper position indicator returns to closed position Vent Damper Manual Operation Vent damper may be placed i...

Страница 14: ...h or serious injury Pressure test boiler and gas connection before placing boiler in operation Pressure test over 1 2 psig 3 5 kPa Disconnect boiler and its individual gas shutoff valve from gas suppl...

Страница 15: ...ighting fixtures televisions a fireplace or a chimney 4 Check thermostat operation by raising and lowering thermostat setting as required to start and stop the burners 5 Instructions for the final adj...

Страница 16: ...WIRING DIAGRAMS Figure 11 Electronic Ignition Control WARNING Modification substitution or elimination of factory equipped supplied or specified components may result in personal injury or loss of li...

Страница 17: ...at process Repeat until you have covered every radiation units in the system ending up at highest unit in system If your units have automatic vents this manual venting is unnecessary but it will speed...

Страница 18: ...a qualified service technician to inspect appliance and to replace any part of control system and any gas control which has been under water LIGHTING PROCEDURE FOR BOILER WITH INTERMITTENT PILOT SYST...

Страница 19: ...eset by turning thermostat to lowest setting for one minute then back to normal setting ADJUST PILOT BURNER Pilot flame should surround 3 8 to 1 2 of the pilot sensor See Figure 16 If flame needs adju...

Страница 20: ...egrees C After setting limit control to limit setting check to see if it shuts off gas supply to burners Turn your thermostat up to call for heat and let boiler run until temperature of water reaches...

Страница 21: ...by qualified service agency prior to resuming operation 4 ECONOMY Active Indicates thermal targeting function is active and limit control is reducing boiler temperature to conserve fuel Economy featu...

Страница 22: ...wiring diagram This insures domestic water calls are prioritized If cable 2 is not used turn Economy Feature OFF House will not get or stay warm 1 Check for air bound radiators 2 Check thermostat sett...

Страница 23: ...over current protection Verify electric power supply circuit is ON Controls out of adjustment Reset according to instructions Radiators not heating Open radiator vents to expel air Check flow control...

Страница 24: ...YSTEM If system is to remain out of service during freezing weather always drain it completely water left in to freeze will crack pipes and or boiler CLEANING YOUR BOILER AND BURNERS Flue passages bet...

Страница 25: ...the same as pressure produced in system by automatic fill valve When system is first filled tank will contain little or no water As water is heated its pressure increases It expands into tank compress...

Страница 26: ...h will pop up Blocked vent safety switch must be reset manually after switch has cooled off by pushing reset button down Check venting system and chimney for blockage when restoring system to operatin...

Страница 27: ...NOTES...

Страница 28: ...reases This feature is equipped with an override which is provided primarily to permit the use of an external energy management system that serves the same function THIS OVERRIDE MUST NOT BE USED UNLE...

Отзывы: