Boiler Flue Passages
Under normal operating conditions, with the burners properly 

adjusted, it should not be necessary to clean the boiler fl ue 

gas passages. However, to assure trouble-free operation, we 

recommend that you have the fl ue passages, burner adjustment, 

and operation of the controls checked once each year by a 

competent Service Technician.
Before the start of each season (or whenever system has been 

shut down for some time) recheck the whole system for leaks 

and recheck the boiler and vent pipe for leaks. Replace or patch 

any boiler seals that are faulty.
Vent System
The venting of this unit is very important and should be checked 

at least once a season. If the vent piping shows any sign of 

leaking, replace it immediately. 
Water System
If system is to remain out of service during freezing weather, 

always drain it completely (water left in to freeze will crack the 

pipes and/or boiler).

Cleaning Your Boiler And Burners
Flue passages between sections should be examined yearly 

and cleaned if necessary. To clean, remove burners, pilot, and 

vent pipe, Remove top and front jacket panels. Remove the two 

screws attaching the intermediate front panel to the left and right 

side jacket panels. Remove the draft diverter and intermediate 

front panel as a unit. Carefully remove the cerafelt gasket strips. 

Clean passageways between sections with a fl exible handle wire 

brush. Remove dirt from bottom of boiler and from between 

sections by vacuuming. Make sure all fl ame ports in burners are 

open and clear. Shake out or blow out all loose dirt in burners. 

Reseal seams between adjacent sections as necessary with 400° 

F RTV silicone sealant. Reassemble all parts. Be sure to check 

tightness of pilot connections and condition of burner fl ames 

after reassembly (see Figures 20 and 21). Be sure vent 

pipe connections to chimney are secure and no obstructions are 

present.

MAINTAINING YOUR BOILER

SEQUENCE OF OPERATION

The Boiler uses an electronic control to maintain water 

temperature and to monitor the critical water level.  There 

are four (4) LED indicators that will display the mode of 

operation of the unit.

LOW WATER

RED

Low water condition

TSTAT

GREEN

Thermostat call for heat

HIGH LIMIT

YELLOW

Water temperature at high 

limit

ACTIVE

GREEN

Active, power to unit is on

There are four adjustable settings on the control. These can 

be adjusted using a small screw driver or by turning the 

adjusting post.  When power is applied to the unit all LED's 

will illuminate for a brief moment.  The Active LED will 

remain lit indicating that the control is powered and that 

the temperature function is active. The display will then 

cycle through the settings of the control.

CONTROL SETTINGS

Setting

Range (

o

F)

Factory 

setting

HIGH TEMPERATURE LIMIT (HL)

130°-220°

180°

HIGH TEMPERATURE              

DIFFERENTIAL (H df)

10°-30°

10°

LOW  TEMPERATURE                 

DIFFERENTIAL (LL)

10°-30°

10°

LOW TEMPERATURE LIMIT (L df)

OFF or 

110°-200°

OFF

PWXL with Electronic Ignition
Upon a call for heat the room thermostat will close the 

Green Thermostat LED will illuminate.  Power will be 

applied to the pump  circuit enabling the fl ow of water to 

the heating space.  The automatic vent damper will then 

begin to open.  When the vent damper is completely open 

the ignition module will start the ignition sequence.
At the start of the ignition sequence the pilot valve will 

open and the spark controller will light the pilot burner.  

Upon a successful proven pilot light the main gas valve will 

open allowing the main burners to light.  The burners will 

continue to fi re until the call for heat is satisfi ed and the 

thermostat opens or the water temperature in the boiler 

reaches the High Temperature Limit setting.
When the water temperature reaches the High Temperature 

Limit setting, while the thermostat is not satisfi ed, the 

Yellow LED will illuminate and the circulator pump circuit 

will remain energized.  The gas valve will close, shutting 

off the main burners.  While the thermostat is calling, if the 

water temperature falls below the High Temperature Limit 

setting (minus) the High Temperature differential setting, 

the ignition sequence will start again to maintain the boiler 

water temperature.
If the Low Temperature Limit is active (not set to OFF) 

the control will maintain a minimum water temperature 

allowing for warm start operation enabling the boiler to 

readily satisfy the heat load.
While the thermostat is NOT calling, the control will allow 

the burner to fi re until the boiler water temperature 

reaches the Low Temperature Limit setting (minus the Low 

Limit Differential).

Содержание PWXL

Страница 1: ...ed Company PWXL Cast Iron Gas Fired Hot Water Boilers INSTALLATION OPERATION MAINTENANCE MANUAL DUNKIRK BOILERS 2210 Dwyer Avenue Utica NY 13504 4729 Phone 315 797 1310 Fax 866 432 7329 e mail info ec...

Страница 2: ...e Operation 11 Vent Damper Operation 12 Gas Supply Piping 14 Electrical Wiring 16 Equipment and Optional Accessories 20 Starting the Boiler 21 Initial Operational Boiler Test Check Out Procedure 23 In...

Страница 3: ...n monoxide which is odorless and invisible CAUTION Indicates a hazardous situation which if not avoided may result in injury NOTICE Indicates information which should be followed to ensure proper inst...

Страница 4: ...by a change in main orifice size For altitudes above 2 000 feet above sea level input ratings should be reduced at the rate of 4 for each 1 000 feet above sea level Consult the latest edition of the N...

Страница 5: ...care must be taken to insure a clean combustion air supply during the construction process Airborne particulates such as from drywall dust and from fiberglass insulation can clog the burner ports flu...

Страница 6: ...crated boiler at selected location remove crate 2 by pulling crate sides from top and bottom boards This boiler must be set on non combustible floor or 3 optional non combustible Base Plate placed ove...

Страница 7: ...not use an air infiltration rate ACH greater than 0 60 Volume 21 ft3 ACH x Total Input Mbh Refer to National Fuel Gas Code for opening C requirements between connected indoor spaces All Outdoor Air Pr...

Страница 8: ...o avoid D reducing safety relief valve relieving capacity below minimum relief valve capacity stated on rating plate Run pipe as short and straight as possible to E location protecting user from scald...

Страница 9: ...or other automatic means to prevent gravity circulation of the boiler water during the cooling cycle Low Design Water Temperature Systems Below 140 If the boiler is to be used in a heating system wher...

Страница 10: ...ly Pipe Sealant On Shaft of Gauge Thread the gauge into the supply water tee as shown in 3 Figure 8 To Prevent damage do not overtighten Figure 8 Thread Gauge Into Supply Water Tee NOTICE IMPORTANT DO...

Страница 11: ...the 10 chimney height HT for single appliance venting see Figure 11 The sections of vent pipe should be fastened with sheet metal screws to make the piping rigid Horizontal portions of the vent syste...

Страница 12: ...damper on pipe curve Do not run wires near high temperature surfaces Use standoff brackets if necessary For safe efficient operation the vent damper and all flue product carrying areas of the applian...

Страница 13: ...l control the burner firing as before while the damper will remain open DO NOT turn damper open manually or motor damage will result Set switch to AUTOMATIC OPERATION to close vent damper during burne...

Страница 14: ...compound pipe dope suitable for liquefied petroleum gas Provide sediment trap upstream of gas valve See Figure 15 GAS SUPPLY PIPING CAUTION WHAT TO DO IF YOU SMELL GAS Do not try to light any applianc...

Страница 15: ...e using gas detector non corrosive detection fluid or other leak detection method acceptable to authority having jurisdiction Do not use matches candles open flames or other methods providing ignition...

Страница 16: ...r on a vertically mounted outlet box It should be sensing aver age room temperature THERMOSTAT LOCATIONS TO AVOID DEAD SPOTS HOT SPOTS COLD SPOTS Behind doors Concealed pipes Concealed pipes or ducts...

Страница 17: ...NOTES VENT DAMPER SHIPPED LOOSE IN CRATE VENT DAMPER HARNESS MUST BE CONNECTED TO VENT WHEN MOUNTED VENT DAMPER HARNESS Figure 16 1 Field Wiring Connections Circulator Pump Wiring Thermostat TW TR Re...

Страница 18: ...2 Wiring Diagram Electronic Ignition NOTICE If any of the original wire as supplied with this appliance must be replaced It must be replaced with type 105 C thermoplastic wire or it s equivalent ELECT...

Страница 19: ...16 3 Wiring Diagram Standing Pilot NOTICE If any of the original wire as supplied with this appliance must be replaced It must be replaced with type 105 C thermoplastic wire or it s equivalent ELECTRI...

Страница 20: ...re changes The diaphragm type tank can be mounted on the air purger fitting or at any convenient place in the supply or return line Air Eliminating Fitting Air Purger An air purger is used to remove e...

Страница 21: ...any phone in your building Immediately call your gas supplier from a neighbor s phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire department Use only yo...

Страница 22: ...Turn off all electric power to the appliance 3 Remove lower front panel 4 Rotate the gas control knob clockwise 5 to OFF See Figure 18 Wait five 5 minutes to clear out any gas Then smell 6 for gas inc...

Страница 23: ...rating and should go off when controls are tested When controls are reset burners should reignite o Test ignition system safety shutoff device after placing boiler in operation See page 25 o For multi...

Страница 24: ...er maintenance personnel Installation Location Customer Name __________________________________________________________________________ Address ________________________________________________________...

Страница 25: ...e inter mittent pilot control box The gas valve should shut off the main burners TURN OFF ELECTRIC POWER to boiler before reconnecting ignition cable to prevent electric shock Relight The electric and...

Страница 26: ...ntact an authorized contractor or qualified service technician to replace the relief valve and inspect the heating system to determine the cause as this may indicate an equipment malfunction This valv...

Страница 27: ...hermostat call for heat HIGH LIMIT YELLOW Water temperature at high limit ACTIVE GREEN Active power to unit is on There are four adjustable settings on the control These can be adjusted using a small...

Страница 28: ...mit setting For example if the High Temperature Limit is set at 1900 F with the High Temperature Differential at 200 F then the Low Temperature Limit needs to be set at 1700 F or lower If the settings...

Страница 29: ...er current protection Check to be sure electric power supply circuit is ON Controls out of adjustment Reset according to instructions Radiators not heating Open radiator vents to excess air Check flow...

Страница 30: ...NOTES...

Страница 31: ...Date Service Performed Company Name Tech Initials Company Address Phone...

Страница 32: ...DUNKIRK BOILERS 2201 Dwyer Avenue Utica NY 13504 4729 web site www ecrinternational com...

Отзывы: